Plan Review Details - Permit 00070108
Plan Review Stops For Permit 00070108
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-15 Cont ID  
Sent By lmartine Date 2000-09-15 Time 16:20 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-14 Cont ID  
Sent By lmartine Date 2000-09-14 Time 13:12 Rev Time 0.00
Received By lmartine Date   Time 16:04 Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 2ND REVIEW
  
 PLEASE REFER TO ORIGINAL COMMENTS DATED
 9/5/00,SEE ATTACHED COPY.
  
 1]OK
 2]OK
 3]SECTIONS AND DETAILS STILL DONT MATCH.
 4]RAMP LEADING TO DOOR#11.DOOR#2 SHALL
 NOT BLOCK ACCESSIBLE MEANS OF EGRESS
 PATH.
 5]OK
 6]EXPLAIN OPENING AT ORIGINAL DOOR#1
 LOCATION ?
 7]DETAIL DOOR#11 CONNECTION TO WOOD
 FENCE,STEPS AND RAILING,WHAT TYPE OF
 WALL WILL BE CONSTRUCTED NEXT TO DOORS
 #12.
 8]PROVIDE TESTING FOR SKYLIGHTS.
 9]OK,ADDITION PLUMB. AND ELECT. INFO
 REQUIRED.
 10]OK
 ADDTIONAL COMMENTS:
 1]SUBMIT DOOR SCHEDULE.
 2]DETAIL OUTDOOR FLOORING.
 3]PROVIDE TESTING FOR NEW EXTERIOR DOORS
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 659-8096#8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-09-05 Cont ID  
Sent By lmartine Date 2000-09-05 Time 10:05 Rev Time 9.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1] SUBMIT 2 COPIES OF CURRENT SIGNED AND
 SEALED SURVEYS.
 2] LAYOUT OF REVISED SHEETS A1 AND A2
 SHALL MATCH REST OF PLANS.
 3] SECTIONS CALLED FOR ON FLOOR PLAN
 SHALL MATCH DETAILS ON SH.A2.
 4] ALL RAMPS AND LANDINGS SHALL COM[LY
 WITH SECTION 4.8 OF '97 FAC.
 5] DOORS #2 AND #8 SHALL COMPLY WITH
 SECTION 4.13.6,FAC.
 6] DOOR #1 SHALL COMPLY WITH SECTION
 1012,'97 SBC,AS AN APPROVED EGRESS
 TYPE DOOR.
 7] SUBMIT COMPLETE DETAILS FOR GARAGE
 AREA.
 8] PROVIDE TESTING FOR SKYLIGHT ASSEMBLY
 FOR WINDLOADING AND IMPACT PROTECTION
 9] PROVIDE DETAILS FOR WADING POOL.
 10] SUBMIT PLANS TO COUNTY IMPACT FEE
 OFFICE,AND PROVIDE RECEIPT.
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096#8456

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 18:25 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 18:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 07:48 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 SHOWING THE 125% FOR ALL CONTINUOUS LOAD
 PLEASE SHOW SQ. FT FOR LOAD CALCS.
  
 2)NOTE: PLEASE NOTE THAT AIC RATINGS ARE
 SUBMITTED FOR PANELS, BUT STILL NEED TO
 PROVIDE AIC RATING FOR MAIN DISCONNECT.L
 AIC RATINGS ARE TO BE SUBMITTED FOR ALL
 EQUIPMENT BEING INSTALLED. 110-9
  
 3)NOTE: PIPE FROM MAIN DISCONNECT TO
 PANELS SHOW NO EQUIPMENT GROUNDING COND-
 --UCTOR? IS THIS RIGID?PLEASE CLARIFY
  
 4)NOTE: PLEASE SHOW ALL LOADING FOR
 TRACK LIGHTING PER 220-12B
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-12 Cont ID  
Sent By mcarsill Date 2000-09-12 Time 17:17 Rev Time 0.00
Received By mcarsill Date 2000-09-12 Time 17:17 Sent To  
Notes
2001-01-08 00:00:001) ALL EXIT DOORS SUBJECT TO AN
 OCCUPANCY OF 50 OR MORE PERSONS TO
 SWING IN THE DIRECTION OF EXIT TRAVEL.
 2) ALL EXIT DOORS SUBJECT TO AN
 OCCUPANCY OF 100 OR MORE PERSONS IS
 TO BE EQUIPPED WITH APPROVED PANIC
 HARDWARE.
 3) PLEASE INDICATE MAIN EXIT LOCATION.
 4) INTERIOR FINISH TO BE AT LEAST
 CLASS A, B, OR C.
 5) AWNINGS TO BE FIRE RETARDANT. PLEASE
 SUBMIT FLAME CERTIFICATIONS.
 6) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 7) WATER FOUNTAIN CANNOT BE INSTALLED
 OR OPERATED TO INTERFERE WITH EXIT
 ACCESS TO ANY REQUIRED EXIT.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 09:49 Rev Time 0.00
Received By mcarsill Date 2000-08-25 Time 09:49 Sent To  
Notes
2001-01-08 00:00:00PLAN REVIEWED BY CAPTAIN RHETT
 TURNQUEST.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-22 Cont ID  
Sent By ndenmark Date 2000-12-22 Time 14:46 Rev Time 0.33
Received By ndenmark Date 2000-12-22 Time 14:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-13 Cont ID  
Sent By ndenmark Date 2000-09-13 Time 11:42 Rev Time 0.33
Received By ndenmark Date 2000-09-13 Time 11:42 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
  
  
  
 THE SPACE IS RECEIVING 5250 CFM OF
 OUTSIDE AIR AND IS REMOVING VIA EXHAUST
 FANS A TOTAL OF 5550 CFM. THIS WOULD PUT
 THE SPACE IN A NEGATIVE CONDITION ACCORD
 ING TO THE PLAN. FLORIDA ENERGY CODE
 DOES NOT ACCEPT THIS CONDITION. ADJUST
 VOLUME TO POSITIVE OR NEUTRAL CONDITION.
 WITH THE RELIEF FAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 07:43 Rev Time 0.33
Received By ndenmark Date 2000-08-24 Time 07:43 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 2. DUCT SMOKE DETECTOR TO BE TIED TO
 HORN AND STROBE IF NO BLDG FIRE ALARM
 FOR NOTIFICATION PER NFPA 90A 4-4.4
 NOTE: EXHAUST FANS TIED TO SWITCH SHALL
 NOT BE USED AS PART OF AIR BALANCE SCHED
 ULE REQUESTED ABOVE

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-12-22 Cont ID  
Sent By jleech Date 2000-12-22 Time 09:07 Rev Time 0.50
Received By jleech Date 2000-12-22 Time 09:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By tlarge Date 2000-09-12 Time 18:50 Rev Time 0.65
Received By tlarge Date 2000-09-12 Time 18:50 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 1)WATER RISER DIAGRAM MISSING WATER
 CLOSET IN WOMEN'S RESTROOM.
  
 2)WATER CLOSET AND FIXTURE BRANCH NOT
 PERMITTED ON WET VENT PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.2 WATER
 CLOSETS MAY BE VENTED PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.3.
  
 3)SUBMIT REVISED SANITARY AND WATER
 RISERS PRIOR TO PLUMBING INSPECTION.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 4)POOL PLANS THAT ARE SIGNED,SEALED AND
 DATED BY A PROFESSIONAL ENGINEER
 REGISTERED IN THE STATE OF FLORIDA SHALL
 BE ROUTED TO THE PALM BEACH COUNTY
 HEALTH DEPT.FOR REVIEW AND APPROVAL
 PRIOR TO REVIEW BY THIS DEPARTMENT.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-10 Cont ID  
Sent By tlarge Date 2000-09-10 Time 10:30 Rev Time 0.65
Received By tlarge Date 2000-09-10 Time 10:15 Sent To  
Notes
2001-01-08 00:00:001)PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH DEPT.FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 2)NUMBER OF WATER CLOSETS IN WOMEN'S RR
 SHALL COMPLY W/TABLE 407 OF SPC.ED ON
 THE OCCUPANT LOAD.
  
 3)OVERFLOW REQD.ON CONDENSATE TO DRYWELL
 TO ENSURE PROPER OPERATION/MAINTENANCE
 OF SYSTEM.SMC SEC.304.8.3,SPC SEC.301.4.
  
 4)PROTECTION AGAINST HAZARD AND NOISE IN
 THE WATER DISTRIBUTION SYSTEM SHALL
 COMPLY W/SPC 607.8.3.CALCULATED AIR
 CHAMBERS SHALL BE EQUIPPED W/METHOD OF
 RECHARGING AND BE ACCESSIBLE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-19 Cont ID  
Sent By tlarge Date 2000-08-19 Time 05:37 Rev Time 1.25
Received By tlarge Date 2000-08-19 Time 05:12 Sent To  
Notes
2001-01-08 00:00:001)PLANS SHALL BE ROUTED TO PALM BEACH
 COUNTY HEALTH DEPT.FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 2)INDICATE THE NUMBER OF SEATS ON THE
 PLANS(INTERIOR AND EXTERIOR)TO DETERMINE
 MIN.FIXTURE REQS.PER TABLE 407.
  
 3)PRIVACY SCREENS ARE REQD.FOR URINALS
 PER SPC SEC.404.3 AND SHALL NOT EXTEND
 BEYOND THE FRONT EDGE OF THE RIM PER
 FACBC SEC.4.18.3.SHOW REQD.CLEAR FLOOR
 SPACE FOR ACCESSIBLE URINAL.
  
 4)OVER 2 FIXTURES ARE SUPPLIED BY 1/2"
 C.W.COMPLY W/COUNTYWIDE AMENDMENTS SEC.
 607.7.
  
 5)WATER CLOSETS ARE NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 6)OVERFLOW REQD.ON CONDENSATE DRAIN TO
 ENSURE PROPER OPERATION/MAINTENANCE OF
 SYSTEM.SPC SEC.301.4,SMC SEC.304.8.3.
  
 7)PLEASE COMPILE PLANS INTO 2 COMPLETE
 SETS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-16 Cont ID  
Sent By gjoyce Date 2000-07-06 Time 14:43 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS DMP REVIEW GVE TO JOE MINICOZZI