Plan Review Details - Permit 00061704
Plan Review Stops For Permit 00061704
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-09 Cont ID  
Sent By dpalmer Date 2000-08-09 Time 07:19 Rev Time 0.00
Received By dpalmer Date 2000-08-09 Time 07:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-05 Cont ID  
Sent By dpalmer Date 2000-07-05 Time 10:49 Rev Time 0.00
Received By dpalmer Date 2000-07-05 Time 10:49 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT LOAD CALCULATION
 PER ART;220-3-C-1
 PLEASE SHOW EXISTING PANEL/ SERVICE SIZE
  
 2)NOTE: PLEASE SHOW THE REQ`D A/C COND.
 UNIT DISC. PER 440-11 AND THE GFI OUTLET
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-01 Cont ID  
Sent By cthirben Date 2000-07-01 Time 13:21 Rev Time 1.00
Received By cthirben Date 2000-07-01 Time 13:20 Sent To  
Notes
2001-01-08 00:00:00PROVISO:INDICATE RETURN AIR, PROVIDE
 INFORMATION ON RELOCATED AHU.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-02 Cont ID  
Sent By tlarge Date 2000-07-02 Time 07:53 Rev Time 0.25
Received By tlarge Date 2000-07-02 Time 07:53 Sent To  
Notes
2001-01-08 00:00:00NOPLUMBING THIS PERMIT.

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2000-08-18 Cont ID  
Sent By rmcdouga Date 2000-08-18 Time 16:49 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO
 1)PROVIDE PRODUCT APPROVALS FOR INSWING
 DOOR "D" AS SHOWN ON PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2000-08-10 Cont ID  
Sent By rmcdouga Date 2000-08-10 Time 14:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR INSWING
 EXTERIOR DOOR (D) AS SHOWN ON PLANS.
  
 2)ENERGY EFFICIENCY FORMS MUST BE SIGNED
 BY OWNER/AGENT.
  
 3)DESIGN COMPLIANCE FORM MUST HAVE WET
 SIGNATURE,DATE AND SEAL.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-07-28 Cont ID  
Sent By rmcdouga Date 2000-07-28 Time 13:07 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED
  
 1)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR SPECIFIC
 EXTERIOR WINDOWS AND DOORS TO BE USED.
  
 2)MISSLE IMPACT PROTECTION IS REQUIRED
 FOR ALL EXTERIOR GLAZING.CITY OF WPB
 AMENDMENTS TO THE 97 SBC SEC.1606.4.
 PROVIDE 2 COPIES OF METRO-DADE OR SBCCI
 PRODUCT APPROVALS,KEY PLAN AND INSTALL-
 ATION SCHEDULE WITH SPECIFIC TYPE ANCHOR
 TO BE USED FOR STORM PANELS.
  
 3)SUBMIT 2 COMPLETED CITY OF WPB DESIGN
 COMPLIANCE FORMS.1997 SBC OR ASCE 7-95.
  
 4)FL ENERGY EFFICIENCY CODE FORMS 600A-
 97 MUST BE SIGNED BY OWNER/AGENT.
  
 5)INDICATE ON PLANS LOCATION OF ATTIC
 ACCESS AND ATTIC VENTILATION. 97 SBC
 2309.6 AND 2309.7
  
 6)FINISH FLOOR ELEVATION MUST BE MINIMUM
 OF 6" ABOVE BASE FLOOD ELEVATION. CITY
 CODE CHAPTER 12. PROJECT IS LOCATED IN
 A5 FLOOD ZONE EL 7.
  
 7)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND A COPY
 OF THE RECIEPT SUBMITTED TO CITY OF WPB
 BUILDING DEPT. BEFORE A PERMIT TO
 CONSTRUCT WILL BE ISSUED.
  
 8)SAFETY GLASS IS REQUIRED IN THE
 WINDOWS ADJACENT TO DOORS C AND D ON
 PLAN. 97 SBC 2405.2.1
  
 9)INDICATE ON PLANS METHODS OF
 ATTACHMENT TO BE USED TO CONNECT STUDS
 TO TOP PLATES AND WOOD COLUMNS TO WOOD
 HEADERS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-30 Cont ID  
Sent By gjoyce Date 2000-06-30 Time 16:22 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***