| Plan Review Stops For Permit 00061543 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2001-02-05 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-02-05 00:00:00 | STOREFRONT SHOP DRAWINGS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-12-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-12-12 |
Time |
07:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMITTAL REVIEW COMMENTS | | | | | | 1] | | | ENGINEERS CALCULATIONS ARE FOR THE STORM | | | PANELS,ALSO ASCE 7-88 IS NOT CURRENT,USE | | | ASCE 7-95 AND DESIGN FOR THE GLAZING. | | | 2] | | | SUBMIT CURRENT TEST REPORT FOR STORM | | | PANELS. | | | 3] | | | SUBMIT TEST REPORTS FOR WIND AND IMPACT | | | PROTECTION FOR NEW GLAZING PANELS. | | | 4] | | | ALL SHOP DRAWINGS AND REPORTS SUBMITTED | | | SHALL BE REVIEWED AND APPROVED BY THE | | | PROJECT DESIGN PROFESSIONAL. | | | | | | | | | | | | REVIEWED BY; | | | LUIS MARTINEZ | | | 561-659-8096 | | | #8456 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-07-28 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-07-28 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *********PROVISO*********** | | | | | | SUBMIT TEST REPORTS FOR ALL EXTERIOR | | | DOORS AND WINDOWS,TO COMPLY WITH WIND | | | AND IMPACT PROTECTION REQUIREMENTS. | | | | | | | | | REVIEWED BY: | | | LUIS MARTINEZ | | | 561-659-8096#8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-08-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-29 |
Time |
20:41 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-29 |
Time |
20:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-26 |
Time |
21:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-26 |
Time |
21:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE:PLEASE SEE THE REQ`MENTS FOR | | | SHOW WINDOW REC. PER 210-62 AND LOAD | | | CALCULATIONS PER 220-12 | | | | | | 2)NOTE: NEED TO MEET THE REQ`MENTS FOR | | | OUTLETS IN STORAGE AREA PER LOCAL CODE. | | | 20` OF WALL SPACE AND OUTLETS FOR | | | SHOW ROOM AREA ALONG FIXED GLASS PANELS. | | | | | | 3)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | SHOWING ALL CONTINUOUS LOADS AT 125% | | | (LIGHTING, CASH REG. ETC. | | | PLEASE CHECK THE LOAD BEING INTRODUCED | | | TO PANEL "A". THIS WILL CHANGE TOTAL | | | LOAD ON PANEL 'B' | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-02 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-02 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-02 |
Time |
16:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-25 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-25 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG INTERIOR FINISH. INTERIOR | | | FINISHES ON WALLS AND CEILINGS SHALL BE | | | CLASS A OR B NOT C AS NOTED IN | | | GENERAL NOTES SECTION. | | | 2) NO FIRE SPRINKLER DRAWINGS PROVIDED. | | | THIS INFORMATION WAS REQUESTED AFTER | | | THE JULY 13, 2000 REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-07-13 |
Time |
10:32 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVIDE FIRE SPRINKLER DRAWINGS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-10-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-10-21 |
Time |
07:14 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-10-21 |
Time |
07:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-25 |
Time |
14:07 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-25 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE OUTSIDE AIR CALCULATION AS PER | | | ASHRAE 62-89. | | | NOTE: | | | FAN SHUTDOWN BY SMOKE DETECTOR TO BE | | | TIED-IN TO HORN AND STROBE AS PER NFPA | | | 90A 4.4.4.3.. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-10-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-10-25 |
Time |
10:55 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-10-25 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-26 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-26 |
Time |
12:55 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-26 |
Time |
12:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)WIDTH OF ACCESSIBLE STALL IN MEN'S R.R | | | SHALL COMPLY W/4.1.6(B),4.17.3(MIN.83") | | | | | | 2)CLEARLY SHOW OCCUPANT LOAD ON PLANS | | | BASED ON SQUARE FEET OF HABITABLE FLOOR | | | SPACE.SEE SPC SEC.407.1.3 FOR ALLOWED | | | DEDUCTIBLE AREAS. | | | | | | 3)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC.610.4.1,610.4.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-23 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-23 |
Time |
13:44 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT A-2 WOMENS REST ROOM STALL IS | | | REQUIRED TO HAVE A LAV IN THE STALL, | | | FACBC 4.17.3 (1 EX NEW CONST ) | | | (2) SHT A-2 WATER HEATER TO BE READLY | | | ACCESSIBLE SPC 94 SEC 501.7, OPTION, | | | RELOCATE TO THE FLOOR OR PROVIDE A FIXED | | | SHIPS LADDER,WITH A WORKING PLATFORM. | | | (3)SHT M-2 FLR DRAIN IN PUBLIC REST RM, | | | SPC 94 SEC 409.1.1 TRAP PRIMER REQUIRED. | | | (4) SHT M-2 BACK FLOW LOCATION & TYPE TO | | | COMPLY W/LOCAL ORDINANCE # 2853-95, | | | RPZV W/INDRECT DRAIN,MAX HGTH 48" AFF. | | | END OF COMMENTS |
|
|