| Plan Review Stops For Permit 00061767 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-11 |
Time |
15:39 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: SUBMIT PRODUCT APPROVALS FOR | | | EXTERIOR WINDOWS AND DOOR FOR IMPACT | | | RESISTANT GLAZING. PAY FOR AND SECURE | | | SEPERATE PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-10 |
Time |
15:31 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SECOND REVIEW | | | LETTER FROM SPECIAL INSPECTOR NOT | | | SUPPLIED SECOND REQUEST. | | | | | | PROVISO: STORE FRONT REQUIRES ADDITIONAL | | | PERMITS AND FEES IF NOT SUBMITTED AND | | | APPROVED PRIOR TO ISSUSNCE OF PRIME | | | PERMIT. SECOND NOTICE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-25 |
Time |
14:02 |
Rev Time |
1.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | PLAN REVIEW: | | | | | | | | | 1)PROVIDE LETTER FROM SPECIAL INSPECTOR | | | THAT WORK IS READY TO BEGIN PRIOR TO | | | ISSUANCE OF THE BUILDING PERMIT. | | | 2)FIRE SPRINKLER CONTRACTOR MUST | | | SECURE PERMIT PRIOR TO ISSUANCE OF THE | | | BUILDING PERMIT. | | | 3)CHANGE SHEET A-1 NOTE A FROM SBC 1994 | | | TO SBC 1997 | | | | | | | | | ***************PROVISO****************** | | | | | | PROVIDE SBCCI OR METRO DADE PRODUCT | | | APPROVALS FOR IMPACT RESISTANT STORE | | | FRONT AND DOORS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-10 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-10 |
Time |
12:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-20 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-20 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: AS PER 450-13B TANSFORMER MAY | | | NOT BE INSTALLED IN CEILING SPACE ABOVE. | | | | | | 2)NOTE: CLARIFY WHEATER PANEL"A" IS | | | 200AMPS OR 225AMPS. | | | | | | 3)NOTE:FLOOR PLANS DO ONLY SHOW ONE | | | PANEL. RISER SHOW IT TO BE TWO SEPARATE | | | SECTIONS.? PLEASE CORRECT. | | | | | | 4)NOTE: PLEASE SEE 220-12 FOR THE REQ`D | | | LOAD CALCULATIONS TO BE SHOWN FOR TRACK | | | LIGHTING. | | | | | | 5)NOTE: PLEASE LABEL THE TRANSFORMER | | | GROUND AS GROUNDING ELECTRODE AND SIZE | | | PER 250-66 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-10 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-26 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR HYDRAULIC | | | CALCULATIONS PROVIDED WITH DRAWINGS. | | | 2) INTERIOR FINISH TO BE CLASS A OR B | | | ON WALLS AND CEILING. | | | 3) NO FIRE ALARM EQUIPMENT SHOWN ON | | | DRAWINGS. | | | 4) EXITING THROUGH STOCKROOM PERMITTED | | | IF, NOT MORE THAN 50 PERCENT OF EXIT | | | ACCESS IS PROVIDED THROUGH STOCKROOM, | | | THE STOCKROOM DOOR IS NOT SUBJECT TO | | | LOCKING, MAIN AISLE IN STOCKROOM SHALL | | | BE AT LEAST 44" WIDE, AND THIS AISLE IS | | | TO BE MAINTAINED. | | | 5) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 6) ADDITIONAL EMERGENCY LIGHTING MAY | | | BE NEEDED IN GALLERY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-10 |
Time |
13:32 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-10 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | FAN SHUTDOWN REQUIRED NOPTIFICATION OF | | | ACTIVATION OF DUCT SMOKE DETECTOR BY | | | VISUAL AND AUDIBLE SIGNAL. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-21 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-21 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-21 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 | | | 3.REQUIRES ENERGY EFFICIENCY RATING PER | | | FL. ENERGY EFFICIENCY CODE. | | | 4.PROVIDE ALL INFOFMATION ON THE AHU | | | UNIT ON SHEET M-2. | | | 5.INDICATE SMOKE DETECTOR PER 1997 SMC | | | 406.1 ON PLANS. | | | 6.REQUIRE DUCT MATERIAL SCHEDULE. | | | 7.PROVIDE EXHAUST FAN DETAIL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-11 |
Time |
15:53 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-08-11 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-09 |
Time |
17:49 |
Rev Time |
0.75 |
| Received By |
tlarge |
Date |
2000-08-09 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT OCCUPANT LOAD BASED ON SQUARE | | | FEET OF HABITABLE FLOOR SPACE.SEE SPC | | | SEC.407.1.3.FOR ALLOWED DEDUCTIBLE AREAS | | | | | | 2)AN ADDITIONAL LAVATORY IS REQD.IN THE | | | WOMEN'S TOILET ROOM PER SPC TABLE 407. | | | | | | 3)GRAB BAR BEHIND WATER CLOSETS SHALL BE | | | A MIN.OF 36" PER FACBC SEC.4.16.4. | | | | | | 4)A MIN. OF 29"IS REQD.UNDER LAV.FROM | | | FINISH FLOOR TO BOTTOM OF THE APRON. | | | FACBC SEC.4.19.2. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-22 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-22 |
Time |
08:57 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1A) SHT A-1 ACCESS TO H/C REST RM'S | | | THRU STORAGE RM IS NOT ACCESSIBLE TO | | | THE PUBLIC, AS REQUIRED BY | | | FACBS 4.1.3 (11) | | | (B) 1 D/F REQ SPC 94 TAB 407 TO COMPLY | | | W/FACBC 4.1.3 (10) (A) PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | (C) SEE CPPR FOR ADDITIONAL COMMENTS. | | | NOTE # 12 FOR TRAP SEAL, LAV WASTE IS | | | PERMITED. | | | END OF COMMENTS |
|
|