| Plan Review Stops For Permit 00070108 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-15 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-09-14 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-14 |
Time |
13:12 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | 2ND REVIEW | | | | | | PLEASE REFER TO ORIGINAL COMMENTS DATED | | | 9/5/00,SEE ATTACHED COPY. | | | | | | 1]OK | | | 2]OK | | | 3]SECTIONS AND DETAILS STILL DONT MATCH. | | | 4]RAMP LEADING TO DOOR#11.DOOR#2 SHALL | | | NOT BLOCK ACCESSIBLE MEANS OF EGRESS | | | PATH. | | | 5]OK | | | 6]EXPLAIN OPENING AT ORIGINAL DOOR#1 | | | LOCATION ? | | | 7]DETAIL DOOR#11 CONNECTION TO WOOD | | | FENCE,STEPS AND RAILING,WHAT TYPE OF | | | WALL WILL BE CONSTRUCTED NEXT TO DOORS | | | #12. | | | 8]PROVIDE TESTING FOR SKYLIGHTS. | | | 9]OK,ADDITION PLUMB. AND ELECT. INFO | | | REQUIRED. | | | 10]OK | | | ADDTIONAL COMMENTS: | | | 1]SUBMIT DOOR SCHEDULE. | | | 2]DETAIL OUTDOOR FLOORING. | | | 3]PROVIDE TESTING FOR NEW EXTERIOR DOORS | | | | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 659-8096#8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-09-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-05 |
Time |
10:05 |
Rev Time |
9.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | BUILDING COMMENTS | | | ------------------- | | | | | | 1] SUBMIT 2 COPIES OF CURRENT SIGNED AND | | | SEALED SURVEYS. | | | 2] LAYOUT OF REVISED SHEETS A1 AND A2 | | | SHALL MATCH REST OF PLANS. | | | 3] SECTIONS CALLED FOR ON FLOOR PLAN | | | SHALL MATCH DETAILS ON SH.A2. | | | 4] ALL RAMPS AND LANDINGS SHALL COM[LY | | | WITH SECTION 4.8 OF '97 FAC. | | | 5] DOORS #2 AND #8 SHALL COMPLY WITH | | | SECTION 4.13.6,FAC. | | | 6] DOOR #1 SHALL COMPLY WITH SECTION | | | 1012,'97 SBC,AS AN APPROVED EGRESS | | | TYPE DOOR. | | | 7] SUBMIT COMPLETE DETAILS FOR GARAGE | | | AREA. | | | 8] PROVIDE TESTING FOR SKYLIGHT ASSEMBLY | | | FOR WINDLOADING AND IMPACT PROTECTION | | | 9] PROVIDE DETAILS FOR WADING POOL. | | | 10] SUBMIT PLANS TO COUNTY IMPACT FEE | | | OFFICE,AND PROVIDE RECEIPT. | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 659-8096#8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-12 |
Time |
18:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-12 |
Time |
18:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-21 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
07:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS | | | SHOWING THE 125% FOR ALL CONTINUOUS LOAD | | | PLEASE SHOW SQ. FT FOR LOAD CALCS. | | | | | | 2)NOTE: PLEASE NOTE THAT AIC RATINGS ARE | | | SUBMITTED FOR PANELS, BUT STILL NEED TO | | | PROVIDE AIC RATING FOR MAIN DISCONNECT.L | | | AIC RATINGS ARE TO BE SUBMITTED FOR ALL | | | EQUIPMENT BEING INSTALLED. 110-9 | | | | | | 3)NOTE: PIPE FROM MAIN DISCONNECT TO | | | PANELS SHOW NO EQUIPMENT GROUNDING COND- | | | --UCTOR? IS THIS RIGID?PLEASE CLARIFY | | | | | | 4)NOTE: PLEASE SHOW ALL LOADING FOR | | | TRACK LIGHTING PER 220-12B | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-12 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-12 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) ALL EXIT DOORS SUBJECT TO AN | | | OCCUPANCY OF 50 OR MORE PERSONS TO | | | SWING IN THE DIRECTION OF EXIT TRAVEL. | | | 2) ALL EXIT DOORS SUBJECT TO AN | | | OCCUPANCY OF 100 OR MORE PERSONS IS | | | TO BE EQUIPPED WITH APPROVED PANIC | | | HARDWARE. | | | 3) PLEASE INDICATE MAIN EXIT LOCATION. | | | 4) INTERIOR FINISH TO BE AT LEAST | | | CLASS A, B, OR C. | | | 5) AWNINGS TO BE FIRE RETARDANT. PLEASE | | | SUBMIT FLAME CERTIFICATIONS. | | | 6) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 7) WATER FOUNTAIN CANNOT BE INSTALLED | | | OR OPERATED TO INTERFERE WITH EXIT | | | ACCESS TO ANY REQUIRED EXIT. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-25 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-25 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLAN REVIEWED BY CAPTAIN RHETT | | | TURNQUEST. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-22 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-22 |
Time |
14:46 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-12-22 |
Time |
14:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-13 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-13 |
Time |
11:42 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-09-13 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | | | | | | | | | | THE SPACE IS RECEIVING 5250 CFM OF | | | OUTSIDE AIR AND IS REMOVING VIA EXHAUST | | | FANS A TOTAL OF 5550 CFM. THIS WOULD PUT | | | THE SPACE IN A NEGATIVE CONDITION ACCORD | | | ING TO THE PLAN. FLORIDA ENERGY CODE | | | DOES NOT ACCEPT THIS CONDITION. ADJUST | | | VOLUME TO POSITIVE OR NEUTRAL CONDITION. | | | WITH THE RELIEF FAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-24 |
Time |
07:43 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-24 |
Time |
07:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 2. DUCT SMOKE DETECTOR TO BE TIED TO | | | HORN AND STROBE IF NO BLDG FIRE ALARM | | | FOR NOTIFICATION PER NFPA 90A 4-4.4 | | | NOTE: EXHAUST FANS TIED TO SWITCH SHALL | | | NOT BE USED AS PART OF AIR BALANCE SCHED | | | ULE REQUESTED ABOVE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-12-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-12-22 |
Time |
09:07 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-12-22 |
Time |
09:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-09-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-12 |
Time |
18:50 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-12 |
Time |
18:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | 1)WATER RISER DIAGRAM MISSING WATER | | | CLOSET IN WOMEN'S RESTROOM. | | | | | | 2)WATER CLOSET AND FIXTURE BRANCH NOT | | | PERMITTED ON WET VENT PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1.2 WATER | | | CLOSETS MAY BE VENTED PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.3. | | | | | | 3)SUBMIT REVISED SANITARY AND WATER | | | RISERS PRIOR TO PLUMBING INSPECTION. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 4)POOL PLANS THAT ARE SIGNED,SEALED AND | | | DATED BY A PROFESSIONAL ENGINEER | | | REGISTERED IN THE STATE OF FLORIDA SHALL | | | BE ROUTED TO THE PALM BEACH COUNTY | | | HEALTH DEPT.FOR REVIEW AND APPROVAL | | | PRIOR TO REVIEW BY THIS DEPARTMENT. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7 | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-09-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-10 |
Time |
10:30 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-10 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)PLANS SHALL BE ROUTED TO PALM BEACH | | | COUNTY HEALTH DEPT.FOR REVIEW AND | | | APPROVAL.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | 2)NUMBER OF WATER CLOSETS IN WOMEN'S RR | | | SHALL COMPLY W/TABLE 407 OF SPC.ED ON | | | THE OCCUPANT LOAD. | | | | | | 3)OVERFLOW REQD.ON CONDENSATE TO DRYWELL | | | TO ENSURE PROPER OPERATION/MAINTENANCE | | | OF SYSTEM.SMC SEC.304.8.3,SPC SEC.301.4. | | | | | | 4)PROTECTION AGAINST HAZARD AND NOISE IN | | | THE WATER DISTRIBUTION SYSTEM SHALL | | | COMPLY W/SPC 607.8.3.CALCULATED AIR | | | CHAMBERS SHALL BE EQUIPPED W/METHOD OF | | | RECHARGING AND BE ACCESSIBLE. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-19 |
Time |
05:37 |
Rev Time |
1.25 |
| Received By |
tlarge |
Date |
2000-08-19 |
Time |
05:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)PLANS SHALL BE ROUTED TO PALM BEACH | | | COUNTY HEALTH DEPT.FOR REVIEW AND | | | APPROVAL.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | 2)INDICATE THE NUMBER OF SEATS ON THE | | | PLANS(INTERIOR AND EXTERIOR)TO DETERMINE | | | MIN.FIXTURE REQS.PER TABLE 407. | | | | | | 3)PRIVACY SCREENS ARE REQD.FOR URINALS | | | PER SPC SEC.404.3 AND SHALL NOT EXTEND | | | BEYOND THE FRONT EDGE OF THE RIM PER | | | FACBC SEC.4.18.3.SHOW REQD.CLEAR FLOOR | | | SPACE FOR ACCESSIBLE URINAL. | | | | | | 4)OVER 2 FIXTURES ARE SUPPLIED BY 1/2" | | | C.W.COMPLY W/COUNTYWIDE AMENDMENTS SEC. | | | 607.7. | | | | | | 5)WATER CLOSETS ARE NOT PERMITTED ON WET | | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | | SEC.911.1.1. | | | | | | 6)OVERFLOW REQD.ON CONDENSATE DRAIN TO | | | ENSURE PROPER OPERATION/MAINTENANCE OF | | | SYSTEM.SPC SEC.301.4,SMC SEC.304.8.3. | | | | | | 7)PLEASE COMPILE PLANS INTO 2 COMPLETE | | | SETS. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-07-06 |
Time |
14:43 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NEEDS DMP REVIEW GVE TO JOE MINICOZZI |
|
|