Plan Review Details - Permit 00061693
Plan Review Stops For Permit 00061693
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-25 Cont ID  
Sent By drunnels Date 2000-08-25 Time 11:08 Rev Time 1.00
Received By drunnels Date 2000-08-25 Time 11:08 Sent To  
Notes
2001-01-08 00:00:00*************PROVISO*******************
 1.HURRICANE SHUTTERS TO REQUIRES
 SEPERATE PERMIT
 2.SIGNS REQUIRES SEPERATE PERMIT
 3.AWNING REQUIRES SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-18 Cont ID  
Sent By drunnels Date 2000-08-18 Time 09:30 Rev Time 1.00
Received By drunnels Date 2000-08-18 Time 09:30 Sent To  
Notes
2001-01-08 00:00:00 
 1.PROVIDE PRODUCT APPROVAL FOR HURRICANE
 SHUTTERS,SHOW LOCATION WHERE SHUTTERS
 ARE TO BE STORED, IF SHUTTERS STACKED ON
 END, SHUTTERS TO BE DESIGNED FOR
 ADDITIONAL LOADING, SUBMIT WHO AND HOW
 SHUTTERS ARE TO BE INSTALLED AND BY WHO
 FOR APPROVAL BY BUILDING OFFICIAL.
 2.SUBMIT FIRE SPRINKLER PLAND AND
 APPLICATION FOR PERMIT.
 NOTE: SIGNS AND AWNING ARE TO BE UNDER
 SEPERATE PERMITS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By drunnels Date 2000-07-26 Time 13:58 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
 1. SUBMIT LETTER FROM SPECIAL INSPECTOR
 2. FIRE SPRINKLER PERMIT MUST BE ISSUED
 PRIOR TO ISSURANCE OF PERMIT.
 3. BUILDING IS TYPE 2 CONSTRUCTION
 1997 SBC.
 4. FIRE MARSHALL TO GIVE DIRECTION OF
 FIRE EXTINGUISHER TYPE AND LOCATION.
 5. TITLE PAGE-GOVERNING CODES-CORRECT-
 SEE M/P/FP COMMENTS FOR LISTING
 6. PARTITION DETAIL 11A ON A.IA-TENTANT
 DEMISING WALL REQUIRED TO BE 1HR.
 RATED PROVIDE UL NUMBER.ASSEMBLY
 REQUIRED TO BE COMPLETED PRIOR TO C.O
 ONE SIDE COMPLETED AS SHOWN IS
 UNACCEPTABLE PER DETAIL.
 7. PROVIDE PRODUCT APPROVAL FOR
 HURRICANE SHUTTERS, SHOW LOCATION
 WHERE SHUTTERS ARE TO BE STORED, IF
 SHUTTERS STACKED ON END, SHUTTERS TO
 BE DESINGED FOR ADDITIONAL LOADING.
 8. COMPLY TO TABLE 407 OF THE SPC,
 SUBMIT SQUARE FOOTAGE OF HABITABLE
 FLOOR SPACE. REFER TO SECTION 407.1.3
 FOR ALLOWED DEDUCTIBLE AREAS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 15:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 20:25 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 20:25 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE ME-1, PLEASE NOTE
 YOU SHOW NO OVERCURRENT PROTECTION FOR
 A/C UNIT STARTER/DISC. PLEASE GIVE
 CLARIFICATION. #12`S ARE SHOWN WITH
 100 AMP OCP AT MAIN DISCONNECT.
  
 2)NOTE: PLEASE SEE ORIG NOTES FOR TRACK
 LIGHTING CALCULATIONS PER 220-12B
  
 3)NOTE: PLEASE SEE 210-62 FOR SHOW WIND-
 -OW RECEPTS. YOU SHOW ON SAME CIRCUITS
 WITH WALL OUTLETS. ALSO SEE 220-12A
  
 4)NOTE" PLEASE INDICATE SQ FT IN LOAD
 CALC. PER 220-3-A
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-19 Cont ID  
Sent By dpalmer Date 2000-07-19 Time 21:58 Rev Time 0.00
Received By dpalmer Date 2000-07-20 Time 08:44 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT A ONE LINED FOR
 ELETRICAL SERVICE. NO SERVICE SHOWN.??
  
 2)NOTE:SUBMIT AIC RATINGS FOR ALL MAINS/
 PANELS. ALL EQUIPMENT MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110-9
  
 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS.
 TO INCLUDE ALL CONTINUOUS LOADS AT 125%
 (LIGHTING ETC ) PER 220
 SHOW LOAD CALCULATIONS COMPLETED. 215-5
  
 4)NOTE: PLEASE SEE 220-12 FOR ALL TRACK
 LIGHTING LOADS TO BE SHOWN.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL .
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By mcarsill Date 2000-08-16 Time 14:17 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISHES SHALL BE CLASS A
 OR B IN ALL AREAS, NOT ONLY THE EXITS.
 2) FIRE SPRINKLER PERMIT ALREADY APPLIED
 FOR ON 6.23.00.
 3) PROVIDE FIRE ALARM SYSTEM DRAWINGS
 FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By mcarsill Date 2000-07-26 Time 11:16 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER PLANS OR HYDRAULIC
 CALCULATIONS PROVIDED.
 2) WRONG FIRE CODE REFERENCE, SHOULD
 READ NFPA 101, 1985 EDITION INSTEAD OF
 NFPA 101, 1991 EDITION.
 3) LOWER SOFFIT IN ENTRY AT 7'-1 AFF
 NOT PROPER. HEADROOM IN MEANS OF EGRESS
 SHALL BE 7'-6 OR 6'-8 IF PROJECTED FROM
 CEILING. PLEASE EXPLAIN SOFFIT.
 4) EXITING PERMITTED THRU STOCKROOM ONLY
 IF, NOT MORE THAN 50 PERCENT OF THE
 OCCUPANT LOAD PERMITTED THROUGH
 STOCKROOM.AISLE TO BE AT LEAST 44" WIDE
 AND MAINTAINED IN AN UNOBSTRUCTED
 CONDITION.
 5) INTERIOR FINISH TO BE CLASS A OR B.
 6) ENSURE EMERGENCY LIGHTING IS PROVIDED
 IN STOCKROOM.
 7) FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 14:56 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 14:56 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1. CONSENSATE FROM AIR HANDLING UNIT TO
 RUN FULL SIZE FROM UNIT TO STORM SEWER
 OR APPROVED FRENCH DRAIN. CITY UTILITY
 DEPT DOES NOT ALLOW CONDENSATE INTO
 CITY SANITARY SEWER SYSTEM. OVERFLOW
 PROTECTION FOR AHU REQUIRED BY 1997 SMC
 TOM CONSPICOUS LOCATION OR FLOAT SWITCH
 TO SHUT OFF UNIT IF PRIMARY DRAIN FAILS

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-19 Cont ID  
Sent By cthirben Date 2000-07-19 Time 12:13 Rev Time 0.00
Received By cthirben Date 2000-07-19 Time 13:01 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 REQUIRES OUTSIDE CALCULATIONS PER ASHRAE
 62-89.
 PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 PROVIDE THE ENERGY EFFICIENCY RATING OF
 AHU AND ENERGY CALCULATION SHEETS.
 NOTES:
 AUXILIARY DRAIN PAN SHALL HAVE A SEPERA-
 TE DRAIN LINE/SYSTEM 1997 SMC 504.8.6.1.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 18:41 Rev Time 0.33
Received By tlarge Date 2000-08-17 Time 18:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-04 Cont ID  
Sent By pschmitz Date 2000-08-04 Time 08:27 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PROVISO FOR 700 S. ROSEMARY
 AVE UNIT # 170
 (1) ACCESS TO PUBLIC REST RMTHRU A
 STORAGE AREA IS TO COMPLY W/FACBC SEC.4
 FOR ACCESSILE H/C REST RM'S.
 (2)SPC 94 TAB 407 ALLOWS 1 REST RM,WHEN
 COMMON FACILITIES ARE PROVIDED FOR IN
 THE COMMON AREA.
 (3) SHT M.1 H/C LAV SHOWS A FUNNEL ON
 THE WASTE LINE, ALL INDIRECT WASTE TO
 FLOOR SINKS, SPC SEC 802.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-04 Cont ID  
Sent By pschmitz Date 2000-07-20 Time 13:59 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A.1 ACCESS TO H/C REST RM THRU
 A STOCK RM,IS NOT ACCESSIBLE TO THE
 PUBLIC,AS REQUIRED IN FACBC 4.1.3(11).
 (2) SHT M.1 ALL INDIRECT WASTE TO FLR
 SINKS SPC SEC 807, SHOW PURPOSE OF
 FUNNEL DDAIN ON H/C LAV.
 END OF COMMENTS