| Notes |
| 2001-01-08 00:00:00 | NOTE: FIRE SPRINKLER PERMIT 00061349 | | | ISSUED, M. CARSILLO. | | | 1. SHEET A-0 CODE REFERENCES NOT CORRECT | | | MECHANICAL CODE SHOULD BE 1997 | | | BUILDING CODE"" 1997 | | | UNDER PLUMBING CODE REFERENCE IS TO | | | 1994 MECHANICAL CODE SHOULD BE 1994 | | | PLUMBING CODE. | | | 2. SHEET A-1 INDICATE USE FOR SHADED | | | AREA INDICATED ON PLAN. DETAIL #10 AND | | | MALL COMMENTS #1. | | | SHEETS A-1 AND A-3 NOTE 4&6 PROVIDE | | | PRODUCT APPROVALS FOR IMPACT RESISTANT | | | GLAZING AS PER 1997 SBC, SSTD12-97. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-06-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-27 |
Time |
20:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-27 |
Time |
20:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-07-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-06-26 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-06-26 |
Time |
12:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) WRONG FIRE CODE REFERENCE. SHOULD BE | | | NFPA 101,LIFE SAFETY CODE, 1985 EDITION | | | INSTEAD OF NFPA 101, LIFE SAFETY CODE, | | | 1991 EDITION. | | | 2) NO FIRE SPRINKLER SYSTEM DRAWINGS | | | INCLUDED IN MAIN PERMIT SET. | | | 3) A 44 INCH AISLE TO BE MAINTAINED TO | | | REAR EXIT DOOR IN BACK ROOM. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-31 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-31 |
Time |
11:17 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-31 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | RECIEVED THE AIR BALANCE SCHEDULEAND | | | INCLUDED IN PLANS SAME. | | | ITEM #1 ON PREVIOUS REVIEW NEEDSTO BE | | | SUBMITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-19 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-19 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO:******************************** | | | 1.DUCT MATERIAL AND CONNECTION DETAILS | | | REQUIRED PER FLORIDA ENERGY EFFICIENCY | | | CODE. | | | 2.THREE (3) COPIES OF THE AIR BALANCE | | | SCHEDULE WITH THE DESIGN PROFESSIONAL | | | WHO SIGNED AND SEALED THE PLANS, THIS IS | | | REQUIRED BEFORE THE ROUGH INSPECTION IS | | | SCHEDULED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-26 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-26 |
Time |
14:26 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-26 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | INDICATE THE RETURN AIR FROM MAIN STORE | | | AREA TO THE AHU. | | | PROVIDE CFM VALUE OF EACH DROP IN MAIN | | | STORE AREA. | | | PROVIDE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | REQUIRED OUTSIDE AIR PER ASHRAE 62-89. | | | PROVISO: DUCT MATERIAL & CONNECTION | | | DETAILS REQUIRED PER FLORIDA | | | ENERGY EFFICIENCY CODE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-19 |
Time |
17:01 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-06-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-28 |
Time |
18:33 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-06-28 |
Time |
18:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER TABLE | | | 407 OF THE SPC.DRINKING FOUNTAIN SHALL | | | COMPLY W/FACBC SEC.4.1.3(10)(A). | | | PROVISIONS SHALL BE MADE FOR PEOPLE WHO | | | HAVE TROUBLE BENDING OR STOOPING. | | | | | | CLEAR FLOOR SPACE UNDER LAV.TO FINISH | | | FLOOR SHALL COMPLY W/FACBC SEC.4.19.2. | | | | | | GRAB BARS SHALL COMPLY W/FACBC SEC. | | | 4.16.4.(LENGTH)AND MEASURED TO ITS | | | CENTER NOT THE TOP OF BAR PER FACBC FIG. | | | 29.(SEE NOTE #11 ON A-2 | | | | | | TURNING SPACE IN TOILET ROOM INFRINGES | | | ON WATER CLOSET.COMPLY W/FACBC SEC.4.2.3 | | | | | | REVISE SANITARY AND WATER RISERS TO SHOW | | | REQD.DRINKING FOUNTAIN. | | | | | | DRESSING ROOMS SHALL COMPLY W/FACBC SEC. | | | 4.1.6(H),4.35.1.-4.35.5. | | | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | | REACHED AT 561-659-8096,EXT.8377. | | | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |
|
|