| Plan Review Stops For Permit 00070261 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-07 |
Time |
14:09 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-07 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | STOREFRONT TO BE ISSUED UNDER SEPERATE | | | PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-05 |
Time |
09:36 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-05 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.OWNER/OWNER AGENT MUST SIGN FLORIDA | | | ENERGY SHEETS | | | | | | ************** NOTE ****************** | | | STOREFRONT UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-03 |
Time |
08:23 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | 1. PROVIDE FLORIDA ENERGY CALULATIONS | | | SIGNED AND SEALED WHERE NOTED | | | 2. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT GLAZING FOR STOREFRONT/ METRO | | | DADE COUNTY OR SBCCI SSTD12-97 | | | 3. SUBMIT FIRE SPRINKLER APPLICIATION | | | AND PLANS, FIRE SPRINKLER PERMIT MUST BE | | | ISSURED PRIOR TO ISSURANCE OF BUILDING | | | PERMIT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-07 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-09-07 |
Time |
13:52 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2000-09-07 |
Time |
13:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
19:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
19:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE:PLEASE INSTALL MAIN DISC INLINE | | | FROM BLD ELEC ROOM IN TENANT SPACE WITH | | | TENANT EQUIPMENT. | | | | | | 2)NOTE: PLEASE SEE TABLE 450-3B FOR | | | CLARIFICATION ON MAIN BRKR RATING. | | | | | | 3)NOTE: MORE THAN ONE WIRE SIZE IS SHOWN | | | COMING FROM BLD ELECTRICAL ROOM TO | | | TENANT SPACE??? PLEASE CLARIFY. SIZE PER | | | 310-16. | | | | | | 4)NOTE: PLEASE INCLUDE TRACK LIGHTING | | | IN LOAD CALCULATIONS/ PLEASE SHOW PER | | | 220-12B | | | | | | 5)NOTE:PLEASE NOTE THAT RISER SHOWS | | | 125A MCB AND PANEL "L" SHOWS 100A MCB? | | | PLEASE ADJUST. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REIVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELETRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-27 |
Time |
08:57 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | WITH SPRINKLER DRAWINGS. | | | 2) AN ADDITIONAL EMERGENCY LIGHT | | | REQUIRED IN MAIN FLOOR AREA. | | | 3) INTERIOR FINISH SHALL BE CLASS A OR | | | B. | | | 4) EXITING THROUGH STOCKROOM ALLOWED | | | ONLY IF, NOT MORE THAN 50 PERCENT OF | | | EXIT ACCESS PERMITTED, DOOR LEADING | | | TO STOCKROOM CANNOT BE LOCKED, AISLE | | | USED FOR EXITING SHALL BE AT LEAST | | | 44" WIDE, AND AISLE TO REMAIN IN | | | UNOBSTRUCTED CONDITION. | | | 5) A PORTABLE FIRE EXTINGUISHER WITH | | | A CURRENT SERVICE TAG IS TO BE | | | PROVIDED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-01 |
Time |
13:41 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-09-01 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIOR MECHANICAL COMMENTS CORRECTED BY | | | REVISION DATED 8/26/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-27 |
Time |
17:56 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-27 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | PROVIDE LOCATION AND DETAILS OF DAMPERS | | | AT RATED WALLS AS PER 1997 SMC 610.1.2.. | | | REQUIRE AIR BALANCE SCHEDULE PER 1997 | | | SMC 501.2.. | | | PROVIDE OUTSIDE CALCULATION AS PER | | | ASHRAE 62-89.... | | | PROVIDE EER RATING OF AHU AS PER FLORIDA | | | ENERGY EFFICIENCY CODE,SMOKE DETECTOR | | | IN DUCT, FAN SHUTDOWN AS PER NFPA 90A | | | 4.4.4.2 & 4.4.4.3... | | | PROVIDE AHU MOUNTING DETAIL. | | | REQUIRE DUCT MOUNTING DETAIL AND DIFFU- | | | SER, FLEX CONNECTION DETAIL REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-31 |
Time |
19:47 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-31 |
Time |
19:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | HANDICAP ACCESSIBLE TOILET ROOMS SHALL | | | BE INDELIBLY POSTED FOR THE INTENDED | | | USE,BE ON AN ACCESSIBLE ROUTE AND BE | | | AVAILABLE TO PATRONS WITHOUT RESTRICTION | | | DURING NORMAL OPERATING HOURS.THE | | | ACCESSIBLE ROUTE SHALL BE CLEARLY | | | DEFINED ON THE PLANS.FACBC SEC.4.1,4.2, | | | 4.3,SPC WEC.407.2.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-29 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-29 |
Time |
08:11 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-07-29 |
Time |
08:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT SQUARE FOOTAGE OF SPACE AND | | | OCCUPANT LOAD PER SPC TABLE 407,407.1.3. | | | | | | A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | | W/FACBC SEC.4.1.3(10)(A). | | | | | | HANDICAP FACILITIES SHALL BE AVAILABLE | | | TO THE PUBLIC AND BE ON AN ACCESSIBLE | | | ROUTE PER FACBC SEC.4.1.3(11),4.3,SPC | | | SEC.407.1.4,407.2.2.HANDICAP TOILET | | | ROOMS SHALL BE INDELIBLY POSTED AND | | | ACCESSIBLE WITHOUT RESTRICTION DURING | | | OPERATING HOURS. | | | | | | A FLOOR DRAIN W/TRAP PRIMER IS REQD.IN | | | THE TOILET ROOM PER SPC SEC.409.4.1.1. | | | MIN.SIZE TO BE 3". |
|
|