| Plan Review Stops For Permit 00061542 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2000-08-01 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-24 |
Time |
17:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-24 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO **************** | | | | | | 1)NOTE: FIRST NOTE ON FIRST REVIEW. | | | PLEASE PLACE ALL BRANCH CIRCUIT #`S ON | | | PLANS AND CORRELATE THEM WITH PANEL | | | SCHEDULE.215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ROUGH. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-24 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-24 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ADDRESS ORIG NOTES AND PLEASE HAVE | | | CHANGES DONE IN INK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-27 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-21 |
Time |
11:06 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ALL | | | BRANCH CIRCUIT #`S ON FLOOR PLAN. PLEASE | | | SUBMIT PANEL SCHEDULES TO CORRELATE WITH | | | FLOOR PLAN. | | | | | | 2)NOTE: PLEASE SHOW LOADS ON HOUSE PANEL | | | 215-5 | | | | | | 3)NOTE: PLEASE SHOW WIRE SIZES FOR RISER | | | DIAGRAM. SIZE FOR LOAD OF SERVICE. | | | | | | 4)NOTE: PLEASE SHOW COLD WATER PIPE AS | | | PART OF GROUNDING ELECTRODE SYSTEM. 250- | | | -50.215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS,CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-08-03 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-08-03 |
Time |
13:56 |
Rev Time |
0.30 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-08-17 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-17 |
Time |
13:39 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-17 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
19:16 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
19:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1.PROVIDE EXHAUST FAN AS REQUIRED PER | | | 1997 SMC 503.3.1.. | | | 2.PROVIDE ENERGY EFFICIENCY RATING OF | | | THE AHU. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-24 |
Time |
09:59 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-24 |
Time |
09:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-20 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-20 |
Time |
05:46 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-20 |
Time |
05:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT A FLOOR PLAN THAT CLEARLY | | | REFLECTS THE ENTIRE SCOPE OF PLUMBING | | | WORK BEING DONE.SHOW LOCATIONS OF ALL | | | PLUMBING FIXTURES(INCLUDING FUTURE | | | FIXTURES.) | | | | | | 2)ONLY 2 FIXTURES PERMITTED TO BE | | | SUPPLIED BY 1/2" C.W.LINE. | | | | | | 3)DRY VENTS NOT PERMITTED PER SPC SEC. | | | 906.2.1. | | | | | | 4)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC 610.4.2. | | | | | | 5)SHOW DIMENSIONS OF TOILET ROOM.SHOW | | | COMPLIANCE W/FACBC SEC.4.16,4.19. | | | | | | 6)A DRINKING FOUNTAIN WILL BE REQD.PER | | | SPC TABLE 407 AND SHALL COMPLY W/FACBC | | | SEC.4.1.3(10)(A),4.15.PROVISIONS SHALL | | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | | BENDING OR STOOPING. | | | | | | 7)SUBMIT DETAILS/MOUNTING HEIGHTS OF ALL | | | HANDICAP FIXTURES AND APPURTENANCES. | | | COMPLY W/FACBC-OCT.1997 EDITION. | | | | | | 8)ALL NOTATIONS SHALL BE IN INK,NOT | | | PENCIL. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-07-15 |
Time |
10:44 |
Rev Time |
0.30 |
| Received By |
jleech |
Date |
2000-07-15 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED; | | | 1. SHOW LOCATION OF FUTURE W/C AND LAV., | | | AND TWO SINKS TO BE INSTALLED. | | | 2. ISOMETRIC FOR FUTURE NOT SIZED TO | | | CODE.W/C MUST GO INTO 3 INCH PIPE. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-24 |
Time |
18:02 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-24 |
Time |
18:02 |
Sent To |
|
|
| Notes |
|
|