Plan Review Details - Permit 00061737
Plan Review Stops For Permit 00061737
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 18:14 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 18:14 Sent To  
Notes
2001-01-08 00:00:00************ SEE PLANS*****************
  
 1)NOTE: NOTES REDLINED ON PLANS. MISSING
 THE REQ`D SMOKE DETECTORS PER NFPA-72
 2-2.1.1.1
 MISSING OUTLET FOR HALLWAY PER 210-52H
 NOTES FOR BATH REQ`MENT 210-11-C-3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-11-02 Cont ID  
Sent By jleech Date 2000-11-02 Time 18:59 Rev Time 0.33
Received By jleech Date 2000-11-02 Time 18:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 08:07 Rev Time 0.33
Received By ndenmark Date 2000-08-24 Time 08:07 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 AREAS WITH 300 CFM OR GREATER SHALL
 PROVIDE FOR R/A FROM AREA

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By cthirben Date 2000-07-26 Time 15:07 Rev Time 1.00
Received By cthirben Date 2000-07-26 Time 15:07 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 NO MECHANICAL PLANS SUBMITTED FPR REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By tlarge Date 2000-08-01 Time 12:27 Rev Time 0.33
Received By tlarge Date 2000-08-01 Time 12:27 Sent To  
Notes
2001-01-08 00:00:00SUBMIT REVISED SANITARY RISER PRIOR TO
 PLUMBING INSPECTION.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-08-23 Cont ID  
Sent By fknapp Date 2000-08-23 Time 15:42 Rev Time 2.00
Received By fknapp Date 2000-08-23 Time 15:42 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ***************PROVISO******************
  
 PROVIDE STORM PANEL INFORMATION UNDER
 SEPARATE PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-08-01 Cont ID  
Sent By fknapp Date 2000-08-01 Time 11:41 Rev Time 4.00
Received By fknapp Date 2000-08-01 Time 11:41 Sent To  
Notes
2001-01-08 00:00:00 
  
  
 **********BUILDING UNSAT****************
  
  
 SBC 104.2.2
  
 1)PROVIDE ENERGY CALCULATIONS INCLUDING
 MANUEL J.
  
 2)PROVIDE 2 CURRENT COMPLETE COPIES OF
 SBCCI OR METRO DADE PRODUCT APPROVALS
 FOR:
 A)ALL NEW EXTERIOR DOORS
 B)ROOF TILE
 C)STORM PANELS WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS TO BE USED.
  
 3)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-30 Cont ID  
Sent By gjoyce Date 2000-06-30 Time 16:07 Rev Time 0.33
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***