Plan Review Details - Permit 00060837
Plan Review Stops For Permit 00060837
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-11-27 Cont ID  
Sent By jwitmer Date 2001-11-27 Time 06:51 Rev Time 0.50
Received By jwitmer Date 2001-11-27 Time 06:51 Sent To  
Notes
2001-11-27 00:00:00REVISIONS DATED 10/08/01JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-11-01 Cont ID  
Sent By hpiskura Date 2000-11-01 Time 09:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-10-04 Cont ID  
Sent By drunnels Date 2000-10-04 Time 12:40 Rev Time 2.00
Received By drunnels Date 2000-10-04 Time 12:40 Sent To  
Notes
2001-01-08 00:00:001.FLORIDA ENERGY CALCULATIONS MUST BE
 SIGNED BY OWNER/AGENT
 2.SUBMIT PRODUCT APPROVAL FOR STOREFRONT
 AND DOORS / METRO DADE COUNTY OR SBCCI

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By hpiskura Date 2000-07-24 Time 11:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2002-01-18 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2001-12-10 Cont ID  
Sent By dpalmer Date 2001-12-10 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2001-12-10 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2001-11-20 Cont ID  
Sent By dpalmer Date 2001-11-20 Time 17:07 Rev Time 0.00
Received By dpalmer Date 2001-11-20 Time 17:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2001-10-10 Cont ID  
Sent By dpalmer Date 2001-10-10 Time 19:14 Rev Time 0.00
Received By dpalmer Date 2001-10-10 Time 19:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-09-10 Cont ID  
Sent By dpalmer Date 2001-09-10 Time 10:26 Rev Time 0.00
Received By dpalmer Date 2001-09-10 Time 10:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-11-13 Cont ID  
Sent By dpalmer Date 2000-11-13 Time 11:27 Rev Time 0.00
Received By dpalmer Date 2000-11-13 Time 11:27 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-14 Cont ID  
Sent By dpalmer Date 2000-09-14 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2000-09-14 Time 11:28 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER/PANEL SCHEDULE
 ON E3.1,E2.4. EML1 SHOWN BEING 225A WITH
 250 OCP.?? ALSO CONTINUOUS LOADS TO BE
 SHOWN,,, AT 125%. (LIGHTING) ETC.
 PLEASE SEE THE LOAD SHOWN FOR EML1, THIS
 DOES NOT CORRELATE WITH LOAD SHOWN ON
 EML.?? IF MATCHED THEN LOAD WOULD GO
 OVER THE RATING OF 300 AMPS ON PANEL.
 PLEASE SHOW THE LOAD CALCULATIONS.
 PLEASE SHOW WHERE LOADS ARE COMING FROM.
  
  
 2)NOTE: SEE FOUNTAIN PUMP CONTROLLER ON
 E2.0. PLEASE SUBMIT CLARIFICATION ON
 PLANS WHERE FOUNTAIN LOCATION IS.
 PANEL SCHEDULE SHOWS AS BEING FUTURE??
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER/JAKE LEAHY
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-07-11 Cont ID  
Sent By jleahy Date 2000-07-11 Time 15:54 Rev Time 2.30
Received By jleahy Date 2000-07-11 Time 15:52 Sent To  
Notes
2001-01-08 00:00:001-NO FOUNTAINS SHOWN
 2-Q FIXTURES NOT SHOWN ON FIXTURE SCHEDU
 3-PANEL SCHEDULES DO NOT REFLECT CHANGES
 4-ALL LIGHTING LOADS SHOWN AT 100% NOT
 125%
 5-PLAQUES NEEDED ON SERVICE DISCONNECTS
 PER 230-2E AND 230-70B

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2001-12-11 Cont ID  
Sent By mcarsill Date 2001-12-11 Time 13:43 Rev Time 0.00
Received By mcarsill Date 2001-12-11 Time 13:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2001-11-28 Cont ID  
Sent By mcarsill Date 2001-11-28 Time 11:23 Rev Time 0.00
Received By mcarsill Date 2001-11-28 Time 11:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-29 Cont ID  
Sent By mcarsill Date 2000-09-29 Time 09:04 Rev Time 0.00
Received By mcarsill Date 2000-09-29 Time 09:04 Sent To  
Notes
2001-01-08 00:00:001) WRONG CODE REFERENCE IN CODE ANALYSIS
 BOX. SHOULD READ 1985 LIFE SAFETY CODE
 INSTEAD ON 1997 LIFE SAFETY CODE.
 2) THE ATRIUM SMOKE CONTROL SYSTEM IS
 TO BE ACTIVATED BY SMOKE DETECTORS,
 THE SPRINKLER SYSTEM, THE FIRE ALARM
 SYSTEM, AND MANUAL CONTROLS FOR THE
 FIRE DEPARTMENT PER NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION, SECTION
 6-2.2.3.5, SECTION (G)
 3) THE ENTIRE ATRIUM IS TO MEET THE
 REQUIREMENTS OF NFPA 101, THE LIFE
 SAFETY CODE, 1985 EDITION, SECTION
 6-2.2.3.5, SECTION A-H.
 4) PLEASE PROVIDE TESTING INFORMATION
 FOR THE ATRIUM SMOKE CONTROL SYSTEM.
 5) PLEASE PROVIDE A DRAWING ON WHAT THE
 SMOKE CONTROL PANEL WILL LOOK LIKE.
 6) PLEASE PROVIDE FIRE ALARM SHOP
 DRAWINGS FOR THE INSTALLATION OF NEW
 FIRE ALARM EQUIPMENT. CUT SHEETS AND
 WIRING DIAGRAM ARE TO BE SUBMITTED
 UNDER SEPARATE PERMIT.
 APPROVED PROVISO:

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By rturnque Date 2000-07-05 Time 15:23 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2001-12-11 Cont ID  
Sent By pkrauss Date 2001-12-11 Time 14:18 Rev Time 0.40
Received By pkrauss Date 2001-12-11 Time 14:18 Sent To  
Notes
2001-12-11 00:00:00MECH & ELEC REV. DUCT SMOKE DETECTORS IN
 THE SUPPLY DUCT.SUBMITTAL FOR DUCT
 SMOKE DETECTORS ONLY...

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2001-12-01 Cont ID  
Sent By pkrauss Date 2001-12-01 Time 11:53 Rev Time 0.45
Received By pkrauss Date 2001-12-01 Time 11:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2001-10-15 Cont ID  
Sent By pkrauss Date 2001-10-15 Time 12:10 Rev Time 0.30
Received By pkrauss Date 2001-10-15 Time 12:03 Sent To  
Notes
2001-10-15 00:00:00PROVISO ON PLAN - FAN SHUTDOWN BY DUCT
 SMOKE DETECTOR WITH NOTIFICATION.
 MECHANICAL PERMIT 01021160.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2001-10-04 Cont ID  
Sent By pkrauss Date 2001-10-04 Time 13:33 Rev Time 0.45
Received By pkrauss Date 2001-10-04 Time 13:32 Sent To  
Notes
2001-10-04 00:00:00*****************PROVISO****************
  
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION TO ALARM/STROBE OR TO A
 SUPERVISORY SIGNAL TO BE INDICATED AT A
 CONSTANTLY ATTENDED LOCATION FOR
 SYSTEMS WITH GREATER THAN 2,000 CFM OR
 SYSTEMS SERVING AN AREA USED FOR EGRESS.
  
 PLEASE INDICATE ON PLANS UNITS REQUIRED
 FOR FAN SHUT-DOWN OR UNITS UTILIZED IN
 SMOKE EVAQ.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096 EXT.
 8388

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2001-09-05 Cont ID  
Sent By pkrauss Date 2001-09-05 Time 12:15 Rev Time 0.30
Received By pkrauss Date 2001-09-05 Time 11:45 Sent To  
Notes
2001-09-05 00:00:00REVISION MECH PLANS M2.1 AND M2.2.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2001-03-07 Cont ID  
Sent By pkrauss Date 2001-03-07 Time 11:28 Rev Time 1.00
Received By pkrauss Date 2001-03-07 Time 11:28 Sent To  
Notes
2001-03-07 00:00:00A/C PERMIT 01021160 APPROVED AS PER
 APPROVAL WITH BUILDING SUBMITTAL, PLANS
 ARE THE SAME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-21 Cont ID  
Sent By ndenmark Date 2000-09-21 Time 13:32 Rev Time 2.00
Received By ndenmark Date 2000-09-21 Time 13:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-07-24 Cont ID  
Sent By ndenmark Date 2000-07-24 Time 15:18 Rev Time 2.00
Received By ndenmark Date 2000-07-24 Time 15:18 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
  
 1. PROVIDE INFORMATION SHOWING COMPLIANC
 WITH 1997 SBC 414.4 RELATIVE TO HEIGHT
 AND CU. FT. OF ATRIUM. EXAMPLE: HOW MUCH
 EXHAUST AIR. LOCATION OF MECHANICAL
 SUPPLY AIR @ 75% OF EXHAUST. PROVIDE
 SEQUENCE OF OPERATION FOR SYSTEM.
 2. ALL SMOKE CONTROL EQUIPMENT SHALL BE
 CONNECTED TO STANDBY POWER SYSTEM IN
 ACCORDANCE WITH 412.7
 3.PROVIDE INFORMATION ON OUTSIDE AIR PER
 ASHRAE 62-89
 NOTE: COMPONENT PARTS OF RETURN AIR PLEN
 UM AREAS ARE TO BE CONSTRUCTED ENTIRELY
 OF NON- COMBUSTIBLE MATERIALS. PER 1997
 SMC 609

Review Stop P PLUMBING
Rev No 5 Status P Date 2002-01-13 Cont ID  
Sent By pschmitz Date 2002-01-13 Time 09:10 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-01-13 00:00:00REVISION, AREA DRAINS,PES.

Review Stop P PLUMBING
Rev No 4 Status P Date 2001-11-26 Cont ID  
Sent By kstevens Date 2001-11-26 Time 15:42 Rev Time 0.50
Received By kstevens Date 2001-11-26 Time 15:42 Sent To  
Notes
2001-11-26 00:00:00REVISION/PASSED
  
 CANOPY RAIN WATER REVISION

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-22 Cont ID  
Sent By pschmitz Date 2000-10-22 Time 09:31 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-10-22 Cont ID  
Sent By tlarge Date 2000-09-03 Time 08:44 Rev Time 1.00
Received By pschmitz Date 2000-09-03 Time 07:50 Sent To  
Notes
2001-01-08 00:00:00CALCULATIONS FOR SECONDARY(EMERGENCY)
 DRAINAGE SHALL BE BASED ON ON THE FLOW
 RATE IN FIGURE 1109.3 OF THE SPC.
 THE CALCULATIONS ARE UNCLEAR TO HOW YOU
 ARRIVED AT THE REQD.SIZES.SPC 1109.3, &
 APPENDIX "A"
  
 2)SHT.P2.4-8" LINE IS DRAINING INTO 6"
 LINE.STORM DRAIN ISOMETRIC SHOWS THE
 SAME.COMPLY W/SPC SEC.709.1.
  
 3)SLOPE OF PIPE SHALL BE NOTED ON THE
 PLANS.COUNTYWIDE AMENDMENTS TO SPC SEC.
  
 4)SUBMIT PIPING DETAILS FOR RELOCATED
 PLANTER DRAINS.NOTES ON P2.1 DON'T
 MENTION PLANTER DRAINS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
 CALL 561-659-8096 EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-10-22 Cont ID  
Sent By tlarge Date 2000-06-22 Time 15:07 Rev Time 2.00
Received By pschmitz Date 2000-06-22 Time 15:07 Sent To  
Notes
2001-01-08 00:00:00SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC
 FOR REVIEW.SHOW SQ.FOOT AREA DRAINED
 BY EACH DRAIN.COMPLY W/SPC SECS.AND
 TABLES 1108.1,1108.2.
  
 PROVIDE CALCULATIONS FOR SECONDARY
 (EMERGENCY)DRAINAGE.SUBMIT DETAILS OF
 SCUPPERS(LXW),OVERFLOW DRAINS AND SIZES,
 AND INCLUDE 1/2 THE AREA OF ANY VERTICAL
 WALLS IN YOUR CALCULATIONS PER SPC SEC.
 1108.3,1109.1,1109.2,1109.3,AND APPENDIX
 "A".
  
 INDICATE SLOPE OF PIPE ON THE PLANS.
  
 SHT.P-2.4-8"LINE IS DRAINING INTO A 6"
 LINE.COMPLY W/SPC SEC.709.1.
  
 SUBMIT PIPING DETAILS FOR RELOCATED
 PLANTER DRAINS.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 SUBMIT PLANS FOR FOUNTAIN IF COVERED
 UNDER THIS PERMIT.COUNTYWIDE AMENDMENTS
 TO SPC SEC.104.2.1.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-11-28 Cont ID  
Sent By gjoyce Date 2000-07-17 Time 16:11 Rev Time 0.25
Received By lsmith Date   Time   Sent To  
Notes
2001-01-08 00:00:00NEEDS MINOR AMEDMENT