Plan Review Details - Permit 00060287
Plan Review Stops For Permit 00060287
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2000-08-07 Cont ID  
Sent By drunnels Date 2000-08-07 Time 10:20 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-08-04 Cont ID  
Sent By drunnels Date 2000-08-04 Time 13:42 Rev Time 1.00
Received By drunnels Date 2000-08-04 Time 13:42 Sent To  
Notes
2001-01-08 00:00:001. SUBMIT LETTER FROM SPECIAL INSPECTOR
 RELEASING SPACE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-14 Cont ID  
Sent By fknapp Date 2000-07-14 Time 15:36 Rev Time 1.00
Received By bstaples Date 2000-07-14 Time 15:36 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
 REVIEW NOTES: 2ND REVIEW 7-14-00
 CALL 561-659-8096 EXT 8315
 WITH ANY QUESTIONS
  
 1)FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSUANCE OF THE BUILDING PERMIT.
  
 2)FLORIDA ENERGY SHEETS NEED SIGNATURE
 OF PERSON WHO PREPARED CALCULATIONS AND
 OWNER/AGENT.
  
 3)NEED COPIES OF ACTUAL PRODUCT APPROVAL
 FROM METRO DADE FOR IMPACT GLAZING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-13 Cont ID  
Sent By bstaples Date 2000-06-13 Time 08:36 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001ST REVIEW 6/13/00
 CALL 561-659-8096 EXT. 8315 IF QUESTIONS
 1. FIRE SPRINKLER PERMIT REQUIRED PRIOR
 TO ISSUANCE OF THE BUILDING PERMIT.
 2. FLORIDA ENERGY SHEETS 1997 CODE.
 3. SHEET 1D-1 NOTES
 A. NOTE #15: REVISE TO REFERENCE THE
 1997 STANDARD BUILDING CODE.
 B. NOTE#24: AND SHEET 1D-5 PROVIDE
 PRODUCT APPROVAL INFORMATION FOR IMPACT
 RESISTANT GLAZING FROM SBCCI OR METRO
 DADE COUNTY.
 C. NOTE #65: REFERENCE IS TO ADA, REVISE
 TO REFERENCE THE 1997 FLORIDA
 ACCESSAQBILITY CODE FOR BUILDING
 CONSTRUCTION.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-11-06 Cont ID  
Sent By dpalmer Date 2000-11-06 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2000-11-06 Time 18:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-17 Cont ID  
Sent By dpalmer Date 2000-07-17 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2000-07-17 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-15 Cont ID  
Sent By dpalmer Date 2000-06-15 Time 18:06 Rev Time 0.00
Received By dpalmer Date 2000-06-15 Time 18:05 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATINGS
 OF MAINS/PANELS.215-5 MAINS/PANELS MUST
 BE RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9.
  
 2)NOTE: PLEASE SUBMIT A CLEAR DETAILED
 RISER DIAGRAM,.SHOW THE ATTACHMENT FOR
 THE GROUNDING FOR TRANSFORMER.
 ALSO NOTE THAT YOU HAVE 70AMP OC PROTECT
 -ION GOING TO A 60 AMP DISCONNECT?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SHOW THE LOAD CALCULATION
 WITH THE BREAKDOWN OFCALCULATIONS.
 PLEASE INCLUDE ALL CONTINUOUS LOADS AT
 125% (LIGHTING) ETC. 215-5/220
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-19 Cont ID  
Sent By bstaples Date 2000-06-19 Time 13:44 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO M. CARSILLO 6/19/00

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-11-01 Cont ID  
Sent By ndenmark Date 2000-11-01 Time 13:44 Rev Time 0.33
Received By ndenmark Date 2000-11-01 Time 13:44 Sent To  
Notes
2001-01-08 00:00:00AS BUILTS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-14 Cont ID  
Sent By cthirben Date 2000-07-14 Time 12:10 Rev Time 1.00
Received By cthirben Date 2000-07-14 Time 12:09 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 REVISED PLANS COMPLIED WITH PREVIOUS
 REVIEW DATED 06.09.00.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-09 Cont ID  
Sent By cthirben Date 2000-06-09 Time 08:37 Rev Time 1.00
Received By cthirben Date 2000-06-09 Time 10:50 Sent To  
Notes
2001-01-08 00:00:00DENIED**********************************
 1. AUXILIARY DRAIN TO BE RUN SEPERATE
 FROM THE CONDENSATE DRAIN. 1997 SMC
 304.8.6.1.
 2. NO COMBUSTIBLES ALLOWED IN RETURN AIR
 PLENUM.SMC 609.1.1.
  
 3. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89.
 4. REQUIRES AIR BALANCE SCHEDULE PER
 1997 SMC 501.2.

Review Stop P PLUMBING
Rev No 3 Status P Date 2000-10-21 Cont ID  
Sent By pschmitz Date 2000-10-21 Time 07:32 Rev Time 0.50
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-19 Cont ID  
Sent By pschmitz Date 2000-07-15 Time 12:53 Rev Time 1.00
Received By pschmitz Date 2000-07-15 Time 12:52 Sent To  
Notes
2001-01-08 00:00:00SHT-M-1 A/C COND. TO COMMON COND.
 PROVIDED BY OWNER.
 VENT ON W/C TO BE DOWN STREAM OF W/C'S.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-26 Cont ID  
Sent By tlarge Date 2000-06-09 Time 12:13 Rev Time 0.65
Received By pschmitz Date 2000-06-09 Time 11:15 Sent To  
Notes
2001-01-08 00:00:00A DRINKING IS REQUIRED IN THE SPACE PER
 SPC SEC.407.FOUNTAIN SHALL BE H.C.
 ACCESSIBLE AND COMPLY W/FABC SEC.4.1.3.
 (10)(A).PROVISIONS SHALL BE MADE FOR
 PEOPLE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 DRESSING ROOMS SHALL COMPLY W/FACBC SEC.
 4.1.3.(21) ,4.35.
  
 DRY VENTS NOT PERMITTED ON SANITARY
 SYSTEM.(SEEVENTS FOR W.C.) COMPLY W/
 SPC 906.2.1.
  
 SHOW DRINKING FOUNTAIN ON SANITARY AND
 WATER RISERS.