| Plan Review Stops For Permit 00061597 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-30 |
Time |
09:20 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-30 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTE:SIGNS TO BE UNDER SEPERATE PERMIT |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-17 |
Time |
12:25 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | 1.SUBMIT FLORIDA ENERGY SHEETS SIGNED & | | | SEALED BY ENG. AND SIGNED BY OWNER/AGENT | | | 2.SUBMIT PRODUCT APPROVAL FOR STOREFRONT | | | IMPACT RESISTANT GLAZING | | | 3.SUBMIT PLANS AND APPLICATION FOR FIRE | | | SPRINKLER PERMIT. | | | | | | NOTE: SIGNS UNDER SEPERATE PERMIT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-07 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-07 |
Time |
11:52 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-07 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | 1. SUBMIT FLORIDA ENERGY SHEETS SIGNED | | | AND SEALED BY ENGINEER AND SIGNED BY | | | OWNER/AGENT. | | | 2. SUBMIT LETTER FROM SPECIAL INSPECTOR | | | RELEASING SPACE. | | | 3. PROVIDE PRODUCT APPROVAL INFORMATION | | | ON STOREFRONT INDICATING COMPLIANCE WITH | | | 1997 SBC CHAPTER 16 AS AMENDEDED BY WPB | | | OR METRO DADE COUNTY SBCCI PRODUCTS ARE | | | ACCEPTABLE. | | | 4. SIGNS TO BE PERMITED UNDER SEPERATE | | | PERMIT. | | | 5. SUBMIT APPLICATION AND PLANS FOR FIRE | | | SPRINKLER. FIRE SPRINKLER TO BE ISSUED | | | PRIOR TO BUILDING PERMIT. | | | 6. PROVIDE DETAILS ON DEMISING WALL- | | | FIRE RATING AND UL NUMBERS- ALL DEMISING | | | WALL SHALL BE FINISHED BOTH SIDES PRIOR | | | TO C.O. BEING ISSUED. | | | 7. SHEET A2 DECK DETAILS - DEFINE | | | LOCATION LOADING AND ACCESS TO COMPLY | | | WITH 1997 SBC. | | | 8.DEFINE WALL AND RATING AT REAR OF | | | LIMIT AND DOOR SWING IF THIS IS AN EXIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2000-08-17 |
Time |
11:39 |
Rev Time |
0.45 |
| Received By |
jleahy |
Date |
2000-08-17 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ADDED ONE OUTLET ON GLASS WALL ON COLUMN | | | PER TREVOR AT LEVY AND ASSOCIATES | | | 330-666-6767 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE ORIGINAL NOTES. | | | NOTE;ALL NOTES WERE NOT ADDRESSED. | | | | | | PLEASE SUBMIT ALL THE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW,. | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-03 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-03 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETED LOAD | | | CALCULATIONS. SHOW ALL CONTINUOUS LOADS | | | AT 125%. | | | | | | 2)NOTE: PLEASE SHOW TRACK LIGHTING CALCS | | | PER 220-12 A/B SHOW WINDOW LIGHTING. | | | | | | 3)NOTE: PLEASE CLARIFY LOAD ON TRANS- | | | -FORMER, ON PANEL "A". | | | | | | 4)NOTE: OUTLET SPACING TO MEET LOCAL | | | CODE. INCLUDING ALL STORAGE AREAS EVERY | | | 20` OF WALL SPACE. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-30 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
2000-08-30 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) LETTER REGARDING THE INSTALLATION OF | | | FIRE ALARM EQUIPMENT IS TO BE SENT TO | | | DEAN RUNNELS ON AUGUST 30, 2000. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-15 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE ALARM EQUIPMENT SHOWN ON | | | DRAWINGS. HOW IS THE BASE BUILDING FIRE | | | ALARM SYSTEM HEARD WITHIN THE TENANT | | | SPACE. | | | 2) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | WITH PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-08 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER SYSTEM DRAWINGS | | | INCLUDED IN PLANS. | | | 2) INTERIOR FINISHES ON WALLS AND | | | CEILINGS SHALL BE CLASS A OR B. | | | 3) PLEASE SHOW CLEARLY THE EMERGENCY | | | LIGHTING DEVICES. | | | 4) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 5) HOW IS THE FIRE ALARM SYSTEM HEARD | | | WITHIN TENANT SPACE. NO FIRE ALARM | | | DEVICES OBSERVED IN SPACE. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-12-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-05 |
Time |
11:17 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-12-05 |
Time |
11:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-16 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-16 |
Time |
09:26 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-16 |
Time |
09:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-04 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-04 |
Time |
08:36 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-04 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | 1. (PGAL)PROVIDE AIR BALANCE COOLING, | | | HEATING CALCULATIONS | | | 2.(PGAL) PROVIDE DETAILS ON THE FOLLOW- | | | ING ITEMS: | | | DUCTWORK MOUNTING DETAILS | | | CONDENSATE TRAP MOUNTING DETAIL | | | CONDENSATE EMERGENCY PLAN | | | 3. (PGAL) CLARIFY IF FIRE DAMPERS ARE | | | REQUIRED PER SMC 610 | | | 4. PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-17 |
Time |
10:49 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-17 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-03 |
Time |
17:49 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-03 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | TOILET ROOM DOORS CANNOT SWING INTO THE | | | CLEAR FLOOR SPACE REQD.FOR THE WATER | | | CLOSET.FACBC SEC.4.22. | | | | | | 2)A DRINKING FOUNTAIN IS REQD.PER SPC | | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | | W/FACBC SEC.4.1.3(10)(A),4.15. | | | | | | 3)HANDICAP TOILET ROOM SHALL BE | | | INDELIBLY POSTED FOR THE INTENDED USE. | | | FACBC SEC.4.1.2(7),4.1.3.(16)(A). | | | | | | 4)HANDICAP TOILET ROOMS SHALL BE LOCATED | | | ON AN ACCESSIBLE ROUTE PER FACBC SECS. | | | 4.1.3(11),4.2.1,4.3.1,4.3.2(3),4.3.3. | | | ACCESIBLE ROUTE SHALL BE CLEARLY DEFINED | | | ON THE PLANS. | | | | | | 5)DOORS ON ACCESSIBLE ROUTE SHALL COMPLY | | | W/FACBC SEC.4.13. | | | | | | 6)TOILET FACILITIES SHALL BE AVAILABLE | | | TO PATRONS WITHOUT RESTRICTION DURING | | | NORMAL OPERATING HOURS PER SPC SEC. | | | 407.2.2. | | | | | | 7)SHOW MOUNTING HEIGHTS & CLEARANCES | | | OF ALL HANDICAP FIXTURES AND APPURTEN- | | | ANCES.COMPLY W/FACBC. | | | | | | 8)MIN.SIZE WATER SUPPLY TO FIXTURES | | | SHALL BE 1/2" PER SPC TABLE 607. | | | | | | 9)HUB DRAIN CANNOT CONNECT TO FLOOR | | | DRAIN AS DRAWN.CONNECT TO FIXTURE DRAIN. | | | SPC 804.5,806. |
|
|