Plan Review Details - Permit 00061747
Plan Review Stops For Permit 00061747
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 19:34 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 19:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By cthirben Date 2000-08-02 Time 16:50 Rev Time 1.00
Received By cthirben Date 2000-08-02 Time 16:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-01 Cont ID  
Sent By cthirben Date 2000-07-01 Time 12:36 Rev Time 1.00
Received By cthirben Date 2000-07-01 Time 12:36 Sent To  
Notes
2001-01-08 00:00:00DENIED: ********************************
 1. PROVIDE EXHAUST FANS FOR THE FOLLOW-
 ING AREAS: WATER-HEATER, GAS DRYER,
 COOKING RANGE,ALL BATHROOMS AS PER 1997
 SMC 503.3
 2.AHU #1 & AHU #2 INFORMATION NEEDS TO
 BE REVERSED

Review Stop P PLUMBING
Rev No 2 Status P Date 2001-02-21 Cont ID  
Sent By jleech Date 2001-02-21 Time 19:38 Rev Time 0.25
Received By jleech Date 2001-02-21 Time 19:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-02 Cont ID  
Sent By tlarge Date 2000-07-02 Time 08:00 Rev Time 0.33
Received By tlarge Date 2000-07-02 Time 08:00 Sent To  
Notes
2001-01-08 00:00:00SUBMIT REVISED SANITARY RISER THAT
 CORRELATES W/FLOOR PLAN PRIOR TO PLUMB-
 ING INSPECTION.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 GAS WATER HEATER SHALL BE PROTECTED FROM
 DAMAGE PER SGC 402.7.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-08-03 Cont ID  
Sent By jgomez Date 2000-08-03 Time 17:21 Rev Time 2.30
Received By jgomez Date 2000-08-03 Time 17:21 Sent To  
Notes
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PROVIDE SAFETY GLASS AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 2-SPECIFY SIZES OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BUILDING CONSTRUCTION,1997 ED
 3-PROVIDE PRODUCT APPROVAL FOR:
 -DOUBLE INSWING ENTRY DOORS.
 -FIREPLACE MEETING THE REQUIREMENTS OF
 UL 127. AND SECTION 2806 SBC 1997.
 -BUTT GLAZING ASSEMBLY.
 -WINDOW MULLIONS.
 -TRANSOM WINDOW WITH THE SIZE AS SHOWN
 ABOVE SLIDING GLASS DOORS AT LIVING RM
 -FRENCH DOOR AT MASTER SUITE.
 4-PROVIDE COMPLETE DETAIL/SPECIFICATIONS
 FOR CEILING CONSTRUCTION AT FRONT AND
 BACK PORCHES.
 NOTE: INCLUDE FASTENER TYPE & SPACING.
 SECTION 2504 SBC 1997.
 5-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 6-COMPLETELY SPECIFY INSTALLATION OF
 AHU IN ATTIC. INCLUDING THE HANGERS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By jgomez Date 2000-07-18 Time 19:37 Rev Time 2.50
Received By jgomez Date 2000-07-18 Time 19:37 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES.
 2-PROVIDE SAFETY GLASS AT BEDROOM #2.
 SECTION 2405.2 SBC 1997.
 3-REVISE ENERGY CALCULATIONS:
 -THERE ARE FOUR BEDROOMS, NOT THREE,
 SEE ARCHITECT'S PLANS.
 4-SPECIFY SIZES OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY EFFICIENCY
 CODE FOR BULDING CONSTRUCTION, 1997 ED
 5-PROVIDE PRODUCT APPROVAL FOR:
 -DOUBLE INSWING ENTRY DOORS.
 -FIREPLACE UL APPROVAL.
 -SLIDING GLASS DOORS WITH THE SIZE
 SHOWN AT LIVING ROOM.
 -BUTT GLAZING ASSEMBLY.
 -WINDOW MULLIONS.
 -TRANSOM WINDOW WITH THE SIZE AS SHOWN
 ABOVE SLIDING GLASS DOORS AT LIVING RM
 -FRENCH DOOR AT MASTER SUITE.
 6-CLARIFY CONSTRUCTION AT ENTRY DOORS:
 IS THERE A PRECAST LINTEL BETWEEN THE
 ENTRY DOORS AND ROUND TRANSOM ABOVE OR
 DOORS AND TRANSOM ARE PART OF THE SAME
 ASSEMBLY ?. IF SO, THEN NEED TO
 PROVIDE THE REQUIRED PRODUCT APPROVAL.
 7-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT FRONT AND BACK
 PORCHES. INCLUDING FASTENERS TYPES AND
 SPACING. SECTION 2504 SBC 1997.
 8-SEE PLANS FOR ADDITIONAL COMMENTS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 9-COMPLETELY SPECIFY INSTALLATION OF
 AHU IN ATTIC. INCLUDING THE HANGERS.
 10-OWES $199.39 TO THE CITY FOR LOW
 VALUATION AND RADON FEES.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXTENSION 8232.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-30 Cont ID  
Sent By gjoyce Date 2000-06-30 Time 15:29 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***