Plan Review Details - Permit 00061010
Plan Review Stops For Permit 00061010
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-10-12 Cont ID  
Sent By lmartine Date 2000-10-12 Time 10:27 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2000-10-04 Cont ID  
Sent By lmartine Date 2000-06-26 Time 14:15 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:00NO BUILDING WORK SHOWN, APPLICATION FOR
 M.E.P. WORK ONLYLM 10/4/00

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-10-02 Cont ID  
Sent By dpalmer Date 2000-10-02 Time 12:14 Rev Time 0.00
Received By dpalmer Date 2000-10-02 Time 12:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-10-11 Cont ID  
Sent By mcarsill Date 2000-10-11 Time 13:31 Rev Time 0.00
Received By mcarsill Date 2000-10-11 Time 13:31 Sent To  
Notes
2001-01-08 00:00:001) ALL EXIT DOORS SHALL SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 2) ALL EXIT DOORS SHALL BE EQUIPPED WITH
 APPROVED PANIC HARDWARE.
 3) OCCUPANT LOAD TO BE DETERMINED BY THE
 FIRE RESCUE DEPARTMENT.
 4) INTERIOR FINISH IN EXITS TO BE CLASS
 A OR B.
 5) ALL STORAGE ROOMS IF ANY ARE TO BE
 FIRE SEPARATED BY AT LEAST ONE HOUR
 FIRE RATING.
 6) PRIOR TO OCCUPANCY, INSPECTIONS ARE
 TO BE PERFORMED BY FIRE RESCUE.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-10-04 Cont ID  
Sent By mcarsill Date 2000-10-04 Time 13:09 Rev Time 0.00
Received By mcarsill Date 2000-10-04 Time 13:09 Sent To  
Notes
2001-01-08 00:00:001) NO INTERIOR FINISH INFORMATION
 PROVIDED WITH PLANS. PLEASE PROVIDE
 INTERIOR FINISH INFORMATION FOR
 WALLS AND CEILINGS.
 2) NO SEATING DIAGRAM PROVIDED FOR
 DINING ROOM AND MEETING ROOM. PLEASE
 PROVIDE SEATING DIAGRAM FOR DINING ROOM
 AND MEETING ROOM.
 3) IS THERE ANY FIRE SEPARATION FOR
 THE STORAGE ROOMS.
 4) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 5) AN ADDITIONAL EMERGENCY LIGHT
 FIXTURE IS REQUIRED IN THE REAR OF
 UNIT 417.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-10-06 Cont ID  
Sent By ndenmark Date 2000-10-04 Time 17:17 Rev Time 0.25
Received By ndenmark Date 2000-10-04 Time 17:16 Sent To  
Notes
2001-01-08 00:00:00PROVIDE INFORMATION ON MECHANICAL WORK
 (BATHROOMS REQUIRE VENTILATION PER ASHRA
 62-89 AND 1997 SMC)
 MECHANICAL BY SEPARATE PERMIT

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-06 Cont ID  
Sent By tlarge Date 2000-10-06 Time 12:12 Rev Time 0.50
Received By tlarge Date 2000-10-06 Time 12:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-02 Cont ID  
Sent By tlarge Date 2000-10-02 Time 09:35 Rev Time 0.75
Received By tlarge Date 2000-10-02 Time 09:35 Sent To  
Notes
2001-01-08 00:00:00NO NOTES.SEE PREVIOUS COMMENTS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-08-11 Cont ID  
Sent By tlarge Date 2000-08-11 Time 17:57 Rev Time 0.75
Received By tlarge Date 2000-08-11 Time 17:57 Sent To  
Notes
2001-01-08 00:00:001)SIZE OF THE HANDICAP STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3
  
 2)NUMBER OF MIN.PLUMBING FIXTURES SHALL
 COMPLY W/SPC TABLE 407.
  
 3)DESIGN OF SANITARY SYSTEM SHALL
 COMPLY W/SPC SEC.914 FOR CIRCUIT AND
 LOOP SYSTEM IF THAT IS THE INTENT.
  
 4)PLANS MUST BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.101.4.7
  
 5)DOOR ON HANDICAP STALL IN MEN'S REST-
 ROOM CANNOT SWING INTO CLEAR FLOOR
 SPACE OF URINAL PER FACBC SEC.4.22.2.
  
 6)ALL PUBLIC AND COMMON TOILET ROOMS/
 RESTROOMS SHALL BE FULLY ACCESSIBLE.
 FACBC 4.1.3(11).