| Plan Review Stops For Permit 00061071 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-19 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | OK PER B.STAPLES |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-07-13 |
Time |
16:38 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. REQUIRES LETTER FROM SPECIAL | | | INSPECTOR CALLED 7/13/00. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-22 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
bstaples |
Date |
2000-06-22 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS NOT SIGNED BY | | | OWNER. | | | 2. PROVIDE PRODUCT APPROVAL FOR WINDOW | | | SYSTEM NOTE DOORS HAVE APPROVAL METRO | | | DADE COUNTY. WINDOWS REQUIRE DADE OR | | | SBCCI. | | | 3. FIRE SPRINKLER CONTRACTOR TO SECURE | | | PERMIT PRIOR TO ISSUANCE OF BUILDING | | | PERMIT. | | | 4. SIGNS REQUIRE SEPERATE PERMITS. | | | 5. LETTER FROM SPECIAL INSPECTOR | | | RELEASING THE SPACE FOR PERMIT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-28 |
Time |
20:34 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-28 |
Time |
20:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-13 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-13 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-22 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-22 |
Time |
17:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: EXIT LIGHTS AND EMERGENCY LIGHTS | | | ARE SHOWN AS BEING SWITCHED? THIS IS NOT | | | PERMITTED. | | | | | | 2)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | ALL EQUIPMENT MAINS/PANELS BEING INSTALL | | | -ED. MUST BE RATED FOR THE AVIALABLE | | | FAULT CURRENT. PER 110-9 | | | | | | 3)NOTE: PLEASE SHOW THE LOADS FIGURED | | | FOR TRACK LIGHTING PER 220-12-B | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-06-23 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-23 |
Time |
11:31 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEE PROVISO ATTACHED TO PLANS, | | | M. CARSILLO 6/23/00. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
17:51 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
17:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-13 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-13 |
Time |
14:14 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-13 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: ******************************** | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | ASHRAE 62-89. | | | 2.REQUIRE AIR BALANCE SCHEDULE TO SHOW | | | COMPLIANCE WITH 1997 SMC 501.2. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-21 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-21 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-06-21 |
Time |
13:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED**************************** | | | PROVIDE THE FOLLOWING ITEM: | | | | | | 1. OUTSIDE AIR CALCULATIONS PER ASHRAE | | | 62-89. | | | 2. AIR BALANCE SCHEDULE TO SHOW COMPLI- | | | -ANCE WITH 1997 SMC 501.2. | | | | | | 3. NFPA 90A REQUIRES NOTIFICATION OF | | | ACTIVATION OF DUCT SMOKE DETECTOR BY | | | VISUAL AND AUDIBLE SIGNAL. THIS IS | | | NOT REQUIRED TO BE TIED TO THE MALL | | | FIRE ALARM SYSTEM. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-21 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-21 |
Time |
13:56 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-06-21 |
Time |
13:56 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | RELIEF LINE FOR EWH SHALL DISCHARGE PER | | | SPC SEC.507.8.4. | | | | | | DRESSING ROOM SHALL COMPLY W/FACBC SEC. | | | 4.35. |
|
|