| Plan Review Stops For Permit 00061369 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2001-01-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2001-01-30 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-30 00:00:00 | REVIEWED FOR THREE COMMENTS ON PREVIOUS | | | LIST ONLY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2000-12-29 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-12-29 |
Time |
09:27 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS SUBMITTED 12/13/00 | | | DENIED FOR THE FOLLOWING REASONS | | | | | | 1. ENERGY SHEETS NOT SIGNED BY OWNER | | | AGENT 2ND REQUEST | | | 2. SHEET A2.1 HANDRAILS MUST COMPLY WITH | | | FLORIDA ACCESSABILITY CODE SEE FIGURE 19 | | | 1997 EDITION. 2ND REQUEST | | | 3. SHEET A4.2 NOTE #5 INDICATES A 1 HOUR | | | FIRE SEPERATION WHERE A 2 HOUR IS | | | REQUIRED. 2ND REQUEST |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-12-14 |
Time |
12:53 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVIEW OF REVISION DATED 12/14/00 | | | 1. FLORIDA ENERGY SHEETS NOT SIGNED BY | | | OWNER/AGENT | | | 2. HAND RAILS AT STAIRS TO NOT MEET | | | FLORIDA ACCESSABILITY CODE SEE PAGE 99 | | | HAND RAIL EXTENSIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2000-09-20 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-20 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION SUBMITED 9/14/00 APPROVED | | | BZ#172235 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-09-08 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-08 |
Time |
11:58 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-08 |
Time |
11:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO *************** | | | SUBMIT FLORIDA ENERGY SHEETS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-09-06 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-09-06 |
Time |
10:55 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-09-06 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PROVIDE FLORIDA ENERGY SHEETS SIGNED | | | AND SEALED AS REQUIRED. | | | 2.PROVIDE DETAILS SHOWING HOW 2 HOUR | | | TENANT SEPERATION IS ACHIVED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-22 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-22 |
Time |
07:51 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-22 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1.PROVIDE FLORIDA ENERGY SHEETS SIGNED | | | AND SEALED AS REQUIRED. | | | 2. PROVIDE DESIGN INFORMATION ON IRWIN | | | 5000 TELESCOPING PLATFORM- SHEET A2.3 | | | 3. PROVIDE DETAILS SHOWING HOW 2 HOUR | | | TENANT SEPERATION IS ACHIVED. | | | 4. PROVIDE HEALTH DEPARTMENT APPROVAL | | | FOR WARMING KITCHEN. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-01 |
Time |
07:49 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | 1. PROVIDE FLORIDE ENERGY SHEETS SIGNED | | | AND SEALED AS NOTED | | | 2. PROVIDE PRODUCT APPROVAL FOR DOORS & | | | STOREFRONTS FOR EXTERIOR GLAZING PER | | | METRO DADE COUNTY OR 1997 SBC SSTD | | | 12-97 | | | 3. 1998 FLORIDA HANDICAP CODE | | | A) PROVIDE ACCESSIBLE TO ALL LEVELS | | | B) PROJECTION ROOM ON SHEET A2.1 TO | | | BE ACCESSIBLE | | | 4. PROVIDE DESIGN INFORMATION ON JRWIN | | | 5000 TELESCOPING PLATFORM ON | | | SHEET A2.3 | | | 5. SHEET A4.0 & A4.2 SHOWS FLY GALLEY | | | PROVIDE CODE COMPLIANCE INFORMATION | | | FOR STAGE PER 1997 SBC CHAPTER 4 | | | SECTION 403 | | | 6. SHEET A4.2 ROOF ACCESS STAIR | | | GUARDRAIL TO MEET 1997 SBC CHAPTER 10 | | | SECTION 1020.3 HANDRAILS & GUARDRAILS | | | 7. SHEET A6.1 NOTE: REPAIR ALL EXISTING | | | TRUSSES; PROVIDE DETAILS. | | | 8. SHOW HOW 2HOUR TENANT SEPERATION | | | IS ACHIVED. | | | 9. SHEET A8.0 DETAIL 2 ELEVATOR SHAFT | | | SHOW THAT WALL MEETS MIN 2 HR RATING | | | 10.PROVIDE HEALTH DEPARTMENT APPROVAL | | | FOR WARMING KITCHEN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
P |
Date |
2001-02-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-02-05 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-02-05 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2001-01-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-01-11 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-01-11 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2001-01-11 00:00:00 | *****************UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE E-7 PLEASE NOTE | | | MISSING OUTLET FOR EQUIPMENT PER | | | MECHANICAL CODE 309.2 AND NEC 210-63. | | | | | | 2)NOTE: PLEASE SEE E-8 PLEASE PLACE NOTE | | | ON PLANS FOR CEILING TO REMAIN OPEN TO | | | MEET NEC 450-13 (A,B). FOR TRANSFORMER | | | INSTALLATION. | | | | | | 3)NOTE: PLEASE SEE E-10PANEL"2 AC. | | | PLEASE CORRELATE LOAD/WIRE SIZE/BRKR | | | AND CONDUIT TO MEET NEC. | | | | | | | | | PLEASE REVISE THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561--659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2000-12-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-12-14 |
Time |
20:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-12-14 |
Time |
20:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
15:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE REVISION FORM FILLED | | | OUT BY CONTRACTOR. IT SAYS REVISIONS\\ | | | ARE CLOUDED????? ALSO PLANS DO NOT | | | INDICATE ANY REVISIONSMADE TO EXISTING | | | PLANS?? | | | | | | PLEASE HAVE PLANS INDICATE REVISED SHEET | | | -S AND CLOUD AREAS REVISED. | | | IT LOOKS LIKE THE LOAD CALCULATIONS WERE | | | RE-DONE,, IF SO PLEASE CLOUD THESE ALSO. | | | ONLY SUBMIT E-SHEETS THAT REVISIONS | | | WERE MADE. | | | | | | PLEASE SUBMIT FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-01 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-01 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SAME PROVISO SHEETS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO E-SHEETS FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-19 |
Time |
19:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-19 |
Time |
19:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO *************** | | | | | | 1)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | WITH ALL CONTINUOUS LOADS SHOWN AT 125% | | | (LIGHTING) ETC. PER 220 OF THE NEC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMAITON FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESITONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2000-07-20 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2000-07-20 |
Time |
14:31 |
Rev Time |
0.25 |
| Received By |
mgonzale |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DOESN'T NEED ENGINEERING REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2000-12-29 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-29 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-29 |
Time |
12:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2000-12-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-12-12 |
Time |
08:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-12-12 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 2) PLEASE EXPLAIN TWO STEPS SHOWN ON | | | SECOND FLOOR LIFE SAFETY PLAN. | | | 3) WHAT FIRE RATING DOES THE HUFCOR | | | PATHFINDER DOOR PROVIDE. | | | 4) ALL STORAGE ROOMS TO BE ONE HOUR FIRE | | | RATED. | | | | | | APPROVED PROVISO: | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-09-19 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-09-19 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 2) PLEASE PROVIDE FLAMESPREAD DATA ON | | | BLUEBOARD AND SONASPRAY FINISH FOR | | | CEILING. | | | 3) STANDPIPE LOCATIONS STILL NOT SHOWN | | | ON PLANS. | | | 4) ALL DOORS SUBJECT TO AN OCCUPANCY | | | OF 100 OR MORE PERSONS SHALL BE | | | PROVIDED WITH APPROVED PANIC HARDWARE. | | | FIRE DOORS SHALL BE EQUIPPED WITH | | | APPROVED FIRE EXIT PANIC HARDWARE. | | | 5) PROVIDE FLAMESPREAD DATA ON | | | PROJECTION SCREEN. | | | 6) PROVIDE MORE DETAILS ON TELESCOPING | | | BLEACHER. | | | 7) PLEASE IDENTIFY REQUIRED AISLES ON | | | PAGES FFS.2 AND FFS.3. TABLES AND | | | CHAIRS CANNOT BLOCK EXIT ACCESS TO | | | EXITS. | | | 8) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 9) DRY-CHEMICAL FIRE SUPPRESSION SYSTEM | | | NOT ALLOWED. ONLY WET-CHEMICAL FIRE | | | SUPPRESSION SYSTEMS PERMITTED. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-31 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-31 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PROVIDE DETAILS ON WATER CURTAIN AND | | | DRAFT STOP PLANNED FOR FLOOR OPENING | | | BETWEEN SECOND AND THIRD FLOOR. THESE | | | DETAILS SHOULD SHOW FIRE SPRINKLER AND | | | DRAFT STOPPING TOGETHER. | | | 2) STANDPIPE SYSTEM STILL NOT SHOWN. | | | PLEASE SHOW STANDPIPE SYSTEM CONNECTIONS | | | FOR BUILDING. | | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FOR THE FIRE ALARM | | | EQUIPMENT SHOWN FOR EXHIBITION HALL. | | | PLEASE BE ADVISED THAT FRED GRINER OF | | | CITY PLACE AGREED TO PROVIDE VOICE | | | EVACUATION FOR THE FIRE ALARM SYSTEM | | | WHEN THE EXHIBITION HALL WAS FITTED | | | UP. PLEASE INDICATE THIS ON FUTURE | | | PLANS. CUT SHEETS NEEDED ON ALL DEVICES | | | PLANNED FOR USE. | | | 4) WATER CURTAIN FOR NORTHEAST STAIRWAY | | | NOT SHOWN. | | | 5) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | APPROVED PROVISO: |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-15 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) TRAVEL DISTANCE NOTE ON PLANS IS | | | STILL INCORRECT. TRAVEL DISTANCE NOTE | | | SHOULD READ 200 FEET INSTEAD OF 250 | | | FEET. | | | 2) NEW WOOD GUARDRAIL TO COMPLY WITH | | | NFPA 101, LIFE SAFETY CODE REQUIREMENTS, | | | 1985 EDITION. | | | 3) TWO STEPS SHOWN ON PAGE A4.2 IS NOT | | | PROPER. A MINIMUM OF THREE STEPS SHALL | | | BE PROVIDED AT 7" EACH OR A RAMP IS | | | REQUIRED. | | | 4) WATER CURTAIN WITH FIRE SPRINKLER | | | HEADS NO FARTHER THAN 6 FEET APART ARE | | | REQUIRED AT NORTHEAST STAIR. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-08-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-01 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) TRAVEL DISTANCES TO EXITS IN NEW | | | ASSEMBLY OCCUPANCIES SHALL NOT EXCEED | | | 200 FEET. | | | 2) ALL EXIT DOORS SUBJECT TO AN | | | OCCUPANCY LOAD OF 100 OR MORE PERSONS | | | ARE TO BE EQUIPPED WITH APPROVED PANIC | | | HARDWARE. IF THESE DOORS ARE FIRE RATED | | | THEN THEY ARE TO BE EQUIPPED WITH | | | APPROVED FIRE EXIT PANIC HARDWARE. | | | 3) EXHIBITION HALL TO PROVIDE PROVISIONS | | | FOR AT LEAST TWO HANDICAPPED PERSONS. | | | 4) INTERIOR FINISH SHALL BE CLASS A OR | | | B. | | | 5) NO SEATING ARRANGEMENT SHOWN ON | | | DRAWINGS. | | | 6) ALL STORAGE ROOMS SHALL BE SEPARATED | | | FROM OTHER PARTS OF THE BUILDING BY | | | AT LEAST ONE HOUR AND FIRE SPRINKLERS. | | | 7) STANDPIPE LOCATIONS NOT SHOWN FOR | | | EXHIBITION HALL. | | | 8) NORTH ENTRY STAIR TO BE SLIP | | | RESISTANT. | | | 9) |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2000-12-15 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-12-15 |
Time |
08:52 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-12-15 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-19 |
Time |
12:04 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-09-19 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | FIRE DAMPERS PREVIOUSLY REQUESTED TO BE | | | SHOWN ARE NOT ON PLAN. PROVIDE REVISION | | | SHOWING LOCATION OF FIRE DAMPERS AT | | | RATED WALL PRIOR TO FIRST INSPECTION |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-09-08 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-08 |
Time |
10:58 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-09-08 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | NEW SHEET SHOWING LOCATION OF FIRE DAMP- | | | ERS IN 2 HR RATED WALLS TO BE SUBMITTED | | | PRIOR TO FIRST INSPECTION FOR APPROVAL | | | | | | AIR BALANCE SCHEDULE SHOWING COMPLIANCE | | | WITH 501.2 1997 SMC TO BE SUBMITTED | | | PRIOR TO FIRST INSPECTION FOR REVIEW | | | NANCY DENMARK 9/8/00 (561) 659-8096X8221 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-30 |
Time |
15:42 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-08-30 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***********DENIED*********************** | | | | | | 1. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE W/ 1997 SMC 501.2 | | | 2. DUCTS PENETRATING RATED WALLS TO HAVE | | | FIRE DAMPERS PER 1997 SMC 610.1.2 | | | PROVIDE LOCATION AND DETAILS OF FIRE | | | DAMPERS PER 610.6 (2 HR WALLS, SEE LS | | | PLAN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-08-30 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-16 |
Time |
06:52 |
Rev Time |
0.00 |
| Received By |
bstaples |
Date |
2000-08-16 |
Time |
06:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | NO MECHANICAL PLANS SUBMITTED FOR REVIEW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-27 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-27 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-06-27 |
Time |
10:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: ******************************** | | | | | | 1. PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 2. ENERGY EFFIECIENCY RATING 0F AHU TO | | | BE PROVIDED | | | 3. PROVIDE IN THE JANITOR'S CLOSET AN | | | EXHAUST FAN PER 1997 SMC 503.2 | | | 4. DUCT MATERIAL SCHEDULE REQUIRED | | | | | | NOTES: SEPERATE PERMIT FOR HOODS, GAS, | | | FIER-SUPPRESSION SYSTEM, WALK-IN | | | COOLERS/FREEZERS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2000-12-17 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-12-17 |
Time |
08:20 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW OF COMMENTS | | | DATED 09-19-00 NOT APPROVED,PAUL SCHMITZ | | | (1) SHT P-4,P-2 WTR HTR IS LOCATED ON | | | FLOOR T/P, P/D TERMINATE TO FLOOR SINK | | | IN JANITORS CLOSET #208. | | | (3) SHT P-8 SHOWS AAV VENTS IN ATTIC | | | SPC 94 SEC 904.1.3 MIN.OF ONE 3"VTR. | | | (5) SHT P-2 SHOW DETAIL OF CONDENSATE | | | OVER FLOW AS BUILT. (NO GOOSENECK) | | | (7) SHT P-3 SHOWS THE REQ WHEEL CHAIR | | | TURNING SPACE IN RM # 216,219 INFRINGING | | | IN WATER CLOSET SPACE. FACBC 4.2.3 | | | (9) SAME AS NOTE (1) WTR HTR TO BE | | | READLY ACCESSIBLE. SHOW AS BUILT. | | | END OF COMMENTS 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-09-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-19 |
Time |
18:28 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-09-19 |
Time |
17:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)WATER HEATERS SHALL BEREADILY | | | ACCESSIBLE.SPC SEC.501.7. | | | | | | 2)THE MIN.SIZE GAS LINE TO ITEMS P-14, | | | P-16,P-17 SHALL BE 1 1/4" PER SGC TABLE | | | 305.4(A). | | | | | | 3)THE SANITARY SYSTEM REQUIRES ONE MAIN | | | VENT STACK OR STACK VENT THROUGH THE | | | ROOF (MIN.3")SPC 904.3.1. | | | | | | 4)DESIGN OF DRAINAGE SYSTEM FOR GREASY | | | WASTE SYSTEM SHALL COMPLY W/SPC SEC.921 | | | FOR HORIZONTAL COMBINATION WASTE AND | | | VENT SYSTEM. | | | | | | 5)AN OVERFLOW IS REQD.ON THE CONDENSATE | | | SYSTEM PRIOR TO THE CONNECTION WITH THE | | | STORM DRAINAGE SYSTEM OR CONNECTION | | | SHALL BE INDIRECT.SPC SEC.804.3,806. | | | | | | 6)SHT.A2.2-APPEARS TO SHOW FLOOR DRAINS | | | LOCATED IN THE MECHANICAL ROOM.LOCATION | | | OF FLOOR DRAINS SHALL COMPLY W/SPC SEC. | | | 409.4.4.1. | | | | | | 7)SHT.A2.3-SHOW THE REQD.WHEELCHAIR | | | TURNING SPACE IN THE TOILET ROOMS #216, | | | 219.COMPLY W/FACBC SEC.4.2.3.THE TURNING | | | SPACE THAT IS CURRENTLY SHOWN HAS THE | | | WATER CLOSET INFRINGING COMPLETELY INTO | | | THE SPACE. | | | | | | 8)CLARIFY THE AREA WHERE THE GAS PIPING | | | PENETRATES THE EXTERIOR WALL INTO THE | | | BUILDING.WHAT IS THE USE OF THIS SPACE? | | | | | | 9)ADDENDUM TO COMMENT #1-SUPPLY A SHIP'S | | | LADDER AND PLATFORM OR RELOCATE WATER | | | HEATER TO FLOOR. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-09-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-08 |
Time |
11:12 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-09-08 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-31 |
Time |
12:52 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-08-31 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)THE LAYOUT OF THE RESTROOMS ON THE | | | LIFE SAFETY PLANS DOESN'T CORRELATE WITH | | | THE OTHER SHEETS.COUNTYWIDE AMENDMENTS | | | TO SPC SEC.104.2.1. | | | | | | 2)WATER HEATERS SHALL BE READILY ACCESS- | | | IBLE PER SPC SEC.501.7.SUPPLY FIXED | | | LADDER AND PLATFORM OR RELOCATE WATER | | | HEATER TO FLOOR. | | | | | | 3)A UNION SHALL BE INSTALLED DOWNSTREAM | | | OF THE MANUAL SHUTOFF VALVE BY THE | | | SOLENOID VALVE ON THE GAS SYSTEM PER | | | NFPA 54 SEC.5.5.4.(S.O.V.IS SHOWN AS | | | SOLENOID VALVE.CLARIFY.) | | | | | | 4)THE MIN.SIZE GAS LINE TO ITEMS P-14, | | | P-16,P-17 SHALL BE 1 1/4" PER SGC TABLE | | | 305.4(A). | | | | | | 5)THE SANITARY SYSTEM REQUIRES ONE MAIN | | | VENT STACK OR STACK VENT THROUGH THE | | | ROOF(MIN.3").SPC 904.3.1. | | | | | | 6)DESIGN OF DRAINAGE SYSTEM FOR GREASY | | | WASTE SHALL COMPLY W/SPC SEC.921 FOR | | | HORIZONTAL COMBINATION WASTE AND VENT | | | SYSTEM. | | | | | | 7)AN OVERFLOW IS REQD.ON THE CONDENSATE | | | SYSTEM PRIOR TO THE CONNECTION WITH | | | THE STORM DRAINAGE SYSTEM OR CONNECTION | | | SHALL BE INDIRECT.SPC 804.3,806. | | | | | | CALL 561-569-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-08-19 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-19 |
Time |
12:32 |
Rev Time |
1.75 |
| Received By |
tlarge |
Date |
2000-08-19 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)TOILET ROOM INSIDE THE RESTROOM IS | | | A COMPONENT OF THE RESTROOM AND THE | | | WIDTH OF THE TOILET ROOM SHALL BE MIN. | | | 83"(IF LAV.IS LOCATED ADJACENT TO W.C.) | | | SEE FACBC SEC.4.17.3. | | | | | | 2)SHOW REQUIRED WHEELCHAIR TURNING SPACE | | | IN RESTROOMS 203,205,219,216.PER FACBC | | | SEC.4.2.3. | | | | | | 3)WAINSCOTING TO 4' IS REQD.IN ALL THE | | | TOILET ROOMS PER SBC SEC.1204.2. | | | | | | 4)DISHWASHER SHALL DISCHARGE TO SANITARY | | | PER CITY ORDINANCE. | | | | | | 5)DOORS CANNOT SWING INTO CLEAR FLOOR | | | SPACE OF FIXTURES.FACBC SEC.4.17.5,4.22. | | | | | | 6)SUBMIT COMPLETE GAS DRAWING FOR RE- | | | VIEW.COMPLY W/ATTACHED REQS. | | | | | | 7)SANITARY SYSTEM REQUIRES ONE MAIN | | | VENT THRU ROOF FOR USE WITH AUTOMATIC | | | AIR ADMITTANCE VALVES PER MANUF. | | | INSTALLATION INSTRUCTIONS. | | | | | | 8)CONDENSATE DISPOSAL SHALL COMPLY W/ | | | SMC SEC.304.8.3. | | | | | | 9)RECEPTORS RECEIVING INDIRECT WASTES | | | SHALL BE FLOOR SINKS PER SPC SEC.807.1. | | | | | | 10)DESIGN OF DRAIN SYSTEM FOR FLOOR | | | SINKS/FLOOR DRAINS SHALL COMPLY W/SPC | | | SEC.921. | | | | | | 11)SHT.P-9-DRINKING FOUNTAINS ARE NOT | | | SHOWN ON SANITARY RISER. | | | | | | 12)WATER HEATER IN JANITOR CLOSET SHALL | | | BE READILY ACCESSIBLE PER SPC 501.7. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-19 |
Time |
06:43 |
Rev Time |
2.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) SHT P-A2.3 REST RM #202,206 DOORS TO | | | SWING OUT. FACBC 4.23.2 | | | (2) SHT P-4 JANITORS CLOSET WTR. HTR TO | | | BE READLY ACCESSIBLE SPS 94 SEC 501.7 | | | (3) SHT P-4 KITCHEN #223 CONTACT | | | DEPT OF HOTEL BUSINESS REGULATION FOR | | | THEIR PLAN REVIEW 954-958-5520. | | | (4) SHT P-7 DISHWASHER TO SANITARY SEWER | | | LOCAL ORDINANCE REGIONAL SEWER PLANT. | | | (5) SHT P-7 GAS PIPING ISOMETRIC REQ. | | | SHOW TOTAL DEVELOPED LGTH,TOTAL BTU'S | | | BTU'S OF EA APPLIANCE,TYPE OF MATERIAL, | | | PSI ON SYSTEM.SGC 94 SEC 104.2 | | | (6) SHT P-8,9 AIR ADMITANCE VALVES, | | | ONE VTR ON EACH SANITARY & GREASE WASTE | | | LATERIAL TO BUILDING SEWER. | | | END OF COMMENTS |
|
|