Plan Review Details - Permit 00061244
Plan Review Stops For Permit 00061244
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-08-22 Cont ID  
Sent By drunnels Date 2000-08-22 Time 10:28 Rev Time 1.00
Received By drunnels Date 2000-08-22 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-14 Cont ID  
Sent By drunnels Date 2000-08-14 Time 07:13 Rev Time 1.00
Received By drunnels Date 2000-08-14 Time 07:28 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PERMIT PLANS &
 APPLICATION. FIRE SPRINKLER PERMIT TO BE
 ISSUED PRIOR TO BUILDING ISSURANCE OF
 BUILDING PERMIT.
 2.SUBMIT PRODUCT APPROVAL FOR WINDOW AND
 DOORS FOR STOREFRONT. METRO DADE COUNTY
 OR SBCCI.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-31 Cont ID  
Sent By drunnels Date 2000-07-31 Time 15:55 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
 1.LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE
 2. SUBMIT PRODUCT APPROVALS PER 1997 SBC
 SSTD12-97 OR METRO DADE ON DOORS &
 WINDOWS & STOREFRONTS.
 3. SUBMIT ENERGY CALCS. WITH SIGNATURE
 OF OWNER/AGENT WHERE NOTED.
 4. FIRE SPRINKLER PERMIT TO BE ISSURED
 PRIOR TO ISSURANCE OF BUILDING PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-03 Cont ID  
Sent By lsmith Date 2000-07-03 Time 09:43 Rev Time 2.00
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED:
 1.FIRE SPRINKLER PERMIT TO BE ISSUED
 PRIOR TO ISSUANCE OF BUILDING PERMIT.
 2.LETTER FROM SPEC. INSPECTOR RELEASING
 SPACE.
 3. NEED ROOMS LABELED ON PLANS
 4. PROVIDE COMPLETE SEATING DETAILS
 5. DIMENSIONS ON PLANS INCOMPLETE
 6. CLARIFY REFERENCES TO 1-A.1 & A-A.5
 ON SHEET A-1.
 7. SHOW WALL DETAILS FOR 2 HR DEMISING
 WALL SHOWN ON PLANS.LISTING FROMEX UL
 8. SUBMIT PRODUCT APPROVALS PER 1997 SBC
 SSTD12-97 OR METRO DADE ON DOORS &
 WINDOWS & STOREFRONTS.
  
 9.SUBMIT ENERGY CALCS. WITH SIGNATURES
 WHERE NOTED BY OWNER & ARCH.
 11. BUILDING CODE REFERENCED ON COVER
 PAGE REFERENCES 1994/ SHOULD BE 1997.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-28 Cont ID  
Sent By dpalmer Date 2000-07-28 Time 07:47 Rev Time 0.00
Received By dpalmer Date 2000-07-28 Time 07:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 20:06 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 07:42 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO *************
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. PLEASE SHOW LOAD CALCULATIONS.
  
  
 2)NOTE: PLEASE SUBMIT ALL AIC RATINGS
 OF ALL EQUIPMENT. MAINS/PANELS ARE TO BE
 RATED FOR ALL AVAILABLE FAULT CURRENTS.
 110-9/215-5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-18 Cont ID  
Sent By mcarsill Date 2000-08-18 Time 15:41 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-07-28 Cont ID  
Sent By mcarsill Date 2000-07-28 Time 08:08 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) NO FIRE SPRINKLER SYSTEM PLANS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 DRAWINGS.
 2) IN ASSEMBLY OCCUPANCIES, THE MAIN
 EXIT DOOR(S) CAN BE EQUIPPED WITH
 LOCKING DEVICES IN ACCORDANCE WITH
 SECTION 5-2.1.5.1., IF THE OCCUPANT
 LOAD IS LESS THAN 500 PERSONS. OTHER
 EXIT DOORS MUS COMPLY WITH THE PANIC
 HARDWARE REQUIREMENT.
 3) PROVIDE PLANS AND PERMIT FOR THE
 INSTALLATION OF FIRE ALARM EQUIPMENT
 IN THE TENANT SPACE.
 4) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE HOOD,DUCT AND
 EXTINGUISHING SYSTEMS.
 5) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 6) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 7) PROVISIONS ARE TO BE MADE FOR AT
 LEAST TWO HANDICAPPED PERSONS.
 8) PROVIDE FLAMESPREAD INFORMATION TO
 THE FIRE MARSHALS OFFICE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-07-03 Cont ID  
Sent By bstaples Date 2000-07-03 Time 09:40 Rev Time 1.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00DENIED SEE ATTACHMENT, M. CARSILLO 6/29

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-26 Cont ID  
Sent By cthirben Date 2000-07-26 Time 16:06 Rev Time 0.00
Received By cthirben Date 2000-07-26 Time 16:08 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 ADDITIONAL PERMIT REQUIRED FOR HOODS,
 FIRE SUPPRESSION, FUEL, WALK-IN COOLER/
 FREEZER
 PROVISO:
 FIRE DAMPERS REQUIRED AT RATED WALLS
 WHERE THE DUCT PENETRATES AS PER 1997
 SMC 610.1.2....

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-24 Cont ID  
Sent By cthirben Date 2000-06-23 Time 16:25 Rev Time 1.00
Received By cthirben Date 2000-06-24 Time 09:50 Sent To  
Notes
2001-01-08 00:00:00DENIED:******************************
 THE FOLLOWING REQUIREMENTS ARE TO BE
 PROVIDED:
 1. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
 2. DUCT MATERIAL SCHEDULE PER FLORIDA
 ENERGY CODE.
 3. FLEX DUCT CONNECTION DETAIL.
 4. GRILLE, DIFFUSERS AND REGISTERS
 SCHEDULE.
  
 PROVISO:
 SEPERATE PERMIT REQUIRED FOR HOOD,
 GAS, FIRE-SUPPRESSION SYSTEM,WALK-IN
 COOLERS/FREEZERS.
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY FIRE ALARM SYS-
 TEM OR TIED-IN TO HORN AND STROBE AS
 PER NFPA 90A 4.4.4.2 AND 4.4.4.3..

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-12-31 Cont ID  
Sent By pschmitz Date 2000-12-31 Time 09:55 Rev Time 0.75
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO: SHT.A-4.1
 CORRIDOR GAS PIPING ON A SEPERATE DRWG.
 ON FILE.PES

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 22:56 Rev Time 0.50
Received By tlarge Date 2000-08-10 Time 22:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-30 Cont ID  
Sent By tlarge Date 2000-07-30 Time 06:27 Rev Time 2.75
Received By tlarge Date 2000-07-29 Time 14:49 Sent To  
Notes
2001-01-08 00:00:00`1)WIDTH OF HANDICAP TOILET STALL DOOR
 OPENING SHALL COMPLY W/FACBC SEC.4.17.5
 AND FIGURE 30.SHT.A1.
  
 2)MIN.WIDTH OF HANDICAP STALL SHALL BE
 83" PER FACBC SEC.4.17.3,SPC 403.1
  
 3)THE WATER HEATER LISTING IS OVER
 200,000 BTU'S AND THEREFORE CLASSIFIED
 AS A BOILER AND SHALL COMPLY W/THE
 FOLLOWING CODE SECS.:
 A)SGC SECS.507.7,507.8
 B)SMC SEC.1003.1-1003.4.
 C)SMC SEC.1004.1,1004.2.
 D)TABLE 1003,FOOTNOTE #8.
 E)SBC 704.1.3.3.
 SUBMIT MANUF.SHEETS FOR BOILER.
  
 4)SHT.A4.1-DRY VENTS NOT PERMITTED PER
 SPC SEC.906.2.1.(SEE FLOOR SINK & W.C.)
  
 5)WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 6)CIRCUIT AND LOOP SYSTEM SAHLL COMPLY
 W/SPC SEC.914.2.
  
 7)SIZE OF HORIZONTAL DRAIN FOR W.C.'S IN
 WOMEN'S R.R.SHALL COMPLY W/SPC TABLE
 714.2,FOOTNOTE #2.
  
 8)FLOOR SINK AND HAND SINK SHALL
 DISCHARGE TO G.W.PER 1004.1,1004.4.
  
 9)SHT.A4.1-SIZING/DESIGN OF GAS SYSTEM
 SHALL COMPLY W/SGC.SYSTEM IS UNDERSIZED
 AS DESIGNED.SEE ATTACHED LIST FOR GAS
 DRAWING REQS.
  
 CALL 561-659-8096 EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By tlarge Date 2000-06-27 Time 21:14 Rev Time 1.50
Received By tlarge Date 2000-06-27 Time 20:34 Sent To  
Notes
2001-01-08 00:00:00SIZE OF HANDICAP STALL SHALL COMPLY W/
 FACBC SEC.4.17.3
  
 DISHWASHER SHALL DISCHARGE TO SANITARY
 PER CITY OF WPB ORDINANCE.
  
 DRY VENTS NOT PERMITTED PER SPC SEC.
 906.2.1.(SEE RESTROOMS AND GREASY WASTE)
  
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS SEC.911.1.1.
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.2.
  
 SIZE OF HORIZ.DRAIN FOR WATER CLOSETS
 AND URINALS SHALL COMPLY W/SPC TABLE
 714.2,FOOTNOTE #2.
  
 FLOOR SINK AND HAND SINK SHALL DRAIN TO
 GREASY WASTE PER SPC SEC.1004.4.
  
 TWO WAY CLEANOUT REQD.ON BUILDING DRAIN
 (GREASY WASTE)PER SPC SEC.710.4.
  
 FLOOR SINK SHALL BE USED IN LIEU OF HUB
 DRAIN.SPC 807.1.2.,807.1.3.
  
 A UNION IS REQD.DOWNSTREAM OF GAS
 CONTROLS PER NFPA 54 SEC.5.5.4.
  
 SUBMIT COPY OF/OR MAKE REFERENCE TO
 APPLICABLE GAS SIZING TABLE USED FOR
 SYSTEM DESIGN.SYSTEM DOES NOT COMPLY W/
 SGC FOR PROPER SIZING.
  
 HEATERS OVER 200,000 BTU'S SHALL COMPLY
 W/SPC SEC.507.7.
  
 SIZE THE C.W.DROP TO THE MENS/LADIES
 RESTROOMS.COMPLY W/COUNTYWIDE AMENDMENTS
 SEC.607.7.
  
 WATER SUPPLY TO RESTROOMS AND KIT.AREA
 SHALL COMPLY W/SPC SEC.610.4.1.,610.4.2.
  
 WATER DIAGRAM SHOWS OVER 2 FIXTURES ON
 1/2" C.W.LINE.COMPLY W/SPC SEC.607.7.
  
 GREASY WASTE SYSTEM SHOWS 6"LINE
 DRAINING INTO 4"LINE.COMPLY W/SPC SEC.
 307.5.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.