Plan Review Details - Permit 00060828
Plan Review Stops For Permit 00060828
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-08-08 Cont ID  
Sent By drunnels Date 2000-08-08 Time 08:45 Rev Time 1.00
Received By drunnels Date 2000-08-08 Time 08:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-07-14 Cont ID  
Sent By bstaples Date 2000-07-14 Time 10:12 Rev Time 0.00
Received By drunnels Date 2000-07-14 Time 08:46 Sent To  
Notes
2001-01-08 00:00:001. LETTER FROM SPECIAL INSPECTOR
 RELEASING THE SPACE. CALLED J. COLLIER
 7/14/00.
 2. FIRE SPRINKLER LAY OUT AND PERMIT
 MUST BE APPLIED FOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-06-28 Cont ID  
Sent By bstaples Date 2000-06-28 Time 15:52 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001.FLORIDA ENERGY SHEETS NOT SIGNED BY
 OWNER SEE #3 PRIOR REVIEW.
 2. FIRE SPRINLER PERMIT REQUIRED PRIOR
 ISSUANCE OF BUILDING PERMIT. SEE #4
 PRIOR REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-15 Cont ID  
Sent By bstaples Date 2000-06-15 Time 10:05 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SHEET AA GLAZING IMPACT CODE
 REFERENCE REVISE TO SSTD 12-97.
 2. PROVIDE PRODUCT APPROVAL INFORMATION
 FOR ALL EXTERIOR GLAZING.
 3. PROVIDE SIGNED AND SEALED FLORIDA
 ENERGY SHEETS 1997 EDITION.
 4. FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSUANCE OF THE BUILDING PERMIT.
 4. EXTERIOR SIGNS REQUIRE SEPATATE
 PERMITS.
 5. SHEET A-1 PARTATION TYPE #1 REVISE TO
 COMPLETE BOTH SIDES OF FIRE SEPARATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-06-29 Cont ID  
Sent By dpalmer Date 2000-06-29 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2000-06-29 Time 19:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-19 Cont ID  
Sent By dpalmer Date 2000-06-19 Time 19:16 Rev Time 0.00
Received By dpalmer Date 2000-06-19 Time 19:16 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE PROVIDE AIC RATING OF
 200AMP CB DISCONNECT INLINE FROM THE
 TRANSFORMER TO PANEL-A. 215-5
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 `EVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
 DEWEY PALMER ELECTRICAL PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-07-05 Cont ID  
Sent By mcarsill Date 2000-07-05 Time 10:13 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-19 Cont ID  
Sent By bstaples Date 2000-06-19 Time 13:35 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO M. CARSILLO SEE NOTES ATTACHED
 TO PLANS. WRS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-06-30 Cont ID  
Sent By cthirben Date 2000-06-30 Time 10:30 Rev Time 1.00
Received By cthirben Date 2000-06-30 Time 10:30 Sent To  
Notes
2001-01-08 00:00:00NOTES : MET ALL REQUIREMENTS REQUESTED
 BY NCD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-19 Cont ID  
Sent By ndenmark Date 2000-06-19 Time 07:31 Rev Time 0.50
Received By ndenmark Date 2000-06-19 Time 07:31 Sent To  
Notes
2001-01-08 00:00:00*************DENIED********************
  
 1. 1997 SMC 610 REQUIRES FIRE DAMPERS AT
 ALL PENETRATIONS OF RATED WALLS
 2. SMC 610.6 REQUIRES THAT THE SPECIFIC
 LOCATION AND INSTALLATION DETAILS OF EA.
 FIRE DAMPER SHALL BE SHOWN AND PROPERLY
 IDENTIFIED ON THE BUILDING PLANS BY THE
 DESIGNER
 3. PROVIDE ENERGY EFFIECIENCY RATING OF
 AHU.
 4. OUTSIDE AIR PER ASHRAE 62-89 REQUIRED
 5. PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-07-15 Cont ID  
Sent By pschmitz Date 2000-07-15 Time 11:23 Rev Time 0.00
Received By pschmitz Date 2000-07-15 Time 11:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-06-29 Cont ID  
Sent By tlarge Date 2000-06-29 Time 16:26 Rev Time 0.65
Received By pschmitz Date 2000-06-29 Time 16:26 Sent To  
Notes
2001-01-08 00:00:00OCCUPANT LOAD SHALL BE DETERMINED PER
 TABLE 407 OF SPC.
  
 SHT.P-1 NOTES "SEE ARCH.DRWGS.FOR ACCESS
 DETAILS FOR EWH".NO DETAILS ARE SHOWN.
 SUBMIT FOR REVIEW.COMPLY W/SPC SEC.
 501.7.
  
 DRESSING ROOM SHALL COMPLY W/FACBC SEC.
 4.35.1-4.35.5.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 NOTE:OCCUPANT LOAD AS LISTED REQUIRES
 ADDITIONAL PLUMBING FIXTURES PER TABLE
 407 OF SPC.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-18 Cont ID  
Sent By tlarge Date 2000-06-18 Time 05:41 Rev Time 1.75
Received By pschmitz Date 2000-06-18 Time 05:15 Sent To  
Notes
2001-01-08 00:00:00SHT.AA-INCORPORATE THE STANDARD PLUMBING
 CODE,1994 EDITION INTO CODE COMPLIANCE
 DATA LEGEND.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.2,101.4.6.,F.S.553.06.
 B)THE ADOPTED STANDARD GAS CODE IS THE
 1997 EDITION.
 C)THE ADOPTED ACCESSIBILITY CODE IS THE
 FLA.ACCESSIBILITY CODE FOR BUILDING
 CONSTRUCTION-OCTOBER 1997 EDITION.
  
 SUBMIT SQUARE FOOTAGE OF HABITABLE FLOOR
 SPACE FOR DETERMINATION OF MINIMUM
 SANITARY FACILITIES.SEE SPC SEC.407.1.3.
 FOR ALLOWED DEDUCTIBLE AREAS.
  
 A MINIMUM OF ONE DRINKING FOUNTAIN IS
 REQUIRED PER SPC TABLE 407.FOUNTAIN
 SHALL COMPLY W/FACBC SEC.4.1.3.(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 DRESSING ROOM SHALL COMPLY W/FACBC SEC.
 4.35.4.(BENCH SHALL BE FIXED ALONG LONG
 WALL).
  
 SHT.A-8A-GRAB BARS ALONGSIDE WATER
 CLOSET SHALL BE A MIN.OF 42".DETAILS C &
 G NOTE 36".
  
 FLUSH CONTROLS FOR WATER CLOSETS SHALL
 BE LOCATED ON THE WIDE SIDE OF THE
 WATER CLOSET PER FACBC SEC.4.16.5.
  
 SHT.A-8A SHOWS HEIGHT OF ACCESSIBLE
 WATER CLOSETS AS 15".COMPLY W/FACBC SEC.
 4.16.3.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 OR RELOCATE EWH TO FLOOR.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS SEC.911.1.1.
 OR COMPLY W/SPC SEC.914.1 FOR CIRCUIT
 AND LOOP VEN SYSTEM IF THAT IS THE
 INTENT.