| Plan Review Stops For Permit 00060164 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2000-12-15 |
Time |
07:44 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | TRUSS PLAN : FAILED | | | ARCH SET 964 ANCHORING LEGEND MAXIMUM | | | ALLOWABLE LIMIT 1170. TRUSS PLAN P.86 | | | 1327 REACTION. | | | T1A- ARCH PLAN VALUE NOT GIVEN | | | FGT2 2M 3 POINT BEARING AT FGT2 2X4 POST | | | TYPE OF HANGER? | | | GT4 3M R:2 REACTION 13,545 AT 7.25 WALL | | | CRUSHING VALUES? | | | H-26 R1:9501 R:2 9323 CRUSHING VALUES | | | ADMIN.CODE 104.21 SUCH INFORMATION SHALL | | | BE SPECIFIC, TRUSS TO TRUSS CONNECTIONS | | | TO BE SPECIFIC, TRUSS TO GIRDER CONNEC- | | | TION SHALL BE SPECIFIC.THIS INFORMATION | | | SHALL BE SUPPLIED BY THE TRUSS ENG. AND | | | REVIEWED BY THE DESIGNER OF RECORD |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-06-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-12 |
Time |
20:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-12 |
Time |
20:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2000-10-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2000-10-07 |
Time |
12:52 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2000-10-07 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-07-10 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-10 |
Time |
11:00 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-10 |
Time |
11:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-10 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-24 |
Time |
07:56 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-10 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: **************************** | | | INDICATE ON THE PLANS THE DRYER VENT AND | | | THE EXHAUST FANS IN BATHROOMS SIZES AND | | | WHERE THEY ARE VENTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-06-12 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-12 |
Time |
14:18 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-12 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED********************************** | | | SUPPLY AIR & RETURN AIR SHOWS ON PLANS | | | THAT AIR HANDLER UNIT #1, INDICATE THE | | | UNITS THAT SUPPLIES EACH AREA. | | | 2. A/C SUPPLY DROP ON AHU #2 NEEDS CFM | | | VALUE. | | | 3. INDICATE ON PLANS EXHAUST FANS SIZES, | | | DUCT SIZES IN THE BATHROOMS PER 1997 | | | SMC 503.1 | | | 4. PROVIDE THE DRYER SIZE OF THE VENT, | | | DUCT SIZE AND FAN ON PLANS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-14 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-14 |
Time |
20:42 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-06-14 |
Time |
20:42 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO:SUBMIT A SANITARY RISER PRIOR | | | TO PLUMBING INSPECTION THAT CORRELATES | | | W/FLOOR PLAN AND COMPLIES W/SPC IN ALL | | | RESPECTS.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.104.2.1 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2000-07-11 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-11 |
Time |
15:11 |
Rev Time |
2.00 |
| Received By |
fknapp |
Date |
2000-07-11 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | *************BUILDING PROVISO*********** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR DBL | | | AND SINGLE FRENCH DOORS. | | | | | | PLEASE SUBMIT PRIOR TO INSTALLATION. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2000-06-23 |
|
|
Cont ID |
|
| Sent By |
tmoore |
Date |
2000-06-23 |
Time |
17:22 |
Rev Time |
4.00 |
| Received By |
tmoore |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | ************DENIED******************* | | | | | | SBC 104.2.2 | | | | | | 1) PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR: | | | MULLIONS USED,ONE LIGHT FROSTED | | | FRENCH DOOR,OUTSWING SINGLE HUNG | | | FRENCH DOOR,OUTSWING HOLLOW METAL | | | DOOR,OUTSWING (FRONT DOOR) W/SIDE- | | | LITE,AND FIREPLACE WITH U.L.LISTING | | | | | | 2)PROVIDE MANUEL J, MISSING FROM | | | ENERGY CALCS. | | | | | | 3) BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED,IMPACT FEES MUST BE PAID TO | | | PALM BEACH CO.,THE PERMIT STAMPED BY | | | THEM AND THE RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. | | | | | | 4)PROVIDE ENGINEERING FOR ALL BUTT | | | GLASS OPENINGS. |
|
|