Plan Review Details - Permit 00070157
Plan Review Stops For Permit 00070157
Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-11 Cont ID  
Sent By tlarge Date 2000-07-11 Time 14:16 Rev Time 0.30
Received By tlarge Date 2000-07-11 Time 14:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-10 Cont ID  
Sent By tlarge Date 2000-07-10 Time 18:20 Rev Time 0.33
Received By tlarge Date 2000-07-10 Time 18:20 Sent To  
Notes
2001-01-08 00:00:00HOW CAN YOU CARRY 454,000 BTU'S ON A
 3/4" LINE CONNECTED TO THE METER?
  
 MY CALCULATIONS SHOW 66' TO THE MOST
 REMOTE OUTLET.EXPLAIN HOW YOU CALCULATE
 102'.
  
 SIZE ALL CUT SECTIONS OF PIPE.SEE LINE
 TO POOL HEATER.
  
 REVIEW AND REVISE DRAWING TO COMPLY W/
 SGC.