Plan Review Details - Permit 00061157
Plan Review Stops For Permit 00061157
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-08-17 Cont ID  
Sent By drunnels Date 2000-08-17 Time 11:47 Rev Time 1.00
Received By drunnels Date 2000-08-17 Time 11:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-07-26 Cont ID  
Sent By drunnels Date 2000-07-26 Time 07:29 Rev Time 0.00
Received By nleiva Date 2000-07-28 Time 16:24 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. FLORIDA ENERGY SHEETS NOT SIGNED BY
 OWNER.
 2. GLAZING: PROVIDE PRODUCT APPROVAL FOR
 WIND LOADS AND IMPACT PROTECTION,1997
 SBC OR METRO DADE COUNTY.
 3. SHEET A-2.1 PLATFORM # 104 NOT
 ACCESSABLE TO HANDICAP.
 4. SHEET A-4.2 PLATFORM EXCEEDS MAX.
 HEIGHT OF 30"; SEE 1997 SBC SECTION
 403.2.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-07-21 Cont ID  
Sent By fknapp Date 2000-07-21 Time 10:28 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
 *****************PROVISO****************
  
 2ND PLAN REVIEW
  
 1)PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR
 WINDLOADS AND IMPACT PROTECTION ON ALL
 GLAZING TO BE UNDER SEPARATE PERMIT.
  
 2)SIGNS TO BE UNDER SEPARTE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-01 Cont ID  
Sent By bstaples Date 2000-06-23 Time 14:12 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE SPRINKLER APPROVED MC, 6/23/00
 REVIEW 7/1/00
 1. FLORIDA ENERGY SHEETS NOT SIGNED BY
 OWNER.
 2. GLAZING PROVIDE PRODUCT APPROVAL FOR
 WIND LOADS AND IMPACT PROTECTION, 1997
 SBC OR METRO DADE COUNTY.
 3. SHEET A-2.1 WALL TO TENNANT TO BE
 2 HR. RATED SEE 1997 SBC. SHEET A-4.2
 NOT IN PLANS.(MUST CONSTRUCT BOTH SIDES)
 4. TABLES OBSTRUCT EXITS REVISE LAY OUT.
 5. SIGNS REQUIRE SEPERATE PERMITS.
 6. CODE REFERENCE IS TO 1999 SBC,
 REVISE TO 1997 SBC.
 7. PLATFORM #104 NOT ACCESSABLE TO
 HANDICAPPED AT BAR #1.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-12-13 Cont ID  
Sent By dpalmer Date 2000-12-13 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2000-12-13 Time 17:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-09 Cont ID  
Sent By dpalmer Date 2000-08-09 Time 11:47 Rev Time 0.00
Received By dpalmer Date 2000-08-09 Time 11:47 Sent To  
Notes
2001-01-08 00:00:00**********PROVISO ********************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST AND
 SECOND REVIEW. LOAD CALCUALTIONS TO BE
 CORRECTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-24 Cont ID  
Sent By dpalmer Date 2000-07-24 Time 05:30 Rev Time 0.00
Received By dpalmer Date 2000-07-24 Time 05:30 Sent To  
Notes
2001-01-08 00:00:00**************** PROVISO **************
  
 1)NOTE: PLEASE SEE ORIGINAL NOTES AS
 FOR LOAD CALCULATIONS SHOWING ALL
 CONTINUOUS LOADS AT 125% (LIGHTING )
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEWST PALM BEACH.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-22 Cont ID  
Sent By dpalmer Date 2000-06-22 Time 17:37 Rev Time 0.00
Received By dpalmer Date 2000-06-22 Time 17:37 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE:PLEASE SUBMIT AND SHOW LOAD
 CALCULATION. GIVE BREAKDOWN ON LOADS
 INCLUDING LIGHTING LOADS WHICH ARE TO BE
 AT 125% FOR CONTINUOUS DUTY.
 SHOW SQ. FT CALCS AND WITH OTHER LOAD
 CALCS.
  
 PLEASE SUBMIT THA ABOVE INFORATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-08-17 Cont ID  
Sent By mcarsill Date 2000-08-17 Time 13:46 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-23 Cont ID  
Sent By bstaples Date 2000-06-23 Time 14:11 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRE SPRINKLER APPROVED 6/23 00 MC.
 PLAN REVIEW FAILED M.CARSILLO SEE NOTES
 ATTACHED TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-12-20 Cont ID  
Sent By ndenmark Date 2000-12-20 Time 09:49 Rev Time 0.25
Received By ndenmark Date 2000-12-20 Time 09:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-19 Cont ID  
Sent By cthirben Date 2000-07-19 Time 17:28 Rev Time 1.00
Received By cthirben Date 2000-07-19 Time 17:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-23 Cont ID  
Sent By cthirben Date 2000-06-23 Time 09:47 Rev Time 1.00
Received By cthirben Date 2000-06-23 Time 09:34 Sent To  
Notes
2001-01-08 00:00:00NOTES:********************************
 1. PROVIDE ADDITIONAL INFORMATION ON THE
 PRE-FAB ELECTRIC FIRE PLACE.
 2. ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR WALK-IN COOLER/FREEZER, HOOD FIRE
 SUPRESSION, FUEL ETC. SUBMIT PLANS
 WITH PERMIT APPLICATION.

Review Stop P PLUMBING
Rev No 7 Status P Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 12:44 Rev Time 0.50
Received By tlarge Date 2000-08-17 Time 12:43 Sent To  
Notes
2001-01-08 00:00:00*******************PROVISO**************
 DESIGN OF DRAINAGE SYSTEM FOR BAR AREAS
 SHALL COMPLY W/SPC SEC.921 FOR WASTE AND
 VENT SYSTEM.

Review Stop P PLUMBING
Rev No 6 Status F Date 2000-08-10 Cont ID  
Sent By tlarge Date 2000-08-10 Time 10:51 Rev Time 2.00
Received By tlarge Date 2000-08-10 Time 10:51 Sent To  
Notes
2001-01-08 00:00:001)SHT.A2.1-THE DIMENSIONS OF THE
 HANDICAP STALLS IN THE RESTROOMS SHALL
 COMPLY W/FACBC SEC.4.17.3(NEW CONSTRUCT-
 ION) AND FIGURE 30(A).MINIMUM WIDTH
 SHALL BE 83".THE DETAIL ON THE PLANS
 IS FOR TOILET ROOMS,NOT STALLS.
  
 2)THE SYSTEM OF PIPING ENCOMPASSING THE
 FLOOR DRAIN AND FLOOR SINKS SHALL BE
 DESIGNED TO COMPLY W/SPC SEC.921.4.1.

Review Stop P PLUMBING
Rev No 5 Status N Date 2000-08-17 Cont ID  
Sent By tlarge Date 2000-08-17 Time 12:47 Rev Time 0.00
Received By tlarge Date 2000-08-10 Time 06:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-07-26 Cont ID  
Sent By pschmitz Date 2000-07-26 Time 07:12 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW REF. SPC 94
 (1) PROVISO: SHT P2-1 4TH PLAN REVIEW.
 DISHWASHER,BY LOCAL ORDINANCE # 2938-96
 W.PALM BCH REG SEWER TREATMENT PLANT.
 SHALL BY PASS GREASE WASTE SYSTEM,AND
 CONNECT TO SANITARY SYSTEM.
 (2)SHT P2-1 GAS LINE TO BE PERMITED
 SEPERATLY, AS/ NOTE, TO FIELD VERIFY
 SIZE & LOCATION OF MANIFOLD,ISOMETRIC
 SHOWING TOT DEVELOPED LGTH, TOT BTU'S
 TYPE OF MATERIAL, GAS PSI.SGC 97 SEC 104
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-07-24 Cont ID  
Sent By pschmitz Date 2000-07-24 Time 14:57 Rev Time 2.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1)THIRD PLAN REVIEW,PLANS SHALL BE
 REVIEWED BY DEPT OF HOTEL REGULATION,AS
 STATED,FOR THE THIRD TIME. 954-958-5520.
 (2)SHT P2.1 DISHWASHER,TO BY PASS GREASE
 WASTE,CONNECT TO SANITARY SEWER,LOCAL
 ORDINANCE #2938-96.
 (3)SHT P2-1 GAS LINE, ISOMETRIC REQ.
 SHOW TOT BTU'S, TOT DEVELOPED LGTH,TYPE
 MATERIAL, PIPE SIZES, GAS PSI.
 SGC 97 SEC 104.2
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-19 Cont ID  
Sent By pschmitz Date 2000-07-19 Time 09:54 Rev Time 0.00
Received By pschmitz Date 2000-07-24 Time 13:50 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) PREVIOUS COMMENT DATED 06-27-00
 NOT ADDRESSED,PLAN REVIEW & APPROVAL
 FROM DEPT. OF HOTEL BUSINESS REGULATION
 REQUIRED TO COMPLETE PLUMBING PLAN
 REVIEW. CONTACT 954-958-5520.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By tlarge Date 2000-06-27 Time 19:48 Rev Time 1.25
Received By pschmitz Date 2000-06-27 Time 19:48 Sent To  
Notes
2001-01-08 00:00:00CLEARLY SHOW LENGTH AND WIDTH OF HANDI-
 CAP STALLS.SIZE SHALL COMPLY W/FACBC
 SEC.4.17.3.
  
 PLANS SHOW PREPARATION AREA.CLARIFY TYPE
 OF OPERATIONS TO BE PERFORMED IN THIS
 AREA.IF FOOD PREP WILL TAKE PLACE,PLANS
 SHALL BE ROUTED TO DBR FOR REVIEW AND
 APPROVAL.IF NO FOOD WILL BE PREPARED OR
 SOLD,PLANS SHALL BE REVIEWED AND
 APPROVED BY PALM BEACH COUNTY HEALTH
 DEPT.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7.
  
 SHT.P0.1-CLARIFY CODE SEC.1002.4.THERE
 IS NO SUCH SECTION.
  
 TEMPERATURE TO RESTROOMS SHALL NOT
 EXCEED 110 DEGREES PER FEC 412.1.
  
 CALL 561-659-8096 EXT.8377 IF YOU HAVE
 ANY QUESTIONS.TIMOTHY LARGE,PLUMBING
 PLANS EXAMINER.