Plan Review Details - Permit 00061767
Plan Review Stops For Permit 00061767
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-11 Cont ID  
Sent By bstaples Date 2000-08-11 Time 15:39 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: SUBMIT PRODUCT APPROVALS FOR
 EXTERIOR WINDOWS AND DOOR FOR IMPACT
 RESISTANT GLAZING. PAY FOR AND SECURE
 SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-10 Cont ID  
Sent By bstaples Date 2000-08-10 Time 15:31 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SECOND REVIEW
 LETTER FROM SPECIAL INSPECTOR NOT
 SUPPLIED SECOND REQUEST.
  
 PROVISO: STORE FRONT REQUIRES ADDITIONAL
 PERMITS AND FEES IF NOT SUBMITTED AND
 APPROVED PRIOR TO ISSUSNCE OF PRIME
 PERMIT. SECOND NOTICE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By fknapp Date 2000-07-25 Time 14:02 Rev Time 1.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
 PLAN REVIEW:
  
  
 1)PROVIDE LETTER FROM SPECIAL INSPECTOR
 THAT WORK IS READY TO BEGIN PRIOR TO
 ISSUANCE OF THE BUILDING PERMIT.
 2)FIRE SPRINKLER CONTRACTOR MUST
 SECURE PERMIT PRIOR TO ISSUANCE OF THE
 BUILDING PERMIT.
 3)CHANGE SHEET A-1 NOTE A FROM SBC 1994
 TO SBC 1997
  
  
 ***************PROVISO******************
  
 PROVIDE SBCCI OR METRO DADE PRODUCT
 APPROVALS FOR IMPACT RESISTANT STORE
 FRONT AND DOORS.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By dpalmer Date 2000-08-10 Time 12:29 Rev Time 0.00
Received By dpalmer Date 2000-08-10 Time 12:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-20 Cont ID  
Sent By dpalmer Date 2000-07-20 Time 11:07 Rev Time 0.00
Received By dpalmer Date 2000-07-20 Time 11:07 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: AS PER 450-13B TANSFORMER MAY
 NOT BE INSTALLED IN CEILING SPACE ABOVE.
  
 2)NOTE: CLARIFY WHEATER PANEL"A" IS
 200AMPS OR 225AMPS.
  
 3)NOTE:FLOOR PLANS DO ONLY SHOW ONE
 PANEL. RISER SHOW IT TO BE TWO SEPARATE
 SECTIONS.? PLEASE CORRECT.
  
 4)NOTE: PLEASE SEE 220-12 FOR THE REQ`D
 LOAD CALCULATIONS TO BE SHOWN FOR TRACK
 LIGHTING.
  
 5)NOTE: PLEASE LABEL THE TRANSFORMER
 GROUND AS GROUNDING ELECTRODE AND SIZE
 PER 250-66
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 15:48 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By mcarsill Date 2000-07-26 Time 12:22 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED WITH DRAWINGS.
 2) INTERIOR FINISH TO BE CLASS A OR B
 ON WALLS AND CEILING.
 3) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS.
 4) EXITING THROUGH STOCKROOM PERMITTED
 IF, NOT MORE THAN 50 PERCENT OF EXIT
 ACCESS IS PROVIDED THROUGH STOCKROOM,
 THE STOCKROOM DOOR IS NOT SUBJECT TO
 LOCKING, MAIN AISLE IN STOCKROOM SHALL
 BE AT LEAST 44" WIDE, AND THIS AISLE IS
 TO BE MAINTAINED.
 5) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 6) ADDITIONAL EMERGENCY LIGHTING MAY
 BE NEEDED IN GALLERY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-10 Cont ID  
Sent By cthirben Date 2000-08-10 Time 13:32 Rev Time 1.00
Received By cthirben Date 2000-08-10 Time 13:29 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 FAN SHUTDOWN REQUIRED NOPTIFICATION OF
 ACTIVATION OF DUCT SMOKE DETECTOR BY
 VISUAL AND AUDIBLE SIGNAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-21 Cont ID  
Sent By cthirben Date 2000-07-21 Time 13:04 Rev Time 0.00
Received By cthirben Date 2000-07-21 Time 13:00 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 2.PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 3.REQUIRES ENERGY EFFICIENCY RATING PER
 FL. ENERGY EFFICIENCY CODE.
 4.PROVIDE ALL INFOFMATION ON THE AHU
 UNIT ON SHEET M-2.
 5.INDICATE SMOKE DETECTOR PER 1997 SMC
 406.1 ON PLANS.
 6.REQUIRE DUCT MATERIAL SCHEDULE.
 7.PROVIDE EXHAUST FAN DETAIL.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-11 Cont ID  
Sent By tlarge Date 2000-08-11 Time 15:53 Rev Time 0.30
Received By tlarge Date 2000-08-11 Time 15:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-09 Cont ID  
Sent By tlarge Date 2000-08-09 Time 17:49 Rev Time 0.75
Received By tlarge Date 2000-08-09 Time 17:17 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD BASED ON SQUARE
 FEET OF HABITABLE FLOOR SPACE.SEE SPC
 SEC.407.1.3.FOR ALLOWED DEDUCTIBLE AREAS
  
 2)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
  
 3)GRAB BAR BEHIND WATER CLOSETS SHALL BE
 A MIN.OF 36" PER FACBC SEC.4.16.4.
  
 4)A MIN. OF 29"IS REQD.UNDER LAV.FROM
 FINISH FLOOR TO BOTTOM OF THE APRON.
 FACBC SEC.4.19.2.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-22 Cont ID  
Sent By pschmitz Date 2000-07-22 Time 08:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1A) SHT A-1 ACCESS TO H/C REST RM'S
 THRU STORAGE RM IS NOT ACCESSIBLE TO
 THE PUBLIC, AS REQUIRED BY
 FACBS 4.1.3 (11)
 (B) 1 D/F REQ SPC 94 TAB 407 TO COMPLY
 W/FACBC 4.1.3 (10) (A) PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
 (C) SEE CPPR FOR ADDITIONAL COMMENTS.
 NOTE # 12 FOR TRAP SEAL, LAV WASTE IS
 PERMITED.
 END OF COMMENTS