| Plan Review Stops For Permit 00061786 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-02 |
Time |
18:03 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | PRODUCT APPROVAL FOR IMPACT RESISTANT | | | WINDOW SYSTEM RECEIVED 8-2-00 | | | WINDOW PROVISO REMOVED FROM THIS PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-02 |
Time |
12:30 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | "POVISO" | | | | | | PROVIDE PRODUCT APPROVAL FOR WINDOW | | | GLAZING PER METRO DADE COUNTY OR SBCCI | | | SSTD12-97 | | | STOREFRONT REQUIRES SEPERATE PERMIT. | | | | | | NOTE: ALL 1 HOUR FIRE RATED TENANT | | | ASSEMBLIES (UL# U465) SHALL BE COMPLETED | | | PRIOR TO C.O. BEING ISSUED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-10-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-10-24 |
Time |
18:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-10-24 |
Time |
18:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
20:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
20:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-22 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-22 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
20:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
20:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-02 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-02 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PROVIDE FIRE ALARM SYSTEM SHOP | | | DRAWINGS FOR FIRE ALARM EQUIPMENT | | | SHOWN ON POWER PLAN. | | | 2) EXITING THROUGH STOCKROOM PERMITTED | | | IF THE FOLLOWING CONDITIONS EXIST, NOT | | | MORE THAN 50 PERCENT OF EXIT ACCESS | | | IS PROVIDED THROUGH STOCKROOM, AN AISLE | | | OF AT 44" WIDE TO BE PRESENT THROUGH | | | STOCKROOM, THE 44" AISLE IS TO BE | | | MAINTAINED, AND THE STOCKROOM CANNOT | | | BE LOCKED. | | | 3) AN ADDITIONAL EXIT SIGN MAY BE NEEDED | | | TO DIRECT PERSONS TO REAR EXIT DOOR IN | | | STOCKROOM. | | | FIRE PLAN REVIEW CONDUCTED BY ASST. | | | FIRE MARSHAL MIKE CARSILLO |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-01 |
Time |
12:28 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-01 |
Time |
12:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-22 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-22 |
Time |
12:42 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-09-22 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | INSTALL POINT OF USE WATER HEATER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-01 |
Time |
20:11 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-01 |
Time |
20:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | 1)SHT.A1-DRESSING ROOM SHALL COMPLY W/ | | | FACBC SEC.4.35.4.BENCH SHALL BE LOCATED | | | ALONG THE LONGER DIMENSION WALL. | | | | | | 2)WATER CLOSETS NOT PERMITTED WET VENTS | | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 911.1.1.SUBMIT REVISED SANITARY RISER | | | PRIOR TO PLUMBING INSPECTION. | | | | | | 3)POINT OF USE WATER HEATER SHALL BE | | | LISTED PER SPC 503.3. | | | | | | 4.)HANDICAP ACESSIBLE TOILET ROOMS SHALL | | | BE INDELIBLY POSTED FOR THE INTENDED | | | USE,BE ON AN ACCESSIBLE ROUTE,AND | | | AVAILABLE TO PATRONS DURING NORMAL | | | OPERATING HOURS.ACCESSIBLE ROUTE SHALL | | | BE CLEARLY DEFINED ON THE PLANS. | | | FACBC SECS.4.1.2(7),4.1.3.(16),4.1.3(11) | | | 4.2.1.,4.3.1,4.3.2(3),4.3.3. | | | SPC SEC.407.2.2. |
|
|