Plan Review Details - Permit 00061597
Plan Review Stops For Permit 00061597
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-30 Cont ID  
Sent By drunnels Date 2000-08-30 Time 09:20 Rev Time 1.00
Received By drunnels Date 2000-08-30 Time 09:20 Sent To  
Notes
2001-01-08 00:00:00NOTE:SIGNS TO BE UNDER SEPERATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-17 Cont ID  
Sent By drunnels Date 2000-08-17 Time 12:25 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 1.SUBMIT FLORIDA ENERGY SHEETS SIGNED &
 SEALED BY ENG. AND SIGNED BY OWNER/AGENT
 2.SUBMIT PRODUCT APPROVAL FOR STOREFRONT
 IMPACT RESISTANT GLAZING
 3.SUBMIT PLANS AND APPLICATION FOR FIRE
 SPRINKLER PERMIT.
  
 NOTE: SIGNS UNDER SEPERATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-08-07 Cont ID  
Sent By drunnels Date 2000-08-07 Time 11:52 Rev Time 1.00
Received By drunnels Date 2000-08-07 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00 
 1. SUBMIT FLORIDA ENERGY SHEETS SIGNED
 AND SEALED BY ENGINEER AND SIGNED BY
 OWNER/AGENT.
 2. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.
 3. PROVIDE PRODUCT APPROVAL INFORMATION
 ON STOREFRONT INDICATING COMPLIANCE WITH
 1997 SBC CHAPTER 16 AS AMENDEDED BY WPB
 OR METRO DADE COUNTY SBCCI PRODUCTS ARE
 ACCEPTABLE.
 4. SIGNS TO BE PERMITED UNDER SEPERATE
 PERMIT.
 5. SUBMIT APPLICATION AND PLANS FOR FIRE
 SPRINKLER. FIRE SPRINKLER TO BE ISSUED
 PRIOR TO BUILDING PERMIT.
 6. PROVIDE DETAILS ON DEMISING WALL-
 FIRE RATING AND UL NUMBERS- ALL DEMISING
 WALL SHALL BE FINISHED BOTH SIDES PRIOR
 TO C.O. BEING ISSUED.
 7. SHEET A2 DECK DETAILS - DEFINE
 LOCATION LOADING AND ACCESS TO COMPLY
 WITH 1997 SBC.
 8.DEFINE WALL AND RATING AT REAR OF
 LIMIT AND DOOR SWING IF THIS IS AN EXIT.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-17 Cont ID  
Sent By jleahy Date 2000-08-17 Time 11:39 Rev Time 0.45
Received By jleahy Date 2000-08-17 Time 11:37 Sent To  
Notes
2001-01-08 00:00:00ADDED ONE OUTLET ON GLASS WALL ON COLUMN
 PER TREVOR AT LEVY AND ASSOCIATES
 330-666-6767

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 15:50 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 15:50 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT **************
  
 1)NOTE: PLEASE SEE ORIGINAL NOTES.
 NOTE;ALL NOTES WERE NOT ADDRESSED.
  
 PLEASE SUBMIT ALL THE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW,.
 CITY OF WEST PALM BEACH
  
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By dpalmer Date 2000-08-03 Time 14:53 Rev Time 0.00
Received By dpalmer Date 2000-08-03 Time 14:53 Sent To  
Notes
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE SUBMIT COMPLETED LOAD
 CALCULATIONS. SHOW ALL CONTINUOUS LOADS
 AT 125%.
  
 2)NOTE: PLEASE SHOW TRACK LIGHTING CALCS
 PER 220-12 A/B SHOW WINDOW LIGHTING.
  
 3)NOTE: PLEASE CLARIFY LOAD ON TRANS-
 -FORMER, ON PANEL "A".
  
 4)NOTE: OUTLET SPACING TO MEET LOCAL
 CODE. INCLUDING ALL STORAGE AREAS EVERY
 20` OF WALL SPACE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-30 Cont ID  
Sent By drunnels Date 2000-08-30 Time 09:37 Rev Time 0.00
Received By drunnels Date 2000-08-30 Time 09:38 Sent To  
Notes
2001-01-08 00:00:001) LETTER REGARDING THE INSTALLATION OF
 FIRE ALARM EQUIPMENT IS TO BE SENT TO
 DEAN RUNNELS ON AUGUST 30, 2000.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-15 Cont ID  
Sent By mcarsill Date 2000-08-15 Time 17:10 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE ALARM EQUIPMENT SHOWN ON
 DRAWINGS. HOW IS THE BASE BUILDING FIRE
 ALARM SYSTEM HEARD WITHIN THE TENANT
 SPACE.
 2) NO FIRE SPRINKLER DRAWINGS INCLUDED
 WITH PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-08-08 Cont ID  
Sent By mcarsill Date 2000-08-08 Time 10:30 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER SYSTEM DRAWINGS
 INCLUDED IN PLANS.
 2) INTERIOR FINISHES ON WALLS AND
 CEILINGS SHALL BE CLASS A OR B.
 3) PLEASE SHOW CLEARLY THE EMERGENCY
 LIGHTING DEVICES.
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 5) HOW IS THE FIRE ALARM SYSTEM HEARD
 WITHIN TENANT SPACE. NO FIRE ALARM
 DEVICES OBSERVED IN SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-05 Cont ID  
Sent By ndenmark Date 2000-12-05 Time 11:17 Rev Time 0.50
Received By ndenmark Date 2000-12-05 Time 11:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-16 Cont ID  
Sent By cthirben Date 2000-08-16 Time 09:26 Rev Time 1.00
Received By cthirben Date 2000-08-16 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-08-04 Cont ID  
Sent By ndenmark Date 2000-08-04 Time 08:36 Rev Time 0.50
Received By ndenmark Date 2000-08-04 Time 08:36 Sent To  
Notes
2001-01-08 00:00:00***********DENIED***********************
 1. (PGAL)PROVIDE AIR BALANCE COOLING,
 HEATING CALCULATIONS
 2.(PGAL) PROVIDE DETAILS ON THE FOLLOW-
 ING ITEMS:
 DUCTWORK MOUNTING DETAILS
 CONDENSATE TRAP MOUNTING DETAIL
 CONDENSATE EMERGENCY PLAN
 3. (PGAL) CLARIFY IF FIRE DAMPERS ARE
 REQUIRED PER SMC 610
 4. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 10:49 Rev Time 0.50
Received By tlarge Date 2000-08-17 Time 10:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-03 Cont ID  
Sent By tlarge Date 2000-08-03 Time 17:49 Rev Time 0.65
Received By tlarge Date 2000-08-03 Time 17:49 Sent To  
Notes
2001-01-08 00:00:00TOILET ROOM DOORS CANNOT SWING INTO THE
 CLEAR FLOOR SPACE REQD.FOR THE WATER
 CLOSET.FACBC SEC.4.22.
  
 2)A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3(10)(A),4.15.
  
 3)HANDICAP TOILET ROOM SHALL BE
 INDELIBLY POSTED FOR THE INTENDED USE.
 FACBC SEC.4.1.2(7),4.1.3.(16)(A).
  
 4)HANDICAP TOILET ROOMS SHALL BE LOCATED
 ON AN ACCESSIBLE ROUTE PER FACBC SECS.
 4.1.3(11),4.2.1,4.3.1,4.3.2(3),4.3.3.
 ACCESIBLE ROUTE SHALL BE CLEARLY DEFINED
 ON THE PLANS.
  
 5)DOORS ON ACCESSIBLE ROUTE SHALL COMPLY
 W/FACBC SEC.4.13.
  
 6)TOILET FACILITIES SHALL BE AVAILABLE
 TO PATRONS WITHOUT RESTRICTION DURING
 NORMAL OPERATING HOURS PER SPC SEC.
 407.2.2.
  
 7)SHOW MOUNTING HEIGHTS & CLEARANCES
 OF ALL HANDICAP FIXTURES AND APPURTEN-
 ANCES.COMPLY W/FACBC.
  
 8)MIN.SIZE WATER SUPPLY TO FIXTURES
 SHALL BE 1/2" PER SPC TABLE 607.
  
 9)HUB DRAIN CANNOT CONNECT TO FLOOR
 DRAIN AS DRAWN.CONNECT TO FIXTURE DRAIN.
 SPC 804.5,806.