Plan Review Details - Permit 00060357
Plan Review Stops For Permit 00060357
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-12 Cont ID  
Sent By hpiskura Date 2000-07-12 Time 10:11 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-01 Cont ID  
Sent By dpalmer Date 2000-08-01 Time 08:43 Rev Time 0.00
Received By dpalmer Date 2000-07-31 Time 18:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-22 Cont ID  
Sent By dpalmer Date 2000-06-22 Time 19:24 Rev Time 0.00
Received By dpalmer Date 2000-06-22 Time 19:24 Sent To  
Notes
2001-01-08 00:00:00**************UNSAT ********************
  
 1)NOTE: PLEASE SEE E3.1. MISSING BRANCH
 CIRCUIT # FOR OUTLETS.(PETER`S OFFICE)
  
 2)NOTE: SUBMIT LOAD CALCULATION FOR
 EACH PANEL. YOU SHOW THE SAME LOAD ON
 EACH PANEL? PLEASE NOTE THAT CONTINUOUS
 LOADS ARE FIGURED AT 125% (LIGHTING)
 PLEASE GIVE A BREAKDOWN ON CALCS.
 OUTLETS, SQ.FT ETC.
  
 3)NOTE: PANEL 'H8A' SHOWS AIC RATING
 AT 14,000? THIS DOES NOT CORRELATE WITH
 STANDARD RATINGS OF EQUIPMENT. PLEASE
 CHECK.
  
 4)NOTE: PLEASE INDICATE ON PLANS THE
 MAIN DISCONNECT SIZE FOR THIS SPACE.
 IS IT THE SAME AS THE ON SHOWN FOR SMITH
 BARNEY?
  
 5)PLEASE SHOW PANEL SCHEDULES SHOWING
 CIRCUITS AS LIGHTING CIRCUITS TO CORRE-
 -LATE WITHROOM #S.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-07-14 Cont ID  
Sent By rturnque Date 2000-07-14 Time 10:40 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-21 Cont ID  
Sent By rturnque Date 2000-06-21 Time 10:30 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVIDE FIRE SPRINKLER DRAWINGS.
 PROVIDE DIRECTIONAL EXIT LIGHTS IN
 CORRIDOR W/I SPACE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-07-31 Cont ID  
Sent By cthirben Date 2000-07-31 Time 16:06 Rev Time 1.00
Received By cthirben Date 2000-07-31 Time 16:04 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 REVISION COMPLIED AS PER REVIEW DONE ON
 07.18.00.....

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 19:37 Rev Time 1.00
Received By cthirben Date 2000-07-18 Time 19:31 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 REVIEW ON 06.24.00 REQUIRES FIRE DAMPERS
 AT FIRE RATED WALLS. RESUBMITTED PLAN
 RESPONSE LETTER STATES THAT SHEET M7.2
 THE INFO.THERE IS NO SHEET M7.2.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-24 Cont ID  
Sent By cthirben Date 2000-06-24 Time 11:38 Rev Time 0.00
Received By cthirben Date 2000-06-24 Time 11:42 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 PROVIDE DETAILS FOR DAMPERS ATFIRE
 RATED WALLS PENETRATION OF DUCT FOR
 THE EXHAUST FAN AND SUPPLY DUCT. 1997

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-17 Cont ID  
Sent By pschmitz Date 2000-06-17 Time 12:34 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PROVISO
 (1) SEE SHT A-3 COMPLY WITH FACBC
 4.1.3 (11) HANDI-CAP ADAPTABEL.