Plan Review Details - Permit 00061576
Plan Review Stops For Permit 00061576
Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-01 Cont ID  
Sent By tlarge Date 2000-08-01 Time 08:22 Rev Time 1.00
Received By tlarge Date 2000-08-01 Time 07:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-06 Cont ID  
Sent By tlarge Date 2000-07-06 Time 08:25 Rev Time 0.50
Received By pschmitz Date 2000-07-06 Time 08:25 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SIGNED AND SEALED CALCULATIONS
 FOR THE GAS SYSTEM.COMPLY W/SGC SEC.
 305.4.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-02 Cont ID  
Sent By tlarge Date 2000-07-02 Time 06:12 Rev Time 0.50
Received By pschmitz Date 2000-07-02 Time 06:12 Sent To  
Notes
2001-01-08 00:00:00SUBMIT MANUF.SHEETS FOR ALL EQUIPMENT.
 EQUIPMENT SHALL BE LISTED/APPROVED PER
 SGC SEC.402.1,NFPA 54 SEC.5.1.1.
  
 A UNION IS REQD.DOWNSTREAM OF S.O.V.PER
 NFPA SEC.5.5.4.
  
 CLEARLY IDENTIFY THE SECTIONS OF PIPE
 ON THE RISER ACCORDING TO THE PIPING
 CALCULATIONS ON THE SHEETS WITH THE
 MUELLER FORMULA.