Plan Review Details - Permit 00060740
Plan Review Stops For Permit 00060740
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2000-07-21 Cont ID  
Sent By fknapp Date 2000-07-21 Time 12:19 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
  
  
 ****************PROVISO*****************
  
  
 2ND PLAN REVIEW
  
 1)PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR
 WINDLOADS AND MISSLE IMPACT FOR ALL
 GLAZING TO BE UNDER SEPARATE PERMIT.
  
 2)FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSUANCE OF BUILDING PERMIT.
  
 3)EXTERIOR SIGNS REQUIRED SEPARATE
 PERMITS.
  
 4) LETTER FOR CITYPLACE SPECIAL
 INSPECTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-14 Cont ID  
Sent By bstaples Date 2000-06-14 Time 14:37 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS: SUBMIT
 ORIGIONAL SIGNED AND SEALED DOCUMENT
 1997 FL. ENERGY CODE.
 2. FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSUANCE OF BUILDING PERMIT.
 3. SHEET A-0 BOTH SIDES OF FIRE
 SEPARATION MUST BE FINISHED.
 4. SHEET A-1 STORAGE ABOVE RESTROOMS
 PROVIDE STAIR FOR ACCESS SEE SECTION
 1005.7 MEZZANINES AND GUSARD RAILS SEE
 SECTION 1015 1997 SBC.
 5. SHEET A-4 NOTE 16: PROVIDE PRODUCT
 APPROVAL INFORMATION FOR LARGE MISSLE
 IMPACT PROTECTION OF EXTERIOR GLAZED
 OPENINGS, MEET 1997 SBC, SSTD 12-97 OR
 METRO DADE COUNTY.
 5. EXTERIOR SIGNS REQUIRE SEPERATE
 PERMITS.
 6. ALL WOOD PRODUCTS SHALL BE PRESSURE
 TREATED FIRE RETARDANT LUMBER AND
 PROTECTED BY ATHERMAL BARRIER SEE
 1997 SBC, SECTION 707.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-26 Cont ID  
Sent By dpalmer Date 2000-07-26 Time 07:48 Rev Time 0.00
Received By dpalmer Date 2000-07-26 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-19 Cont ID  
Sent By dpalmer Date 2000-06-19 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2000-06-19 Time 17:18 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE CHECK THE AVAILABLE FAULT
 FROM TRANSFORMER TO PANEL 'C'.ALSO YOU
 ARE SHOWING AIC RATING AT 24,000?? THIS
 IS NOT A STANDARD SIZE, PLEASE CORRECT.
  
 2)NOTE: PLEASE SHOW THE GROUNDING BOND
 TO COLD WATER PIPE.
  
  
 3)NOTE: PLEASE NOTE OUT SPACING TO MEET
 LOCAL CODE EVERY 20`FOR STORAGE AND
 OFFICE RETAIL EVERY 12` OF UNENCUMERED
 WALL SPACE. 210-50
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL DEWEY V PALMER 561-659-8096
 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-28 Cont ID  
Sent By bstaples Date 2000-06-28 Time 16:48 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00SEE PLAN REVIEW NOTES M. CARSILLO 6/14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-31 Cont ID  
Sent By cthirben Date 2000-07-28 Time 07:27 Rev Time 1.00
Received By bstaples Date 2000-07-28 Time 07:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-19 Cont ID  
Sent By ndenmark Date 2000-06-19 Time 07:16 Rev Time 1.00
Received By ndenmark Date 2000-06-19 Time 07:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-07-28 Cont ID  
Sent By tlarge Date 2000-07-28 Time 17:43 Rev Time 0.65
Received By tlarge Date 2000-07-28 Time 17:28 Sent To  
Notes
2001-01-08 00:00:00PROVISO:HANDICAP DRINKING FOUNTAIN SHALL
 COMPLY W/FACBC SEC.4.1.3.(10)(A).
  
 ACCESSIBLE TOILET ROOMS SHALL BE READILY
 AVAILABLE TO EMPLOYEES AND PATRONS
 DURING NORMAL BUSINESS HOURS AND BE ON
 AN ACCESSIBLE ROUTE PER FACBC SEC.4.1.3
 (11),SPC 407.2.2.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-21 Cont ID  
Sent By pschmitz Date 2000-07-21 Time 15:26 Rev Time 2.00
Received By pschmitz Date 2000-07-21 Time 16:45 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
  
  
 (1) SHT A-1 ACCESS TO H/C REST RM THRU
 STOCK RM102 IS NOT ACCESSIBLE TO THE
 PUBLIC,AS REQUIRED IN FACBC 4.1.3.(11)
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-19 Cont ID  
Sent By tlarge Date 2000-06-19 Time 19:41 Rev Time 0.75
Received By pschmitz Date 2000-06-19 Time 19:41 Sent To  
Notes
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.PER TABLE
 407 OF THE SPC.FOUNTAIN SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 SHOW DRINKING FOUNTAIN ON WATER AND
 SANITARY RISER.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.SHOW LENGTH AND WIDTH OF
 TOILET ROOMS.COMPLY W/FACBC SEC.4.16.2.
  
 WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.
  
 PIPE INSULATION SHALL COMPLY W/FEC
 TABLE 4-11.SEE SHT.MP-1.
  
 SUBMIT MANUF.SHEETS ON EWH.WATER HEATER
 SHALL BE LISTED PER SPC SEC.503.3.
  
 SIZE THE SOIL AND WASTE STACKS ON THE
 SANITARY RISER.