Plan Review Details - Permit 00070149
Plan Review Stops For Permit 00070149
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-08-31 Cont ID  
Sent By dpalmer Date 2000-08-31 Time 10:50 Rev Time 0.00
Received By dpalmer Date 2000-08-31 Time 10:50 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-10-19 Cont ID  
Sent By jgomez Date 2000-10-19 Time 15:36 Rev Time 0.33
Received By jgomez Date 2000-10-19 Time 15:36 Sent To  
Notes
2001-01-08 00:00:00DOOR, WINDOW AND STORM PANELS PRODUCT
 APPROVAL.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By jgomez Date 2000-10-11 Time 17:53 Rev Time 1.00
Received By jgomez Date 2000-10-11 Time 17:53 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-WINDOW WITHIN 24" RADIUS FROM DOOR TO
 HAVE SAFETY GLASS. SEE PLANS.
 SECTION 2405.2 SBC 1997.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-08-30 Cont ID  
Sent By jgomez Date 2000-08-30 Time 20:26 Rev Time 1.50
Received By jgomez Date 2000-08-30 Time 20:26 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-BRING DRAWINGS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES WILL BE REQUIRED
 OR NOT. GET DRAWINGS STAMPED AND BRING
 RECEIPT TO THE CITY.
 2-FLOOR AT HABITABLE AREAS NEED TO BE
 MINIMUM 4" ABOVE THE FINISH GRADE.
 SECTION 1804.1.9 CITY AMENDMENTS TO
 STANDARD BUILDING CODE, 1997.
 PLEASE, SPECIFY HOW THE FLOOR IS GOING
 TO BE RAISED.
 3-WRITE THE NAME FOR THIS NEW ROOM AND
 SHOW ON DRAWINGS THE ADJACENT ROOMS
 ON BOTH SIDES. THIS IS TO VERIFY THAT
 NOT EGRESS WILL BE BLOCKED.
 4-PROVIDE COMPLETE FRAMING DETAILS AT
 OPENINGS TO RECEIVE STORM PANELS. SHOW
 REINFORCING TO RECEIVE STORM PANEL.
 SECTION 104.2.2 CITY AMENDMENTS.
 5-PRODUCT APPROVALS:
 -PROVIDE 2 COPIES OF EACH PRODUCT APP'L
 -FRENCH DOOR PRODUCT APPROVAL:
 *EXPIRED.
 *THIS PRODUCT APPROVAL IS FOR OUTSWING
 DOORS. DRAWINGS SHOW INSWING DOORS.
 BROWARD COUNTYPRODUCT APPROVALS ARE
 NOT ACCEPTED BY THIS OFFICE.
 -PROVIDE PRODUCT APPROVAL FOR WINDOWS.
 -STORM PANELS:
 *PROVIDE A KEY PLAN AND A COMPLETE
 INSTALLATION SCHEDULE (SEE SAMPLE
 ATTACHED).
 *HIGHLIGHT SPECIFIC MOUNTING CONDITION
 AND ANCHORS AND SPACING TO BE USED.
 6-SEE COMMENTS ON REVIEWED PLAN.
  
  
  
  
  
  
  
 NOTES:
 -PLEASE RETURN REVIEWED DRAWINGS AFTER
 CORRECTIONS ARE DONE TO THE ORIGINALS
 IN ORDER TO EXPEDITE THE REVIEW PROCESS
  
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CALL JULIO GOMEZ AT 659-8096
 EXT. 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-24 Cont ID  
Sent By gjoyce Date 2000-08-24 Time 09:36 Rev Time 0.10
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***