Plan Review Details - Permit 00060472
Plan Review Stops For Permit 00060472
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-12-21 Cont ID  
Sent By rmcdouga Date 2000-12-21 Time 14:52 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00TRUSSES
  
 DENIED
  
 1)PLEASE INDICATE THE TRUSS ANCHORS THAT
 ARE TO BE USED WHERE NONE IS SPECIFIED.
  
 2)THERE IS NO DETAIL C OR C1 SHOWN ON
 SHEET A-8.
  
 3)TRUSS GTD HAS NO ANCHOR INDICATED FOR
 THE LEFT SIDE WHICH TRUSS DRAWINGS SHOW
 7097# OF UPLIFT. STEEL COLUMN IS NOT
 INDICATED ON REVISED DRAWING,UPLIFT AND
 BEARING CAPACITY INDICATED ON TRUSS
 DRAWING EXCEED THOSE LISTED ON SHEET A-8
  
 4)TRUSS GTK HAS UPLIFTS OF 1063# AND
 1713# WITH NO CONNECTORS SPECIFIED.
  
 5)TRUSS GTC IS INDICATED AS HAVING AN
 A-3 ANCHOR. THIS SHOULD BE A STEEL
 COLUMN.
  
 6)TRUSS HB1 IS INDICATED AS HAVING AN
 A-3 ANCHOR AT WOOD FRAME INTERIOR
 BEARING WALL. THIS ANCHOR IS DESIGNED
 FOR EMBEDMENT INTO CONCRETE.
  
 7)A-3 ANCHOR (UPLIFT 2900#)IS INDICATED
 FOR TRUSS GTH1 TRUSS ENGINEERING
 REQUIRES 4652# OF UPLIFT.
  
 8)A-3 ANCHOR (UPLIFT 2900#)IS INDICATED
 FOR TRUSS GTG1 TRUSS ENGINEERING
 REQUIRES 3874# OF UPLIFT.
  
 9)TRUSS ENGINEERING CALLS FOR 1199# OF
 UPLIFT FOR TRUSS HE1,THIS TRUSS IS TO
 BE ANCHORED TO FGTM TRUSSES AT COVERED
 ENTRY. EITHER THE ARCHITECT OR TRUSS
 ENGINEER NEEDS TO INDICATE CONNECTORS
 FOR THESE TRUSSES AND THE SIMILAR ONES
 LOCATED AT REAR PORCH.
  
 10)PLEASE STEEL COLUMNS TO ENSURE THEY
 HAVE ADEQUATE BEARING AREA FOR THE
 TRUSSES THEY SUPPORT.
  
 PLEASE HAVE ARCHITECT ADDRESS THESE
 ITEMS. IF YOU HAVE ANY QUESTIONS PLEASE
 CALL ROBERT MCDOUGAL AT 561-659-8096
 EXT.8202.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-11-08 Cont ID  
Sent By rmcdouga Date 2000-11-08 Time 10:46 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00TRUSS LAYOUT AND TRUSS DRAWINGS
 ****************DENIED******************
  
 1)DUE TO THE AMOUNT OF CHANGES BETWEEN
 THE ARCHITECT'S ROOF FRAMING PLAN AND
 THE ENGINEERED TRUSS LAYOUT, PLEASE
 PROVIDE A REVISED ROOF FRAMING PLAN
 (SHEET A-7) WHICH ADDRESS THE CHANGES
 AND SPECIFIES REQUIRED CONNECTORS AND
 UPLIFTS.
  
 2)CONNECTION DETAIL(C AND C1 ON A-8)AS
 INDICATED ON SHEET A-7 ARE NOT SHOWN OR
 ARE MISIDENTIFIED AS DETAIL B AND B-1.
 PLEASE CLARIFY.
  
 3)PLEASE INDICATE SPECIFIC CONNECTORS
 AND UPLIFT CAPACITY OF TRUSS TO GIRDER
 CONNECTIONS AT ENTRY FOYER AND COVERED
 PORCH.
  
 4)THE UPLIFT LOADS INDICATED ON THE
 TRUSS DRAWING EXCEED THE VALUES OF THE
 CONNECTORS SPECIFIED FOR TRUSS GTD.
  
 5)DETAIL 2 ON A-8 FOR INTERIOR BEARING
 WALLS SPECIFIES SEMCO RTP 18816 WHICH
 ARE RATED AT 1172# UPLIFT TRUSS DRAWINGS
 LIST UPLIFT AT 1204#.
  
 6)TRUSS LAYOUT SHOWS FGTM1 AS A THREE
 MEMBER TRUSS, HAS (2M) TWO MEMBER ? AND
 TRUSS DRAWINGS INDICATE 1 PLY. PLEASE
 CLARIFY.
  
 7)PLEASE HAVE DESIGNER OF RECORD REVIEW
 TRUSS DRAWINGS FOR DISCREPANCIES IN
 ADDITION TO HIS REVIEW OF THE LAYOUT.
  
 8)PLEASE CLARIFY SPECIFIC CONNECTOR AND
 UPLIFT RATING TO BE USED ON TRUSSES NOT
 SPECIFICALLY NOTED.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 ROBERT MCDOUGAL AT 659-8096 EXT.8202.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-14 Cont ID  
Sent By dpalmer Date 2000-06-14 Time 21:02 Rev Time 0.00
Received By dpalmer Date 2000-06-14 Time 21:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-17 Cont ID  
Sent By cthirben Date 2000-06-17 Time 12:24 Rev Time 1.00
Received By cthirben Date 2000-06-17 Time 12:24 Sent To  
Notes
2001-01-08 00:00:00PROVISO:********************************
 PROVIDE ALL INFORMATION ON THE SIZE,
 LOCATION ETC OF FAN IN BATHROOM AND INFO
 OF DRYER VENT, RANGE AND HEATER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-14 Cont ID  
Sent By tlarge Date 2000-06-14 Time 19:59 Rev Time 0.33
Received By tlarge Date 2000-06-14 Time 19:23 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SUBMIT CALCULATIONS FOR
 COMBUSTION AIR .COMPLY W/SGC SEC.402.4

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2000-09-20 Cont ID  
Sent By rmcdouga Date 2000-09-20 Time 09:50 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION SUBMITTED 8-20-00 OK 9-20-00RLM
 RELOCATE STEEL COLUMN AND ADD BEARING
 WALL AND STEEL TO CARRY TRUSSES.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By rmcdouga Date 2000-07-05 Time 11:36 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-12 Cont ID  
Sent By gjoyce Date 2000-06-12 Time 14:19 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***