Plan Review Details - Permit 00061043
Plan Review Stops For Permit 00061043
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-20 Cont ID  
Sent By dpalmer Date 2000-06-20 Time 18:50 Rev Time 0.00
Received By dpalmer Date 2000-06-20 Time 18:50 Sent To  
Notes
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: SMOKE DETECTOR IS REQ`D ON
 EACH LEVEL AND OUTSDIE BEDROOM.
 1996 NFPA-72 2-2.1.1.1
  
 2)NOTE:PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) AS PER
 210-11-C-3
  
 3)NOTE:PLEASE LABEL ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECTE
 AS PER 210-8-A-6
  
 4)NOTE:PLEASE SHOW THE REQ`D WP GFI
 OUTLET FOR NEW A/C CU.
  
 5)NOTE:PLEASE SUBMIT THE AIC RATING OF
 NEW 200 AMP PANEL. PANELS/MAINS ARE TO
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 AS PER 110-9/215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ANY
 QUESTIONS PLEASE CALL D.PALMER AT
 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-21 Cont ID  
Sent By cthirben Date 2000-06-21 Time 07:41 Rev Time 1.00
Received By cthirben Date 2000-06-21 Time 07:22 Sent To  
Notes
2001-01-08 00:00:00PROVISO:******************************
 EXHAUST VENTS REQUIRED FOR THE DRYER AND
 THE RANGE.
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-21 Cont ID  
Sent By tlarge Date 2000-06-21 Time 08:13 Rev Time 0.30
Received By tlarge Date 2000-06-21 Time 08:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-07-21 Cont ID  
Sent By rmcdouga Date 2000-07-21 Time 09:54 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***