Plan Review Details - Permit 00061675
Plan Review Stops For Permit 00061675
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By drunnels Date 2000-10-11 Time 07:35 Rev Time 1.50
Received By drunnels Date 2000-10-11 Time 07:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-31 Cont ID  
Sent By hpiskura Date 2000-07-31 Time 15:25 Rev Time 2.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2001-09-13 Cont ID  
Sent By dpalmer Date 2001-09-13 Time 16:35 Rev Time 0.00
Received By dpalmer Date 2001-09-13 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-26 Cont ID  
Sent By dpalmer Date 2000-09-26 Time 11:16 Rev Time 0.00
Received By dpalmer Date 2000-09-26 Time 11:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 06:14 Rev Time 0.00
Received By dpalmer Date 2000-07-27 Time 06:14 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE COMPLETE LOAD CALCULATION
 -S. SHOW ALL CONTINUOUS LOADS AT 125%
 (LIGHTING) ETC.
 ALSO SHOW TRACK LIGHTING FIGURED INTO
 CALCS PER 220-12
  
 2)NOTE: PLEASE SEE 210-62 FOR SHOW
 WINDOW RECEPT REQ`MENTS AND TO BE
 CALCULATED PER 220-12
  
 3)NOTE: ALL ELECTRICAL BEING SHOWN ON
 FLOOR PLAN,,, IS ALL THIS NEW? WHAT IS
 EXISTING? KITCHEN AREA?
  
 4)NOTE: PLEASE NOTE OUTLETS IN KITCHEN
 AND BATH AREA TO BE GFI/GFI PROTECTED.
 PER 210-8
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-10-13 Cont ID  
Sent By lmartine Date 2000-10-13 Time 11:04 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLAN APPROVED 8/8/00 BY RHETTLM

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-01-08 Cont ID  
Sent By ndenmark Date 2001-01-08 Time 10:53 Rev Time 0.33
Received By ndenmark Date 2001-01-08 Time 10:53 Sent To  
Notes
2001-01-08 00:00:00THIS MECHANICAL REVISION IS FOR PHASE 1
 ONLY. NEW ENGINEER OF RECORD.SEE LETTER
 INCLUDED WITH PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By ndenmark Date 2000-09-21 Time 14:43 Rev Time 0.75
Received By ndenmark Date 2000-09-21 Time 14:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 18:56 Rev Time 1.00
Received By cthirben Date 2000-07-18 Time 18:44 Sent To  
Notes
2001-01-08 00:00:00DENIED:*********************************
 1.PROVIDE DAMPER LOCATION PER 1997 SMC
 610.1.2.ALSO DAMPER DETAIL.
 2.PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2..
 3.PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89.
 4.REQUIRE DUCT MATERIAL SCHEDULE.
 5.REQUIRE FLEX DUCT CONNECTION DETAIL.
 6.LOCAL CODE REQUIRES MIN. 18" OF CLEAR-
 ANCE BETWEEN ROOF SURFACE AND BOTTOM OF
 SUPPORT BEAM OF STAND.

Review Stop P PLUMBING
Rev No 4 Status F Date 2001-01-05 Cont ID  
Sent By jleech Date 2001-01-05 Time 07:33 Rev Time 1.00
Received By jleech Date 2001-01-05 Time 07:33 Sent To  
Notes
2001-01-08 00:00:00DENIED;
  
 1.SHT. P-1 DELETE DRAINAGE LAYOUT. NOT
 THE SAME AS P-2.
  
 2.SHT. P-1 DELETE SANITARY RISER
 DIAGRAM. WOMEN ROOMS ARE SHOWN ON P-3
 RISER DIAGRAM.P-1 DRAWING IS STILL
 NEEDED TO SHOW CHANGE IN TRAP PRIMER.
  
 3.ADD NOTE ON P-2 BY DRINKING FOUNTAIN
 (PROVIDE CUP DISPENSER).
  
 4.SHOW SHOWER DRAIN ON SANITARY LINE
 DRAWING, P-2.
  
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-13 Cont ID  
Sent By tlarge Date 2000-10-13 Time 11:08 Rev Time 0.50
Received By tlarge Date 2000-10-13 Time 11:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-16 Cont ID  
Sent By tlarge Date 2000-09-16 Time .8:15 Rev Time 1.25
Received By tlarge Date 2000-09-16 Time 07:45 Sent To  
Notes
2001-01-08 00:00:001)RM.123-DOOR CANNOT SWING INTO CLEAR
 FLOOR SPACE REQD.FOR THE LAVATORY PER
 FACBC SEC.4.22.2.
  
 2)SINK IN CONCESSION AREA SHALL BE H.C.
 ACCESSIBLE PER FACBC SEC.4,24.1-4.24.7.
  
 3)FLOOR DRAINS ARE REQD.IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 4)WALLS AND FLOORS IN TOILET ROOMS SHALL
 BE NONABSORBENT PER SBC SEC.1204.2.
  
 5)SHOW REQD.WHEELCHAIR TURNING SPACE IN
 TOILET ROOMS PER FACBC SEC.4.2.3.
  
 6)PLANS SHOW WOMEN'S TOILET ROOM IN
 ELECTRONICS RETAIL SALES AREA.CLEARLY
 SHOW HOW MALE PATRONS WILL HAVE FREE
 ACCESS TO MALE TOILET ROOM.
  
 7)NOTE OCCUPANT LOAD ON PLANS USING SPC
 TABLE 407 AS A GUIDE.SEE SPC SEC.407.1.3
 FOR ALLOWED DEDUCTIBLE AREAS.
  
 8)CALCULATED AIR CHAMBERS SHALL COMPLY
 W/SPC SEC.607.8.3,607.8.4.IF USED.
  
 9)SHT.P-3-PROVIDE SHIP'S LADDER IN
 CONJUNCTION W/PLATFORM FOR WATER HEATER
 PER SPC 501.7.
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-23 Cont ID  
Sent By pschmitz Date 2000-07-23 Time 11:31 Rev Time 0.00
Received By tlarge Date 2000-09-16 Time 07:43 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1)SHT.A.1 SPC 94 MIN FACILITIES,TAB 407
 MEN1 W/C WOMEN 2 W/C
 MEN1 LAV WOMEN 2 LAVS
 DRINKING FOUNTAIN 1
 REST RM'S TO COMPLY W/FACBC 4.1.3 (11)
 D/F TO COMPLY WITH 4.1.3 (10) PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
 (2)SHT P0.1 ICE MACHINE DETAIL,
 SEPERATE CUBBER DRAIN & ICE BIB DRAIN.
 SPC 94 SEC 606.1 CROSSCONNECTION
 (3) SHT P-3 WATER HEATER TO BE READLY
 ACCESSIBLE SPC 94 SEC 501.7 RELOCATE TO
 FLOOR OR PROVIDE A FIXED SHIPS LADDER &
 WORKING PLATFORM.
 (4) SHT P3-1SHOW LOCATION OF BACK
 FLOW PREVENTER AS REQUIRED BY LOCAL
 ORDINANCE #2853-95
  
 (5) SHT P0.1 GAS WATER HEATER DETAIL
 DIELECTRIC UNIONS NOT APPROVED IN WATER
 SUPPLY SYSTEM,USE DIELECTRIC NIPPLES OR
 COUPLINGS.SPC 94 SEC 611.2 MATERIALS A/G
 (6) SHT P0.1 IF DETAILS SHOWN,DO NOT
 APPLY,DELETE OR VOID THEM.
 END OF COMMENTS