Plan Review Details - Permit 00061498
Plan Review Stops For Permit 00061498
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-08-02 Cont ID  
Sent By drunnels Date 2000-08-02 Time 17:59 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00PRODUCT APPROVAL FOR IMPACT RESISTANT
 WINDOW SYSTEM RECEIVED 8-2-00
 WINDOW PROVISO REMOVED FROM THIS PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By drunnels Date 2000-08-02 Time 12:49 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 "PROVISO"
  
 PROVIDE PRODUCT APPROVAL FOR WINDOW
 GLAZING PER METRO DADE COUNTY OR SBCCI
 SSTD12-97.
 STOREFRONT REQUIRES SEPRATE PERMIT
  
 NOTE: ALL 2 HOUR FIRE RATED TENANT
 SEPERATION ASSEMBLIES ( UL# U411) SHALL
 BE COMPLETED PRIOR TO C.O. BEING ISSUED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-09-28 Cont ID  
Sent By dpalmer Date 2000-09-28 Time 18:35 Rev Time 0.00
Received By dpalmer Date 2000-09-28 Time 18:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-07-31 Cont ID  
Sent By dpalmer Date 2000-07-31 Time 20:09 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 20:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-08-01 Cont ID  
Sent By mcarsill Date 2000-08-01 Time 15:48 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 IN TENANT SPACE. PLANS AND PERMIT
 REQUIRED.
 2) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 ALLOWED THROUGH STOCKROOM, DOOR CANNOT
 BE SUBJECT TO LOCKING, AISLE IN
 STOCKROOM TO EXIT MUST BE AT LEAST 44"
 WIDE, AISLE TO BE MAINTAINED AT THE
 44" WIDTH.
 3) PORTABLE FIRE EXTINGUISHERS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-29 Cont ID  
Sent By cthirben Date 2000-07-29 Time 08:23 Rev Time 1.00
Received By cthirben Date 2000-07-29 Time 08:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-09-22 Cont ID  
Sent By tlarge Date 2000-09-22 Time 12:41 Rev Time 0.30
Received By tlarge Date 2000-09-22 Time 12:41 Sent To  
Notes
2001-01-08 00:00:00INSTALL POINT OF USE WATER HEATER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-08-02 Cont ID  
Sent By tlarge Date 2000-08-02 Time 16:46 Rev Time 0.65
Received By tlarge Date 2000-08-02 Time 16:44 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 HANDICAP ACCESSIBLE TOILET ROOM SHALL
 BE INDELIBLY POSTED FOR THE INTENDED
 USE,BE ON AN ACCESSIBLE ROUTE,AND BE
 AVAILABLE TO PATRONS WITHOUT RESTRICTION
 DURING NORMAL OPERATING HOURS.
 FACBC SECS.4.1.2(7),4.1.3(16)(11),4.2.1.
 4.3.1,4.3.2(3),4.3.3.
 SPC SEC.407.2.2.
  
 2)FITTING ROOM SHALL COMPLY W/FACBC
 SEC.4.35.4.BENCH SHALL BE LOCATED ALONG
 WALL WITH THE LONGER DIMENSION.
  
 3)WATER HEATER SHALL BE LISTED.SPC SEC.
 503.3.