Plan Review Details - Permit 00061502
Plan Review Stops For Permit 00061502
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By drunnels Date 2000-08-02 Time 17:53 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVAL FOR IMPACT RESISTANT
 WINDOW SYSTEM RECEIVED 8-2-00
 WINDOW PROVISO REMOVED FROM THIS PERMIT
  
 RECEIVED LETTER FROM SPECIAL INSPECTOR
 8-2-00

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By drunnels Date 2000-08-01 Time 15:37 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
 PROVISO
  
 PROVIDE PRODUCT APPROVAL FOR WINDOWS
 FROM METRO DADE COUNTY OR SBCCI
 SSTD12-97
 SEPRATE PERMIT REQUIRED FOR STOREFRONT
  
 LETTER FROM SPECIAL RELEASING SPACE
 REFRENCED IN PACKAGE DATED 7-28-00
 LETTER NOT FOUND IN PACKAGE

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 17:24 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 17:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By mcarsill Date 2000-08-01 Time 16:15 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR THE FIRE ALARM DEVICES
 SHOWN ON PLANS. A PLAN AND PERMIT
 REQUIRED PRIOR TO INSTALLATION.
 2) EXITING ALLOWED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS ARE MET,
 NOT MORE THAN 50 PERCENT OF EXIT
 ACCESS IS PROVIDED THROUGH STOCKROOM,
 DOOR LEADING INTO STOCKROOM CANNOT
 BE LOCKED, AISLE TO BE A MINIMUM OF
 44" IN THE CLEAR, AND SAID AISLE TO
 BE MAINTAINED AT 44" AT ALL TIMES.
 3) FLOOR PLAN INDICATES TWO OFFICES
 104 AND 105. IS 105 GOING TO BE USED
 FOR STOCK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-28 Cont ID  
Sent By cthirben Date 2000-07-28 Time 07:54 Rev Time 1.00
Received By cthirben Date 2000-07-28 Time 07:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By tlarge Date 2000-09-22 Time 12:44 Rev Time 0.30
Received By tlarge Date 2000-09-22 Time 12:43 Sent To  
Notes
2001-01-08 00:00:00INSTALL POPINT OF USE WATER HEATER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-29 Cont ID  
Sent By tlarge Date 2000-07-29 Time 07:18 Rev Time 1.00
Received By tlarge Date 2000-07-29 Time 05:47 Sent To  
Notes
2001-01-08 00:00:00PROVISO:ACCESSIBLE TOILET ROOMS SHALL BE
 INDELIBLY POSTED AND BE AVAILABLE TO
 PATRONS WITHOUT RESTRICTION DURING
 OPERATING HOURS.TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE PER FACBC SEC.
 4.1.3(11).SPC 407.2.2.
  
 2)SHT.MP-1-WATER CLOSETS NOT PERMITTED
 ON WET VENTS PER COUNTYWIDE AMENDMENTS
 TO SPC SEC.911.1.1.SUBMIT REVISED SIGNED
 SEALED AND DATED SANITARY RISER PRIOR TO
 PLUMBING INSPECTION.
  
 3)POINT OF USE WATER HEATERS SHALL BE
 LISTED PER SPC SEC.503.3.