Plan Review Details - Permit 00061167
Plan Review Stops For Permit 00061167
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-24 Cont ID  
Sent By hpiskura Date 2000-07-24 Time 16:24 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By dpalmer Date 2000-08-14 Time 10:16 Rev Time 0.00
Received By dpalmer Date 2000-08-14 Time 10:16 Sent To  
Notes
2001-01-08 00:00:00PROVISO
  
 PROVIDE REVISED PANEL SCHEDULE BEFORE
 FINAL W/ CORRELATING BRANCH `#`S

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-29 Cont ID  
Sent By dpalmer Date 2000-06-29 Time 10:16 Rev Time 0.00
Received By dpalmer Date 2000-06-29 Time 10:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-14 Cont ID  
Sent By rturnque Date 2000-08-14 Time 10:41 Rev Time 0.20
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-18 Cont ID  
Sent By rturnque Date 2000-07-18 Time 10:13 Rev Time 0.15
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-08-08 Cont ID  
Sent By cthirben Date 2000-08-08 Time 09:04 Rev Time 1.00
Received By cthirben Date 2000-08-08 Time 15:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-08-14 Cont ID  
Sent By tlarge Date 2000-08-14 Time 09:35 Rev Time 0.33
Received By tlarge Date 2000-08-14 Time 09:35 Sent To  
Notes
2001-01-08 00:00:00PROVISO:DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).
  
 FIXTURES SHALL BE INSTALLED TO ALLOW
 CLEAR FLOOR SPACE UNDER FIXTURE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-09 Cont ID  
Sent By tlarge Date 2000-08-09 Time 17:07 Rev Time 0.50
Received By tlarge Date 2000-08-09 Time 17:06 Sent To  
Notes
2001-01-08 00:00:00COMPLY W/ALL PREVIOUS COMMENTS.
  
 NEW LAV.CANNOT INFRINGE ON CLEAR FLOOR
 SPACE FOR DRINKING FOUNTAIN.FOUNTAIN
 SHALL COMPLY W/FACBC SEC.4.1.3.(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 12:02 Rev Time 0.50
Received By tlarge Date 2000-07-12 Time 12:02 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY AND WATER ISOMETRICS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 SHOWER SHALL COMPLY W/FACBC FOR CONTROL
 MOUNTING HEIGHT,GRAB BARS,& SPRAY UNIT.
 CURBS ARE NOT PERMITTED IN SHOWERS THAT
 MEASURE MIN.30"X 60".PER FACBC SEC.
 4.21.2-4.21.7.
  
 SUBMIT RISER FOR NEW 2"WASTE FOR TRENCH
 DRAIN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 IF TRENCH DRAIN WILL COLLECT CHEMICALS
 A NEUTRALIZATION TANK WILL BE REQUIRED
 PER SPC SEC.701.5,701.7,801.4.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 TIMOTHY LARGE