| Plan Review Stops For Permit 00061693 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-25 |
Time |
11:08 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-25 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************PROVISO******************* | | | 1.HURRICANE SHUTTERS TO REQUIRES | | | SEPERATE PERMIT | | | 2.SIGNS REQUIRES SEPERATE PERMIT | | | 3.AWNING REQUIRES SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-18 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-18 |
Time |
09:30 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-18 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | 1.PROVIDE PRODUCT APPROVAL FOR HURRICANE | | | SHUTTERS,SHOW LOCATION WHERE SHUTTERS | | | ARE TO BE STORED, IF SHUTTERS STACKED ON | | | END, SHUTTERS TO BE DESIGNED FOR | | | ADDITIONAL LOADING, SUBMIT WHO AND HOW | | | SHUTTERS ARE TO BE INSTALLED AND BY WHO | | | FOR APPROVAL BY BUILDING OFFICIAL. | | | 2.SUBMIT FIRE SPRINKLER PLAND AND | | | APPLICATION FOR PERMIT. | | | NOTE: SIGNS AND AWNING ARE TO BE UNDER | | | SEPERATE PERMITS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-07-26 |
Time |
13:58 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | 1. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | 2. FIRE SPRINKLER PERMIT MUST BE ISSUED | | | PRIOR TO ISSURANCE OF PERMIT. | | | 3. BUILDING IS TYPE 2 CONSTRUCTION | | | 1997 SBC. | | | 4. FIRE MARSHALL TO GIVE DIRECTION OF | | | FIRE EXTINGUISHER TYPE AND LOCATION. | | | 5. TITLE PAGE-GOVERNING CODES-CORRECT- | | | SEE M/P/FP COMMENTS FOR LISTING | | | 6. PARTITION DETAIL 11A ON A.IA-TENTANT | | | DEMISING WALL REQUIRED TO BE 1HR. | | | RATED PROVIDE UL NUMBER.ASSEMBLY | | | REQUIRED TO BE COMPLETED PRIOR TO C.O | | | ONE SIDE COMPLETED AS SHOWN IS | | | UNACCEPTABLE PER DETAIL. | | | 7. PROVIDE PRODUCT APPROVAL FOR | | | HURRICANE SHUTTERS, SHOW LOCATION | | | WHERE SHUTTERS ARE TO BE STORED, IF | | | SHUTTERS STACKED ON END, SHUTTERS TO | | | BE DESINGED FOR ADDITIONAL LOADING. | | | 8. COMPLY TO TABLE 407 OF THE SPC, | | | SUBMIT SQUARE FOOTAGE OF HABITABLE | | | FLOOR SPACE. REFER TO SECTION 407.1.3 | | | FOR ALLOWED DEDUCTIBLE AREAS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-24 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-24 |
Time |
15:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-21 |
Time |
20:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
20:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE ME-1, PLEASE NOTE | | | YOU SHOW NO OVERCURRENT PROTECTION FOR | | | A/C UNIT STARTER/DISC. PLEASE GIVE | | | CLARIFICATION. #12`S ARE SHOWN WITH | | | 100 AMP OCP AT MAIN DISCONNECT. | | | | | | 2)NOTE: PLEASE SEE ORIG NOTES FOR TRACK | | | LIGHTING CALCULATIONS PER 220-12B | | | | | | 3)NOTE: PLEASE SEE 210-62 FOR SHOW WIND- | | | -OW RECEPTS. YOU SHOW ON SAME CIRCUITS | | | WITH WALL OUTLETS. ALSO SEE 220-12A | | | | | | 4)NOTE" PLEASE INDICATE SQ FT IN LOAD | | | CALC. PER 220-3-A | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-19 |
Time |
21:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-20 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT A ONE LINED FOR | | | ELETRICAL SERVICE. NO SERVICE SHOWN.?? | | | | | | 2)NOTE:SUBMIT AIC RATINGS FOR ALL MAINS/ | | | PANELS. ALL EQUIPMENT MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT. 110-9 | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS. | | | TO INCLUDE ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING ETC ) PER 220 | | | SHOW LOAD CALCULATIONS COMPLETED. 215-5 | | | | | | 4)NOTE: PLEASE SEE 220-12 FOR ALL TRACK | | | LIGHTING LOADS TO BE SHOWN. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL . | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-16 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISHES SHALL BE CLASS A | | | OR B IN ALL AREAS, NOT ONLY THE EXITS. | | | 2) FIRE SPRINKLER PERMIT ALREADY APPLIED | | | FOR ON 6.23.00. | | | 3) PROVIDE FIRE ALARM SYSTEM DRAWINGS | | | FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-26 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR HYDRAULIC | | | CALCULATIONS PROVIDED. | | | 2) WRONG FIRE CODE REFERENCE, SHOULD | | | READ NFPA 101, 1985 EDITION INSTEAD OF | | | NFPA 101, 1991 EDITION. | | | 3) LOWER SOFFIT IN ENTRY AT 7'-1 AFF | | | NOT PROPER. HEADROOM IN MEANS OF EGRESS | | | SHALL BE 7'-6 OR 6'-8 IF PROJECTED FROM | | | CEILING. PLEASE EXPLAIN SOFFIT. | | | 4) EXITING PERMITTED THRU STOCKROOM ONLY | | | IF, NOT MORE THAN 50 PERCENT OF THE | | | OCCUPANT LOAD PERMITTED THROUGH | | | STOCKROOM.AISLE TO BE AT LEAST 44" WIDE | | | AND MAINTAINED IN AN UNOBSTRUCTED | | | CONDITION. | | | 5) INTERIOR FINISH TO BE CLASS A OR B. | | | 6) ENSURE EMERGENCY LIGHTING IS PROVIDED | | | IN STOCKROOM. | | | 7) FIRE EXTINGUISHERS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
14:56 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. CONSENSATE FROM AIR HANDLING UNIT TO | | | RUN FULL SIZE FROM UNIT TO STORM SEWER | | | OR APPROVED FRENCH DRAIN. CITY UTILITY | | | DEPT DOES NOT ALLOW CONDENSATE INTO | | | CITY SANITARY SEWER SYSTEM. OVERFLOW | | | PROTECTION FOR AHU REQUIRED BY 1997 SMC | | | TOM CONSPICOUS LOCATION OR FLOAT SWITCH | | | TO SHUT OFF UNIT IF PRIMARY DRAIN FAILS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-19 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-19 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | REQUIRES OUTSIDE CALCULATIONS PER ASHRAE | | | 62-89. | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2.. | | | PROVIDE THE ENERGY EFFICIENCY RATING OF | | | AHU AND ENERGY CALCULATION SHEETS. | | | NOTES: | | | AUXILIARY DRAIN PAN SHALL HAVE A SEPERA- | | | TE DRAIN LINE/SYSTEM 1997 SMC 504.8.6.1. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-17 |
Time |
18:41 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-17 |
Time |
18:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-04 |
Time |
08:27 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PROVISO FOR 700 S. ROSEMARY | | | AVE UNIT # 170 | | | (1) ACCESS TO PUBLIC REST RMTHRU A | | | STORAGE AREA IS TO COMPLY W/FACBC SEC.4 | | | FOR ACCESSILE H/C REST RM'S. | | | (2)SPC 94 TAB 407 ALLOWS 1 REST RM,WHEN | | | COMMON FACILITIES ARE PROVIDED FOR IN | | | THE COMMON AREA. | | | (3) SHT M.1 H/C LAV SHOWS A FUNNEL ON | | | THE WASTE LINE, ALL INDIRECT WASTE TO | | | FLOOR SINKS, SPC SEC 802. | | | END OF COMMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-08-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-20 |
Time |
13:59 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A.1 ACCESS TO H/C REST RM THRU | | | A STOCK RM,IS NOT ACCESSIBLE TO THE | | | PUBLIC,AS REQUIRED IN FACBC 4.1.3(11). | | | (2) SHT M.1 ALL INDIRECT WASTE TO FLR | | | SINKS SPC SEC 807, SHOW PURPOSE OF | | | FUNNEL DDAIN ON H/C LAV. | | | END OF COMMENTS |
|
|