| Plan Review Stops For Permit 00061076 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-19 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK PER B.STAPLES |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-07-14 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-07-14 |
Time |
08:52 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. ITEM 5 SPECIAL INSPECTOR LETTER NOT | | | ON FILE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-07-13 |
Time |
10:36 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. SEE ITEMS 2 & 5 PRIOR REVIEW. NOT | | | SUBMITTED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-22 |
Time |
12:50 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FIRE SPRINKLER PERMIT REQUIRED BEFORE | | | BUILDING PERMIT CAN BE ISSUED. | | | 2. PROVIDE PRODUCT APPROVAL FOR WINDOW | | | SYSTEM, METRO DADE COUNTY OR SBC 1997. | | | NOTE: DOORS OK. | | | 3. FLORIDA ENERGY SHEETS NOT SIGNED BY | | | OWNER. | | | 4. SIGNS REQUIRE SEPERATE PERMITS. | | | 5. LETTER FROM SPECIAL INSPECTOR | | | RELEASING THE SPACE FOR PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
N |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
17:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-18 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-18 |
Time |
19:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-13 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-13 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** PROVISO *************** | | | | | | 1)NOTE: PLEASE SEE ORIG. NOTES. THE | | | DIMMER SCHEDULE SHOWS SWITCH #6 FOR | | | FIXTURE "X" WHICH IS SHOWN AS EXIT SIGN. | | | SWITCHING THE EXIT SIGN IS NOT PERMITTED | | | IF THIS IS NOT THE CASE PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE SEE AND NOTE THAT ON E-1 | | | YOU SHOW TWO WATER HEATERS @ 3500W? YET | | | THE LOAD CALCULATION SHOWS A TOTAL OF | | | 4800W? PLEASE CHECK AND RE-DO. | | | | | | 3)NOTE: PLEASE SEE E-2. THE SHOW WINDOW | | | LIGHTING IS SHOWMN AT .4 KVA. AND ON | | | E-1 ITIS SHOWN AT .45 KVA. 125% OF | | | .4 IS NOT .45. PLEASE VERIFY. | | | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATINGS OF | | | THE DISCONNECTS. IT APPEARS THAT THEY | | | ARE FUSED DISC. PLEASE GIVE FUSE TYPE. | | | | | | | | | 5)NOTE: AS BEFORE; PLEASE SHOW DIMMER | | | LOCATION ON PLANS. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | | 561-659-8096 EXT 8372 | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-21 |
Time |
22:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-21 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SHOW ALL DIMMER/SWITCH | | | LOCATIONS. | | | | | | 2)NOTE: PLEASE NOTE THAT EXIT LIGHTS ARE | | | SHOWN ON SWITCH #6??? THIS IS NOT | | | PERMITTED AND EMERGENCY LIGHTS ALSO. | | | | | | 3)NOTE:PLEASE NOTE THAT LOAD OF TRACK | | | LIGHTING NEEDS TO BE SHOWN SEPARATE | | | IN CALCULATIONS.ALSO AT 125% FOR CONTIN- | | | UOUS LOAD.22-12 | | | | | | 4)NOTE:SHOW WINDOW IS SHOWNON PANEL AT | | | .4 KW AND ON LOAD CALCS AT .45KW? | | | PLEASE CORRELATE | | | | | | 5)NOTE:PLEASE SUBMIT AIC RATING OF MAIN | | | DISCONNECTS.MAINS//PANLES ARE TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT | | | PER 110-9/215-5 | | | | | | ^0NOTE:LIGHTING IS SHOWN ON LOAD CALCS | | | AT 1,630,,,3W-PER-SQ-AT 125% YOU SHOW | | | TOTAL AT 4,890? PLEASE SHOW,,,I COME UP | | | WITHA DIFFERENT TOTAL. | | | | | | 7)NOTE:PLEASE SEE LOAD CALCS,,YOU SHOW | | | LOADS FOR WATER HEATERS AT 3500 EACH | | | AND DIFFERENT TOTAL LOAD?? THIS ALSO | | | DOES NOT CORRELATE WITH PANEL SCHEDLUE? | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-06-23 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-23 |
Time |
13:38 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO SEE NOTES ATTACHED TO PLANS, | | | M. CARSILLO 6/23/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
18:05 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
18:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-13 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-13 |
Time |
13:41 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED:********************************* | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89. | | | 2.REQUIRES AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-21 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-21 |
Time |
16:05 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-21 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED******************************* | | | 1. PROVIDE OUTSIDE CALCULATIONS PER | | | ASHRAE 62-89. | | | 2. REQUIRES AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. | | | 3. NFPA 90A REQUIRES NOTICATION OF | | | ACTIVATION OF DUCT SMOKE DETECTOR BY | | | VISUAL AND AUDIBLE SIGNAL. THIS IS | | | NOT REQUIRED TO BE TIED IN TO THE | | | MALL FIRE ALARM SYSTEM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-09-22 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-22 |
Time |
12:39 |
Rev Time |
0.30 |
| Received By |
tlarge |
Date |
2000-09-22 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ADD POINT OF USE WATER HEATER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-22 |
Time |
05:36 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-06-22 |
Time |
05:36 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************PROVISO***************** | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. | | | | | | DRESSING ROOM SHALL COMPLY W/FACBC SEC. | | | 4.35.(A BENCH IS REQD.ALONG THE WALL W/ | | | THE LONGER DIMENSION.) |
|
|