Plan Review Details - Permit 00060536
Plan Review Stops For Permit 00060536
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-12 Cont ID  
Sent By hpiskura Date 2000-07-12 Time 10:41 Rev Time 0.00
Received By hpiskura Date 2000-07-12 Time 10:26 Sent To  
Notes
2001-01-08 00:00:00DENIED
 TWO INDEPENDENT EXITS ARE REQUIRED. SEE
 SBC 1004.2.2 AND SBC 1004.1.4.
  
 SHOW A CONSTRUCTION DETAIL FOR THE
 WALL AND PARTITON INFILL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-19 Cont ID  
Sent By dpalmer Date 2000-06-19 Time 20:40 Rev Time 0.00
Received By dpalmer Date 2000-06-19 Time 20:40 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT ALL BRANCH CIRCUIT
 #`S ON PLANS .
  
 2)NOTE: SHOW EXISTING PANEL AND SUBMIT
 PANEL SCHEDLUE TO CORRELATE WITH PLANS.
  
 3)NOTE: SUBMIT LOAD CALCULATION FOR
 SERVICE.215-5
  
 4)NOTE:LIGHTING TO FIGURED AT 125% FOR
 CONTIUOUS LOAD.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-29 Cont ID  
Sent By rturnque Date 2000-06-29 Time 11:01 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE ILLUMINATED EXIT MARKINGS AND
 EMERGENCY LIGHTS IN SHOWROOM AND
 WORKSHOP AREA.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-13 Cont ID  
Sent By cthirben Date 2000-06-13 Time 08:24 Rev Time 0.00
Received By cthirben Date 2000-06-13 Time 08:23 Sent To  
Notes
2001-01-08 00:00:00NOTES **********************************
 NO MECHANICAL PLANS SUBMITTED FOR REVIEW