| Plan Review Stops For Permit 00061611 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-23 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-23 |
Time |
11:22 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-23 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO***************** | | | | | | 1.STOREFRONT TO BE UNDER SEPERATE PERMIT | | | 2.SIGNS TO BE UNDER SEPERATE PERMIT. | | | 3.TENANT SEPERATION WALL TO BE COMPLETED | | | PRIOR TO C.O. BEING ISSUED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-03 |
Time |
14:57 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-03 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | | | | | | | | | | 1. PROVIDE PRODUCT APPROVAL FOR IMPACT | | | RESISTANT WINDOWS & DOORS FOR STOREFRONT | | | METRO DADE COUNTY OR SBCCI SSTD12-97 | | | 2. SUBMIT FIRE SPRINKLER APPLICATION AND | | | PLANS.FIRE SPRINKLER PERMIT MUST BE | | | ISSUED PRIOR TO BUILDING PERMIT BEING | | | ISSUED. | | | 3. SIGNS SHALL BE UNDER SEPERATE PERMIT. | | | 4. SHEET S-1 GENERAL NOTES REFERS TO | | | 1994 SBC MUST BE 1997 SBC. | | | 5. SUBMIT DETAIL SHOWING TENANT FIRE | | | SEPERATION UL RATING PER 1997 SBC | | | CHAPTER 7 TABLE 704.1. TENANT SEPERATION | | | WALL TO BE COMPLETED PRIOR TO C.O. BEING | | | ISSUED. | | | 6. ALL WOOD USED IN FRAMING SHALL BE | | | FIRE RESISTANT TREATED TO COMPLY WITH | | | 1997 SBC CHAPTERS 6&7. | | | 7. HEALTH DEPARTMENT APPROVAL REQUIRED | | | PRIOR TO PERMIT BEING ISSUED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-21 |
Time |
20:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
20:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-31 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-31 |
Time |
17:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE CLARIFY PANEL "HA" YOU | | | SHOW 155 AMP LOAD ON 225 AMP PANEL WITH | | | 150 AMP MCB. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-22 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-22 |
Time |
08:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | APPROVED PROVISO | | | 1) INTERIOR FINISH TO BE CLASS A OR B. | | | 2) ENSURE THAT ADEQUATE EMERGENCY | | | LIGHTING FIXTURES ARE PRESENT IN THE | | | DINING AND RETAIL AREA. | | | 3) ENTIRE SPACE IS TO BE FIRE SPRINKLER | | | PROTECTED INCLUDING THE WALK-IN COOLER. | | | 4) PROVIDE FIRE ALARM SYSTEM DRAWINGS | | | FOR FIRE ALARM DEVICES SHOWN ON PLANS. | | | A SEPARATE PERMIT IS REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-07-26 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER SYSTEM DRAWINGS OR | | | HYDRAULIC CALCULATIONS PROVIDED WITH | | | PLANS. | | | 2) EXPLAIN USE FOR 12 GALLON KETTLE. | | | 3) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 4) PROVIDE SHOP DRAWINGS AND SEPARATE | | | PERMIT FOR FIRE ALARM EQUIPMENT | | | INSTALLATION. | | | 5) PORTABLE FIRE EXTINGUISHERS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-03 |
Time |
10:59 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-03 |
Time |
10:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | *LOCAL CODE REQUIRES 18" MIN. CLEARANCE | | | BETWEEN ROOF FINISH AND BOTTOM OF THE | | | SUPPORT BEAM OF THE A/C STAND ON PLANS. | | | *SEPERATE PERMIT IS REQUIRED FOR HOOD, | | | GAS, FIRE SUPPRESSION, WALK-IN COOLERS/ | | | FREEZERS WHERE IT'S APPLICABLE... |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-30 |
Time |
09:38 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-30 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-21 |
Time |
20:58 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-08-21 |
Time |
19:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)PROVIDE GAS ISOMETRIC FOR REVIEW.SEE | | | ATTACHED REQS.FOR PLAN REVIEW. | | | | | | 2)SHT.P-5.DELETE REFERENCE TO UPC.PLUMB- | | | ING INSTALLATION SHALL COMPLY W/STANDARD | | | PLUMBING CODE 1994 EDITION. | | | | | | 3)SHT.P-5.GREASY WASTE SHALL COMPLY W/ | | | SPC SEC.921 FOR HORIZONTAL COMBINATION | | | WASTE AND VENT SYSTEM.(A REFERENCE NOTE | | | ON THE PLAN DOESN'T CORRECT THE | | | VIOLATIONS IN THE DESIGN.) | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-21 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-21 |
Time |
09:21 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A1.2 H/C REST RM, TO COMPLY WITH | | | FACBC 4.16.2 FIG 28,TURNING RADIUS RUNS | | | INTO DOOR, MOVE LAV FOR 36" CLEARANC OF | | | WALL,TO ALLOW TURNING RADIUS TO CLEAR | | | DOOR SWING. | | | (2) SHT P2 DISHWASHER 21 TO BY PASS G/W, | | | AND CONNECT TO SANITARY SEWER , LOCAL | | | ORDINANCE FOR REGIONAL SEWER PLANT. | | | (3) SHT P2 NOTE "H" ALL INDIRECT WASTE, | | | FLOOR SINKS.NO F/D'S | | | (3) SHT P3GEN NOTE #7 CONDENSATE | | | DRAIN FROM COOLER, FLR SINK,NO F/D. | | | (4) SHT P4 WTR HTR, DIELECTRIC UNIONS | | | NOT APPROVED, USE DIELECTRIC NIPPLES OR | | | COUPLINGS SPC SEC 611.2 MATERIALS A/G. | | | (5) SHT P4 PROVIDE GAS ISMETRIC, SHOW | | | TOTAL DEVELOPED LGTH,TOT. BTU'S, BTU'S | | | OF EA APPLIANCE, TYPE OF PIPING MATERIAL | | | GAS PSI USED. SGC 97 SEC 104.2 | | | (6) SHT P6 G/W WASTE & VENT, | | | HORIZONTAL DRY VENTS NOT PERMITED,USE | | | SPC 94 SEC921 COMBINATION WASTE, VENT. | | | SEE ILLUSTRATION PG 275 SPC 94. | | | (7) SEE OTHER COMMENTS BY CPPR. | | | END OF COMMENTS |
|
|