Plan Review Details - Permit 00061070
Plan Review Stops For Permit 00061070
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-26 Cont ID  
Sent By dpalmer Date 2000-06-26 Time 08:07 Rev Time 0.00
Received By dpalmer Date 2000-06-26 Time 08:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-21 Cont ID  
Sent By dpalmer Date 2000-06-21 Time 19:58 Rev Time 0.00
Received By dpalmer Date 2000-06-21 Time 19:58 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT HAVE BEEN MADE
 TO A SIGNED AND SEALED PLAN. THESE
 CHANGES MUST BE MADE BY PERSON OF RECORD
 THIS IS A STATE LAW.
  
 2)NOTE: ALSO SEE THE WIRE SIZES WERE
 CHANGED? ARE NOT RATED FOR OVERCURRENT
 PROTECTION. PLEASE CORRELATE WIRE SIZES
 TO THE NEC.
  
 3)NOTE: PLEASE SHOW THE LOAD AND SIZE
 THAT IS BEING ADDED TO MAIN #3?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
  
  
 4)NOTE: PLEASE SHOW METHOD OF EQUIPMENT
 GROUNDING? PIPE? OR CONDUCTOR?

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-21 Cont ID  
Sent By ndenmark Date 2000-06-21 Time 15:24 Rev Time 1.00
Received By ndenmark Date 2000-06-21 Time 15:24 Sent To  
Notes
2001-01-08 00:00:00PROVISO:
 1) CALL FOR ALL REQUIRED INSPECTIONS
 INCLUDING ROUGH AND PRESSURE TEST PRIOR
 TO INSULATING PIPE