Plan Review Details - Permit 00061542
Plan Review Stops For Permit 00061542
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-08-21 Cont ID  
Sent By hpiskura Date 2000-08-01 Time 08:40 Rev Time 0.00
Received By hpiskura Date   Time 16:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 17:52 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 17:52 Sent To  
Notes
2001-01-08 00:00:00*************** PROVISO ****************
  
 1)NOTE: FIRST NOTE ON FIRST REVIEW.
 PLEASE PLACE ALL BRANCH CIRCUIT #`S ON
 PLANS AND CORRELATE THEM WITH PANEL
 SCHEDULE.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 11:51 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 11:51 Sent To  
Notes
2001-01-08 00:00:00ADDRESS ORIG NOTES AND PLEASE HAVE
 CHANGES DONE IN INK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-27 Cont ID  
Sent By dpalmer Date 2000-07-27 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 11:06 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT PLANS WITH ALL
 BRANCH CIRCUIT #`S ON FLOOR PLAN. PLEASE
 SUBMIT PANEL SCHEDULES TO CORRELATE WITH
 FLOOR PLAN.
  
 2)NOTE: PLEASE SHOW LOADS ON HOUSE PANEL
 215-5
  
 3)NOTE: PLEASE SHOW WIRE SIZES FOR RISER
 DIAGRAM. SIZE FOR LOAD OF SERVICE.
  
 4)NOTE: PLEASE SHOW COLD WATER PIPE AS
 PART OF GROUNDING ELECTRODE SYSTEM. 250-
 -50.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-03 Cont ID  
Sent By rturnque Date 2000-08-03 Time 13:56 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-17 Cont ID  
Sent By cthirben Date 2000-08-17 Time 13:39 Rev Time 1.00
Received By cthirben Date 2000-08-17 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 19:16 Rev Time 1.00
Received By cthirben Date 2000-07-18 Time 19:16 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1.PROVIDE EXHAUST FAN AS REQUIRED PER
 1997 SMC 503.3.1..
 2.PROVIDE ENERGY EFFICIENCY RATING OF
 THE AHU.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-24 Cont ID  
Sent By tlarge Date 2000-08-24 Time 09:59 Rev Time 0.50
Received By tlarge Date 2000-08-24 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-20 Cont ID  
Sent By tlarge Date 2000-08-20 Time 05:46 Rev Time 0.65
Received By tlarge Date 2000-08-20 Time 05:46 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT A FLOOR PLAN THAT CLEARLY
 REFLECTS THE ENTIRE SCOPE OF PLUMBING
 WORK BEING DONE.SHOW LOCATIONS OF ALL
 PLUMBING FIXTURES(INCLUDING FUTURE
 FIXTURES.)
  
 2)ONLY 2 FIXTURES PERMITTED TO BE
 SUPPLIED BY 1/2" C.W.LINE.
  
 3)DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.
  
 4)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC 610.4.2.
  
 5)SHOW DIMENSIONS OF TOILET ROOM.SHOW
 COMPLIANCE W/FACBC SEC.4.16,4.19.
  
 6)A DRINKING FOUNTAIN WILL BE REQD.PER
 SPC TABLE 407 AND SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 7)SUBMIT DETAILS/MOUNTING HEIGHTS OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/FACBC-OCT.1997 EDITION.
  
 8)ALL NOTATIONS SHALL BE IN INK,NOT
 PENCIL.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-15 Cont ID  
Sent By jleech Date 2000-07-15 Time 10:44 Rev Time 0.30
Received By jleech Date 2000-07-15 Time 10:43 Sent To  
Notes
2001-01-08 00:00:00DENIED;
 1. SHOW LOCATION OF FUTURE W/C AND LAV.,
 AND TWO SINKS TO BE INSTALLED.
 2. ISOMETRIC FOR FUTURE NOT SIZED TO
 CODE.W/C MUST GO INTO 3 INCH PIPE.

Review Stop Z ZONING
Rev No 1 Status N Date 2000-08-24 Cont ID  
Sent By dpalmer Date 2000-08-24 Time 18:02 Rev Time 0.00
Received By dpalmer Date 2000-08-24 Time 18:02 Sent To  
Notes
***NONE***