Plan Review Details - Permit 00061611
Plan Review Stops For Permit 00061611
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-23 Cont ID  
Sent By drunnels Date 2000-08-23 Time 11:22 Rev Time 1.00
Received By drunnels Date 2000-08-23 Time 11:22 Sent To  
Notes
2001-01-08 00:00:00***************PROVISO*****************
  
 1.STOREFRONT TO BE UNDER SEPERATE PERMIT
 2.SIGNS TO BE UNDER SEPERATE PERMIT.
 3.TENANT SEPERATION WALL TO BE COMPLETED
 PRIOR TO C.O. BEING ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By drunnels Date 2000-08-03 Time 14:57 Rev Time 1.00
Received By drunnels Date 2000-08-03 Time 14:56 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
  
  
  
 1. PROVIDE PRODUCT APPROVAL FOR IMPACT
 RESISTANT WINDOWS & DOORS FOR STOREFRONT
 METRO DADE COUNTY OR SBCCI SSTD12-97
 2. SUBMIT FIRE SPRINKLER APPLICATION AND
 PLANS.FIRE SPRINKLER PERMIT MUST BE
 ISSUED PRIOR TO BUILDING PERMIT BEING
 ISSUED.
 3. SIGNS SHALL BE UNDER SEPERATE PERMIT.
 4. SHEET S-1 GENERAL NOTES REFERS TO
 1994 SBC MUST BE 1997 SBC.
 5. SUBMIT DETAIL SHOWING TENANT FIRE
 SEPERATION UL RATING PER 1997 SBC
 CHAPTER 7 TABLE 704.1. TENANT SEPERATION
 WALL TO BE COMPLETED PRIOR TO C.O. BEING
 ISSUED.
 6. ALL WOOD USED IN FRAMING SHALL BE
 FIRE RESISTANT TREATED TO COMPLY WITH
 1997 SBC CHAPTERS 6&7.
 7. HEALTH DEPARTMENT APPROVAL REQUIRED
 PRIOR TO PERMIT BEING ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 20:53 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 20:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 17:48 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 17:48 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY PANEL "HA" YOU
 SHOW 155 AMP LOAD ON 225 AMP PANEL WITH
 150 AMP MCB.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-22 Cont ID  
Sent By mcarsill Date 2000-08-22 Time 08:32 Rev Time 0.00
Received By mcarsill Date 2000-08-22 Time 08:32 Sent To  
Notes
2001-01-08 00:00:00APPROVED PROVISO
 1) INTERIOR FINISH TO BE CLASS A OR B.
 2) ENSURE THAT ADEQUATE EMERGENCY
 LIGHTING FIXTURES ARE PRESENT IN THE
 DINING AND RETAIL AREA.
 3) ENTIRE SPACE IS TO BE FIRE SPRINKLER
 PROTECTED INCLUDING THE WALK-IN COOLER.
 4) PROVIDE FIRE ALARM SYSTEM DRAWINGS
 FOR FIRE ALARM DEVICES SHOWN ON PLANS.
 A SEPARATE PERMIT IS REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By mcarsill Date 2000-07-26 Time 10:07 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER SYSTEM DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS.
 2) EXPLAIN USE FOR 12 GALLON KETTLE.
 3) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 4) PROVIDE SHOP DRAWINGS AND SEPARATE
 PERMIT FOR FIRE ALARM EQUIPMENT
 INSTALLATION.
 5) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-03 Cont ID  
Sent By cthirben Date 2000-08-03 Time 10:59 Rev Time 1.00
Received By cthirben Date 2000-08-03 Time 10:52 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 *LOCAL CODE REQUIRES 18" MIN. CLEARANCE
 BETWEEN ROOF FINISH AND BOTTOM OF THE
 SUPPORT BEAM OF THE A/C STAND ON PLANS.
 *SEPERATE PERMIT IS REQUIRED FOR HOOD,
 GAS, FIRE SUPPRESSION, WALK-IN COOLERS/
 FREEZERS WHERE IT'S APPLICABLE...

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-30 Cont ID  
Sent By tlarge Date 2000-08-30 Time 09:38 Rev Time 0.50
Received By tlarge Date 2000-08-30 Time 09:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 20:58 Rev Time 1.00
Received By tlarge Date 2000-08-21 Time 19:52 Sent To  
Notes
2001-01-08 00:00:001)PROVIDE GAS ISOMETRIC FOR REVIEW.SEE
 ATTACHED REQS.FOR PLAN REVIEW.
  
 2)SHT.P-5.DELETE REFERENCE TO UPC.PLUMB-
 ING INSTALLATION SHALL COMPLY W/STANDARD
 PLUMBING CODE 1994 EDITION.
  
 3)SHT.P-5.GREASY WASTE SHALL COMPLY W/
 SPC SEC.921 FOR HORIZONTAL COMBINATION
 WASTE AND VENT SYSTEM.(A REFERENCE NOTE
 ON THE PLAN DOESN'T CORRECT THE
 VIOLATIONS IN THE DESIGN.)
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-21 Cont ID  
Sent By pschmitz Date 2000-07-21 Time 09:21 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A1.2 H/C REST RM, TO COMPLY WITH
 FACBC 4.16.2 FIG 28,TURNING RADIUS RUNS
 INTO DOOR, MOVE LAV FOR 36" CLEARANC OF
 WALL,TO ALLOW TURNING RADIUS TO CLEAR
 DOOR SWING.
 (2) SHT P2 DISHWASHER 21 TO BY PASS G/W,
 AND CONNECT TO SANITARY SEWER , LOCAL
 ORDINANCE FOR REGIONAL SEWER PLANT.
 (3) SHT P2 NOTE "H" ALL INDIRECT WASTE,
 FLOOR SINKS.NO F/D'S
 (3) SHT P3GEN NOTE #7 CONDENSATE
 DRAIN FROM COOLER, FLR SINK,NO F/D.
 (4) SHT P4 WTR HTR, DIELECTRIC UNIONS
 NOT APPROVED, USE DIELECTRIC NIPPLES OR
 COUPLINGS SPC SEC 611.2 MATERIALS A/G.
 (5) SHT P4 PROVIDE GAS ISMETRIC, SHOW
 TOTAL DEVELOPED LGTH,TOT. BTU'S, BTU'S
 OF EA APPLIANCE, TYPE OF PIPING MATERIAL
 GAS PSI USED. SGC 97 SEC 104.2
 (6) SHT P6 G/W WASTE & VENT,
 HORIZONTAL DRY VENTS NOT PERMITED,USE
 SPC 94 SEC921 COMBINATION WASTE, VENT.
 SEE ILLUSTRATION PG 275 SPC 94.
 (7) SEE OTHER COMMENTS BY CPPR.
 END OF COMMENTS