| Plan Review Stops For Permit 00060672 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2000-11-22 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-11-22 |
Time |
10:00 |
Rev Time |
2.00 |
| Received By |
drunnels |
Date |
2000-11-22 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-14 |
Time |
14:56 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO | | | | | | 1. PROVIDE PRODUCT APPROVAL INFORMATION | | | FOR WINDOWS AND DOORS TO MEET 1997 SBC | | | FOR WIND LOADS. PROVIDE PRODUCT APPROVAL | | | FOR SHUTTERS TO MEET IMPACT RESISTANT | | | CODES USE SSTD12-97 OR METRO DADE COUNTY | | | | | | 2. PROVIDE PRODUCT APPROVAL FOR WINDOW | | | NEXT TO EXIT STAIR 1 1/2 HOUR RATING | | | REQUIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-11 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-07-11 |
Time |
14:14 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. ITEM #1 PRIOR REVIEW NOT SUBMITTED | | | LETTER FROM SPECIAL INSPECTOR. | | | 2. ITEM #3 PRIOR REVIEW NOT SUBMITTED | | | PRODUCT APPROVAL INFORMATION FOR | | | EXTERIOR GLAZING. | | | 3. ITEM #5 PRIOR REVIEW OT ADDRESSED | | | FIRE RATING OF OPENINGS REQUIRED | | | SHEET A5.5 SECTION1 NORTH ELEVATION | | | SHEET A5.6 SECTION 1 EAST ELEVATION | | | ALL OPEANINGE WITHIN 10 FEET SHALL BE | | | PROTECTED. SEE 1997 SBC CH. 6, 7 AND 10. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-22 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-22 |
Time |
13:01 |
Rev Time |
2.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. LETTER FROM SPECIAL INSPECTOR | | | RELEASINF SPACE. | | | 2. FIRE SPRINKLER PERMIT TO BE ISSUED | | | PRIOR TO ISSUANCE OF BUILDING PERMIT. | | | 3. EXTERIOR GLAZING PROVIDE PRODUCT | | | APPROVAL INFORMATION, METRO DADE COUNTY | | | OR STANDARD BUILDING CODE 1997, SSTD1297 | | | 4. SHEET A-5.1, SECTION 5 ALL PLYWOOD | | | AND WOOD FRAMING TO BE PRESSURE TREATED | | | FIR RETARDANT LUMBER. SEE 1997 SBC | | | CHAPTERS 6 AND 7, FOR TYPE 2 | | | CONSTRUCTION. | | | 5. SHEET A5.5 OPEANINGSUNDER STAIRS | | | SHALL BE FIRE RATED IF WITHIN 10 FEET | | | SEE 1997 SBC CHAPTERS 6, 7 AND 10. | | | | | | | | | 7. SIGNS REQUIRE SEPERATE PERMITS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2001-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-08 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-08 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2000-11-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-11-14 |
Time |
21:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-11-14 |
Time |
21:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***** NOTE**** | | | COVER SHEET STILL SHOWS 96 NEC?? | | | HANDWROTE "99" |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-09 |
Time |
09:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-09 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO **************** | | | | | | 1)NOTE: LOAD CALCULATIONS NEED TO BE | | | COMPLETED. SHOW ALL CONTINUOUS LOADS | | | FIGURED AT 125% (LIGHTING,LARGEST MOTOR | | | ETC). PLEASE SHOW ALL THE FINAL LOADS | | | IN AMPS FOR EACH PANEL AND MDP.. | | | | | | 2)NOTE: PLEASE CHANGE COVER SHEET TO | | | REFLECT THE "99" NEC. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW BEFORE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. IF | | | THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-25 |
Time |
06:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-25 |
Time |
06:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** PROVISO *************** | | | | | | 1)NOTE: SHEET CS-1 SHOWS THE CHANGES TO | | | E-1 - E-4. THIS IS OK BUT STILL REF. | | | THE 96 NEC. PLEASE HAVE THIS CHANGE | | | MADE BEFORE ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. | | | | | | IF THERE AREANY QUESTIONS PLEASE CALL. | | | 561 659-8096 EXT 8372 | | | DEWEY PALMER | | | PLAN REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-06 |
Time |
20:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-06 |
Time |
20:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE SEE THAT COMPLETE SET FOR | | | ELECTRICAL IS NOT SUBMITTED. SHEET CS-1 | | | SHOWS E-1 - E-8? | | | SHEET CS-1 AND E-4 ALSO REFERENCES 1996 | | | NEC AND NO LOCAL AWMENDMENTS. | | | WE ARE UNDER 1999 NEC AND HAVE LOCAL | | | AMENDMENTS. | | | | | | PLEASE CORRECT AND CLARIFY THE ABOVE | | | INFORMATION. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-19 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-19 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SUBMIT AICRATINGS FOR | | | ALL MAINS/PANELS. ALL EQUIPMENT MUST BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110-9/215-5 | | | | | | 2)NOTE: PLEASE SUBMIT AND SHOW THE | | | ENTIRE LOAD CALCULATION FOR EAACH PANEL | | | AND THE MDP/MAIN. PLEASE SHOW ALL LOADS | | | THAT ARE CONTINUOUS AT 125%(LIGHTING)ETC | | | AND 25% FOR LARGEST MOTOR LOAD. | | | | | | 3)NOTE:PLEASE SHOW THE GROUNDING SYSTEM. | | | COLD WATER/EXISTING BLDG. GROUND ATTACH. | | | 215-5 | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL DEWEY PALMER 561-659-8096 | | | EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-11-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-11-21 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-11-21 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-14 |
Time |
14:54 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | M. CARSILLO REVIEWED 7/13/00 SEE NOTES | | | ATTACHED TO PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-06-19 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-19 |
Time |
14:26 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOT APPROVED SEE NOTES ATTACHED TO PLANS | | | M. CARSILLO 6/14/00. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-11-16 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-11-16 |
Time |
12:16 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-11-16 |
Time |
12:16 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTE: SEPARATE PERMIT REQUIRED FOR HOOD | | | AND SUPPRESSION SYSTEM AND WALK IN COOL- | | | ERS AND FREEZERS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-11 |
Time |
08:48 |
Rev Time |
0.50 |
| Received By |
ndenmark |
Date |
2000-08-11 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIOR COMMENTS CORRECTED BY REVISION | | | 8/11/00 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-07-18 |
Time |
07:37 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-07-18 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *********DENIED************************* | | | 1) OUTSIDE AIR CALCULATIONS DO NOT | | | COMPLY WITH ASHRAE 62-89. EX: | | | SMOKING LOUNGE CALLS FOR 60 CFM PER | | | PERSON THERE IS NO EQUIVELANT PER SQ FT | | | VALUE TO USE. SMOKING DINING @ 20 CFM | | | PER PERSON WOULD BE 1160 @ 58 PEOPLE | | | AND LOUNGE @ 59 PEOPLE = 3540 CFM TOTAL | | | OUTSIDE AIR FOR AC 3 = 4700 CFM. VALUE | | | SUPPIED = 2310 CFM NOT PER REQUIREMENT | | | PROVIDE OUTSIDE AIR PER ASHRAE 62-89 | | | 2) GREASE EXHAUST DUCT REQUIRES 1" PER | | | 12" SLOPE TOWARD HOOD MIN. PER 1997 SMC | | | 505.4 PROVIDE ELEVATION SHOWING SPACE | | | AVAIABILITY FOR LENGTH OF RUN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-24 |
Time |
10:55 |
Rev Time |
1.00 |
| Received By |
ndenmark |
Date |
2000-06-24 |
Time |
10:55 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************DENIED******************** | | | PLEASE PROVIDE ADDITIONAL INFORMATION | | | FOR REVIEW: | | | 1. PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2PROVIDE ROOF PLAN SHOWING TERMINATION | | | OF GREASE DUCT, OUTSIDE AIR INTAKE, FLUE | | | AND RTU'S | | | 3. PROVIDE DETAIL SHOWING VERTICAL RUN | | | OF FLUE, GREASE DUCT, ETC FOR REVIEW | | | 4. PROVIDE ENERGY EFFICIENCY RATING PER | | | ENERGY EFFICIENCY CODE FOR BUILDING | | | CONSTRUCTION (STATE OF FLORIDA) 1997 ED | | | NOTE: SEPARATE PERMITS REQUIRED FOR HOOD | | | COOLERS, FIRE SUPPRESSION. SUBMIT PLANS | | | AT TIME OF MECHANICAL PERMIT APPLICATION | | | FOR ABOVE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2000-11-22 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-22 |
Time |
10:54 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2000-11-22 |
Time |
10:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
F |
Date |
2000-11-17 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-11-17 |
Time |
14:45 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2000-11-17 |
Time |
14:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SEAL ALL PAGES. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
P |
Date |
2000-08-11 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-11 |
Time |
14:49 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-11 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-10 |
Time |
19:07 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-08-10 |
Time |
19:07 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)A MIN.OF 4 WATER CLOSETS ARE REQD.IN | | | THE WOMEN'S RESTROOM PER THE OCCUPANT | | | LOAD AND SPC TABLE 407.COMPLY W/FLA. | | | STATUTE 553.141(3)POTTY PARITY. | | | | | | 2)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC.610.4.1,610.4.2. | | | | | | 3)SHT.P-2,P-6-GAS MAIN FROM THE METER | | | SHALL BE SIZED 3" PER SGC TABLE 305.4(A) | | | YOUR NOTE STATES 3" BUT THE DRAWING IS | | | STILL WRONG! | | | | | | 4)ALL FLOOR DRAINS IN TOILET ROOMS SHALL | | | BE 3"PER SPC SEC.409.4.1.1. | | | | | | 5)SHT.P-5-VACUUM RELIEF VALVE IS NOT | | | LOCATED CORRECTLY.VALVE SHALL BE IN- | | | STALLED ON THE WATER SUPPLY OF THE COLD | | | WATER,NOT ON THE HOT WATER SIDE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-27 |
Time |
19:27 |
Rev Time |
2.75 |
| Received By |
tlarge |
Date |
2000-07-27 |
Time |
19:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SHT.P-3-ALL FLOOR DRAINS LOCATED IN | | | TOILET ROOMS SHALL BE 3" PER SPC SEC. | | | 409.4.1.1. | | | | | | 2)SHT.P-3-(BAR AREA)-DESIGN OF PLUMBING | | | SHALL COMPLY W/SPC SEC.921 FOR WASTE | | | AND VENT SYSTEM IF THAT IS THE INTENT. | | | | | | 3)NOTE THE OCCUPANT LOAD ON THE PLANS | | | ACCORDING TO THE TOTAL NUMBER OF SEATS | | | AND SEATING SPACE AT BOOTHS AND BARS. | | | COMPLY W/TABLE 407 OF SPC.SEE SBC TABLE | | | 1003.1 FOOTNOTE #1 FOR BAR AND BOOTH | | | REQS. | | | | | | 4)MINIMUM NUMBER OF REQD.SANITARY | | | FACILITIES SHALL BE BASED ON ABOVE REQS. | | | | | | 5)WATER SUPPLY CONTROL SHALL COMPLY W/ | | | SPC SEC.610.4.1.,610.4.2. | | | | | | 6)SHT.P-6-GAS MAIN FROM METER SHALL BE | | | SIZED A MIN.OF 3"PER SGC TABLE 305.4(A). | | | | | | 7)SHT.A1.1-A MIN.OF 4 WATER CLOSETS ARE | | | REQD.IN THE WOMEN'S RESTROOM PER SPC | | | TABLE 407.ADDITIONAL PLUMBING FIXTURES | | | MAY BE REQD.IN BOTH RESTROOMS PENDING | | | CORRECT OCCUPANT LOAD COUNT. | | | | | | 8)NUMBER OF SANITARY FACILITIES SHALL | | | COMPLY W/FLA.STATUTE 553.141.(POTTY | | | PARITY). |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-18 |
Time |
15:04 |
Rev Time |
3.00 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW OF REVISIONS | | | DATED 06-30-00 GEO SLADEK | | | (1) ITEMS #6,#7 SHT P-6 NOT INCLUDED. | | | (2) ITEM #11 CO INFO NOT PROVIDED. | | | (3) ITEM #13 VACUM RELIEF, WATTS 36-A. | | | (4) ITEM #15 MIN FACILITIES SHOW COUNT | | | FOR EMPLOYEES & PUBLIC. | | | END OF COMMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-07-11 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-11 |
Time |
12:22 |
Rev Time |
7.50 |
| Received By |
pschmitz |
Date |
2000-07-11 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ADDITIONAL PLUMBING FIXTURES ARE REQD.IN | | | THE MEN'S AND WOMENS RESTROOMS PER TABLE | | | 407 OF THE SPC BASED ON NUMBER OF SEATS. | | | BATHROOMS SHALL ALSO COMPLY W/FLA.STAT. | | | 555.141.(POTTY PARITY). | | | | | | NUMBER AND LOCATION OF PLUMBING FIXTURES | | | IN THE MEN'S ROOM ARE NOT TYPICAL | | | THROUGHOUT THE PLANS.(TWO URINALS ARE | | | SHOWN ON SOME SHEETS AND ONE IS SHOWN ON | | | OTHERS.)COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | PLANS STILL SHOW THE VENTS FOR THE FLOOR | | | DRAINS OFFSETTING HORIZONTALLY BELOW | | | THE SLAB.SHOW COMPLIANCE W/SPC SEC. | | | 906.2.1.(NOTES ARE NOT ACCEPTABLE.) | | | | | | SUBMIT COMPLETE GAS RISER DIAGRAM FOR | | | REVIEW.SHOW DISTANCE TO MOST REMOTE | | | OUTLET,PIPE SIZES,,PIPE MATERIAL,BTU | | | LOAD OF EACH APPLIANCE,CALCULATIONS FOR | | | COMBUSTION AIR,DETAILS ON VENT AND VENT- | | | MATERIALS,ETC... | | | | | | GAS CONTROLS SHALL COMPLY W/NFPA 5.5.4. | | | SHOW COMPLIANCE ON THE GAS RISER. | | | | | | INSTALLATION OF CLEANOUTS IN THE DRAIN- | | | AGE SYSTEM SHALL COMPLY W/SPC SEC.710.2. | | | | | | VACUUM RELIEF VALVE IS REQUIRED ON THE | | | COLD WATER SUPPLY TO THE WATER HEATERS | | | PER SPC SEC.507.1.2.(THE PLANS SHOW A | | | CHECK VALVE,NOT A VACUUM RELIEF VALVE.) | | | | | | THE U.L ASSEMBLY NUMBER FOR THE FIRE | | | SAFING DETAIL OF PIPE PENETRATIONS SHALL | | | BE ON THE PLANS.COUNTYWIDE AMENDMENTS TO | | | SPC SEC.104.2.1. | | | | | | SHT.CS-1-REVISE EDITION OF STANDARD GAS | | | CODE TO READ 1997 EDITION. | | | | | | SHT.CS-1-BUILDING SUMMARY-SANITARY | | | FACILITIES CANNOT BE BASED ON 50% MALES | | | AND 50% FEMALES.TABLE 407 OF THE SPC | | | LISTS SANITARY FACILITIES FOR TOTAL | | | PERSONS. | | | | | | EMPLOYEE TOILET ROOM SHALL BE HANDICAP | | | ACCESSIBLE PER FACBC SEC.4.1.3.(11) | | | | | | FLUSH CONTROLS IN ACCESSIBLE STALLS AND | | | TOILET ROOMS SHALL BE LOCATED ON THE | | | WIDE SIDE PER FACBC SEC.4.16.5. | | | | | | CONDENSATE DRAINS CANNOT DISCHARGE TO | | | FLOOR SINK.DISPOSAL SHALL COMPLY W/SMC | | | SEC.304.8.3. | | | | | | SHT.P-3-FLOOR SINK SHALL NOT EXCEED | | | DISTANCE FROM VENT AS MANDATED IN SPC | | | SEC.908.1.(SEE F.S.BY MENS R.R.) | | | | | | DRY VENTS NOT PERMITTED PER SPC SEC. | | | 906.2.1.(SEE VENT BY WINE ROOM) |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-06-14 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-14 |
Time |
12:23 |
Rev Time |
6.75 |
| Received By |
pschmitz |
Date |
2000-06-14 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SUBMIT OCCUPANT LOAD BASED UPON 40 SQ. | | | FT.PER PERSON PER TABLE 407 OF SPC.SEE | | | SPC SEC.407.1.3.FOR ALLOWED DEDUCTIBLE | | | AREAS. | | | | | | URINAL IN MEN'S ROOM IS LOCATED IN LINE | | | OF SIGHT FROM CORRIDOR.FIXTURES SHALL BE | | | SUITABLY SCREENED FOR PRIVACY PER SPC | | | 404.3. | | | | | | NUMBER AND LOCATION OF PLUMBING FIXTURES | | | ON SHT.PR-1 DOESN'T CORRELATE W/ARCH. | | | DRAWINGS.CLARIFY.COUNTYWIDE AMENDMENTS | | | TO SPC 104.2.1. | | | | | | DISHWASHER SHALL DISCHARGE TO THE | | | SANITARY SYSTEM PER CITY OF WEST PALM | | | BEACH ORDINANCE. | | | | | | INDICATE IF GREASE TRAP/GREASY WASTE | | | SYSTEM IS NEW OR EXISTING.SUBMIT DETAILS | | | ON GREASE TRAP.GREASE RECOVERY UNITS ARE | | | NOT PERMITTED.SPC 1004.2 | | | | | | INDIRECT WASTES SHALL DISCHARGE TO FLOOR | | | SINKS PER 807.1.2, 807.1.3. | | | | | | THE DISCHARGE FROM ALL SINKS,INDIRECT | | | WASTES,ETC.(EXCEPT THE DISHWASHER)SHALL | | | DISCHARGE TO THE GREASY WASTE SYSTEM. | | | SPC SEC.1004.4 | | | | | | SUBMIT APPROVAL FROM CITY OF WPB | | | UTILITIES FOR GREASE TRAP. | | | | | | 2-WAY CLEANOUTS ARE REQD.ON THE INLET | | | AND OUTLET OF THE GREASE INTERCEPTOR PER | | | SPC SEC.710.4. | | | | | | SHT.P-3-VENTS FOR FLOOR DRAINS SHALL | | | 6"ABOVE FLOOD LEVEL RIM PRIOR TO OFF- | | | SETTING HORIZONTALLY PER SPC SEC.906.2.1 | | | | | | SUBMIT COMPLETE GAS RISER DIAGRAM FOR | | | REVIEW.SHOW DISTANCE TO MOST REMOTE | | | OUTLET,PIPE SIZES,PIPE MATERIAL,BTU LOAD | | | OF EACH APPLIANCE, ETC.COMPLY W/SGC SEC. | | | 305.4. | | | | | | GAS CONTROLS SHALL COMPLY W/NFPA 54 SEC. | | | 5.5.4. | | | | | | LOCATION OF GAS VALVES FOR EQUIPMENT | | | SHALL BE READILY ACCESSIBLE PER SGC SEC. | | | 310.1. | | | | | | PLEASE SUBMIT A LEGIBLE AND EXPANDED | | | SANITARY ISOMETRIC FOR REVIEW.(SEE REST- | | | ROOM AREAS.)COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1. | | | | | | BACKFLOW PREVENTERS ARE REQD.ON THE | | | CARBONATION EQUIP PER SPC SEC.606.1. | | | | | | SHT.P-6-NOTE #8-INSTALLATION OF CLEAN- | | | OUTS IN THE DRAINAGE SYSTEM SHALL COMPLY | | | W/SPC SEC.710.2.4. | | | | | | SUBMIT MANUF.SHEETS FOR COMPONENTS OF | | | THE 2# SYSTEM.SGC SEC.1006. | | | | | | A VACUUM RELIEF VALVE IS REQD.ON THE | | | COLD WATER SUPPLY TO THE WATER HEATERS | | | PER SPC SEC.507.1.2. | | | | | | SUBMIT U.L. ASSEMBLY NUMBER FOR FIRE | | | SAFING DETAIL OF PIPE PENETRATIONS THRU | | | RATED WALLS.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.4. | | | | | | NUMBER OF REQUIRED SANITARY FACILITIES | | | SHALL COMPLY W/FLA.STATUTE 553.141. | | | (POTTY PARITY) |
|
|