Plan Review Details - Permit 00061543
Plan Review Stops For Permit 00061543
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2001-02-05 Cont ID  
Sent By lmartine Date 2001-02-05 Time 06:46 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-02-05 00:00:00STOREFRONT SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-12-12 Cont ID  
Sent By lmartine Date 2000-12-12 Time 07:17 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00SUBMITTAL REVIEW COMMENTS
  
 1]
 ENGINEERS CALCULATIONS ARE FOR THE STORM
 PANELS,ALSO ASCE 7-88 IS NOT CURRENT,USE
 ASCE 7-95 AND DESIGN FOR THE GLAZING.
 2]
 SUBMIT CURRENT TEST REPORT FOR STORM
 PANELS.
 3]
 SUBMIT TEST REPORTS FOR WIND AND IMPACT
 PROTECTION FOR NEW GLAZING PANELS.
 4]
 ALL SHOP DRAWINGS AND REPORTS SUBMITTED
 SHALL BE REVIEWED AND APPROVED BY THE
 PROJECT DESIGN PROFESSIONAL.
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 561-659-8096
 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-28 Cont ID  
Sent By lmartine Date 2000-07-28 Time 10:58 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00*********PROVISO***********
  
 SUBMIT TEST REPORTS FOR ALL EXTERIOR
 DOORS AND WINDOWS,TO COMPLY WITH WIND
 AND IMPACT PROTECTION REQUIREMENTS.
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096#8456

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By dpalmer Date 2000-08-29 Time 20:41 Rev Time 0.00
Received By dpalmer Date 2000-08-29 Time 20:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 21:45 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 21:45 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE:PLEASE SEE THE REQ`MENTS FOR
 SHOW WINDOW REC. PER 210-62 AND LOAD
 CALCULATIONS PER 220-12
  
 2)NOTE: NEED TO MEET THE REQ`MENTS FOR
 OUTLETS IN STORAGE AREA PER LOCAL CODE.
 20` OF WALL SPACE AND OUTLETS FOR
 SHOW ROOM AREA ALONG FIXED GLASS PANELS.
  
 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 SHOWING ALL CONTINUOUS LOADS AT 125%
 (LIGHTING, CASH REG. ETC.
 PLEASE CHECK THE LOAD BEING INTRODUCED
 TO PANEL "A". THIS WILL CHANGE TOTAL
 LOAD ON PANEL 'B'
  
 PLEASE SUBMIT THE ABOVE INFORMAITION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-11-02 Cont ID  
Sent By mcarsill Date 2000-11-02 Time 16:38 Rev Time 0.00
Received By mcarsill Date 2000-11-02 Time 16:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-25 Cont ID  
Sent By mcarsill Date 2000-08-25 Time 10:45 Rev Time 0.00
Received By mcarsill Date 2000-08-25 Time 10:45 Sent To  
Notes
2001-01-08 00:00:001) WRONG INTERIOR FINISH. INTERIOR
 FINISHES ON WALLS AND CEILINGS SHALL BE
 CLASS A OR B NOT C AS NOTED IN
 GENERAL NOTES SECTION.
 2) NO FIRE SPRINKLER DRAWINGS PROVIDED.
 THIS INFORMATION WAS REQUESTED AFTER
 THE JULY 13, 2000 REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-13 Cont ID  
Sent By rturnque Date 2000-07-13 Time 10:32 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-10-21 Cont ID  
Sent By ndenmark Date 2000-10-21 Time 07:14 Rev Time 0.50
Received By ndenmark Date 2000-10-21 Time 07:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-25 Cont ID  
Sent By cthirben Date 2000-07-25 Time 14:07 Rev Time 1.00
Received By cthirben Date 2000-07-25 Time 13:56 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATION AS PER
 ASHRAE 62-89.
 NOTE:
 FAN SHUTDOWN BY SMOKE DETECTOR TO BE
 TIED-IN TO HORN AND STROBE AS PER NFPA
 90A 4.4.4.3..

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-10-25 Cont ID  
Sent By tlarge Date 2000-10-25 Time 10:55 Rev Time 0.50
Received By tlarge Date 2000-10-25 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-26 Cont ID  
Sent By tlarge Date 2000-08-26 Time 12:55 Rev Time 0.50
Received By tlarge Date 2000-08-26 Time 12:55 Sent To  
Notes
2001-01-08 00:00:001)WIDTH OF ACCESSIBLE STALL IN MEN'S R.R
 SHALL COMPLY W/4.1.6(B),4.17.3(MIN.83")
  
 2)CLEARLY SHOW OCCUPANT LOAD ON PLANS
 BASED ON SQUARE FEET OF HABITABLE FLOOR
 SPACE.SEE SPC SEC.407.1.3 FOR ALLOWED
 DEDUCTIBLE AREAS.
  
 3)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1,610.4.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-23 Cont ID  
Sent By pschmitz Date 2000-07-23 Time 13:44 Rev Time 2.50
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) SHT A-2 WOMENS REST ROOM STALL IS
 REQUIRED TO HAVE A LAV IN THE STALL,
 FACBC 4.17.3 (1 EX NEW CONST )
 (2) SHT A-2 WATER HEATER TO BE READLY
 ACCESSIBLE SPC 94 SEC 501.7, OPTION,
 RELOCATE TO THE FLOOR OR PROVIDE A FIXED
 SHIPS LADDER,WITH A WORKING PLATFORM.
 (3)SHT M-2 FLR DRAIN IN PUBLIC REST RM,
 SPC 94 SEC 409.1.1 TRAP PRIMER REQUIRED.
 (4) SHT M-2 BACK FLOW LOCATION & TYPE TO
 COMPLY W/LOCAL ORDINANCE # 2853-95,
 RPZV W/INDRECT DRAIN,MAX HGTH 48" AFF.
 END OF COMMENTS