Plan Review Details - Permit 00070261
Plan Review Stops For Permit 00070261
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-07 Cont ID  
Sent By drunnels Date 2000-09-07 Time 14:09 Rev Time 1.00
Received By drunnels Date 2000-09-07 Time 14:09 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
 STOREFRONT TO BE ISSUED UNDER SEPERATE
 PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-05 Cont ID  
Sent By drunnels Date 2000-09-05 Time 09:36 Rev Time 1.00
Received By drunnels Date 2000-09-05 Time 09:36 Sent To  
Notes
2001-01-08 00:00:001.OWNER/OWNER AGENT MUST SIGN FLORIDA
 ENERGY SHEETS
  
 ************** NOTE ******************
 STOREFRONT UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By drunnels Date 2000-08-03 Time 08:23 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. PROVIDE FLORIDA ENERGY CALULATIONS
 SIGNED AND SEALED WHERE NOTED
 2. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT GLAZING FOR STOREFRONT/ METRO
 DADE COUNTY OR SBCCI SSTD12-97
 3. SUBMIT FIRE SPRINKLER APPLICIATION
 AND PLANS, FIRE SPRINKLER PERMIT MUST BE
 ISSURED PRIOR TO ISSURANCE OF BUILDING
 PERMIT

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-07 Cont ID  
Sent By jleahy Date 2000-09-07 Time 13:52 Rev Time 0.45
Received By jleahy Date 2000-09-07 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 19:38 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 19:38 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE:PLEASE INSTALL MAIN DISC INLINE
 FROM BLD ELEC ROOM IN TENANT SPACE WITH
 TENANT EQUIPMENT.
  
 2)NOTE: PLEASE SEE TABLE 450-3B FOR
 CLARIFICATION ON MAIN BRKR RATING.
  
 3)NOTE: MORE THAN ONE WIRE SIZE IS SHOWN
 COMING FROM BLD ELECTRICAL ROOM TO
 TENANT SPACE??? PLEASE CLARIFY. SIZE PER
 310-16.
  
 4)NOTE: PLEASE INCLUDE TRACK LIGHTING
 IN LOAD CALCULATIONS/ PLEASE SHOW PER
 220-12B
  
 5)NOTE:PLEASE NOTE THAT RISER SHOWS
 125A MCB AND PANEL "L" SHOWS 100A MCB?
 PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REIVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELETRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-27 Cont ID  
Sent By mcarsill Date 2000-07-27 Time 08:57 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 WITH SPRINKLER DRAWINGS.
 2) AN ADDITIONAL EMERGENCY LIGHT
 REQUIRED IN MAIN FLOOR AREA.
 3) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 4) EXITING THROUGH STOCKROOM ALLOWED
 ONLY IF, NOT MORE THAN 50 PERCENT OF
 EXIT ACCESS PERMITTED, DOOR LEADING
 TO STOCKROOM CANNOT BE LOCKED, AISLE
 USED FOR EXITING SHALL BE AT LEAST
 44" WIDE, AND AISLE TO REMAIN IN
 UNOBSTRUCTED CONDITION.
 5) A PORTABLE FIRE EXTINGUISHER WITH
 A CURRENT SERVICE TAG IS TO BE
 PROVIDED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By ndenmark Date 2000-09-01 Time 13:41 Rev Time 0.33
Received By ndenmark Date 2000-09-01 Time 13:41 Sent To  
Notes
2001-01-08 00:00:00PRIOR MECHANICAL COMMENTS CORRECTED BY
 REVISION DATED 8/26/00

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By cthirben Date 2000-07-27 Time 17:56 Rev Time 1.00
Received By cthirben Date 2000-07-27 Time 17:46 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 PROVIDE LOCATION AND DETAILS OF DAMPERS
 AT RATED WALLS AS PER 1997 SMC 610.1.2..
 REQUIRE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2..
 PROVIDE OUTSIDE CALCULATION AS PER
 ASHRAE 62-89....
 PROVIDE EER RATING OF AHU AS PER FLORIDA
 ENERGY EFFICIENCY CODE,SMOKE DETECTOR
 IN DUCT, FAN SHUTDOWN AS PER NFPA 90A
 4.4.4.2 & 4.4.4.3...
 PROVIDE AHU MOUNTING DETAIL.
 REQUIRE DUCT MOUNTING DETAIL AND DIFFU-
 SER, FLEX CONNECTION DETAIL REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-31 Cont ID  
Sent By tlarge Date 2000-08-31 Time 19:47 Rev Time 0.33
Received By tlarge Date 2000-08-31 Time 19:42 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 HANDICAP ACCESSIBLE TOILET ROOMS SHALL
 BE INDELIBLY POSTED FOR THE INTENDED
 USE,BE ON AN ACCESSIBLE ROUTE AND BE
 AVAILABLE TO PATRONS WITHOUT RESTRICTION
 DURING NORMAL OPERATING HOURS.THE
 ACCESSIBLE ROUTE SHALL BE CLEARLY
 DEFINED ON THE PLANS.FACBC SEC.4.1,4.2,
 4.3,SPC WEC.407.2.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-29 Cont ID  
Sent By tlarge Date 2000-07-29 Time 08:11 Rev Time 0.75
Received By tlarge Date 2000-07-29 Time 08:11 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SQUARE FOOTAGE OF SPACE AND
 OCCUPANT LOAD PER SPC TABLE 407,407.1.3.
  
 A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3(10)(A).
  
 HANDICAP FACILITIES SHALL BE AVAILABLE
 TO THE PUBLIC AND BE ON AN ACCESSIBLE
 ROUTE PER FACBC SEC.4.1.3(11),4.3,SPC
 SEC.407.1.4,407.2.2.HANDICAP TOILET
 ROOMS SHALL BE INDELIBLY POSTED AND
 ACCESSIBLE WITHOUT RESTRICTION DURING
 OPERATING HOURS.
  
 A FLOOR DRAIN W/TRAP PRIMER IS REQD.IN
 THE TOILET ROOM PER SPC SEC.409.4.1.1.
 MIN.SIZE TO BE 3".