Plan Review Details - Permit 00060162
Plan Review Stops For Permit 00060162
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2001-03-20 Cont ID  
Sent By lmartine Date 2001-03-20 Time 13:35 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-03-20 00:00:00TRUSS ENGINEERING, PASSEDLM 3/20/01

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-13 Cont ID  
Sent By lmartine Date 2000-09-13 Time 11:07 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-09-01 Cont ID  
Sent By lmartine Date 2000-09-01 Time 14:04 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2001-01-08 00:00:002ND REVIEW
  
 1] PRODUCT TEST REPORTS SUBMITED ARE NOT
 ACCEPTABLE,CHECK REPORT NUMBERS.
 SUBMIT TESTING FOR ROOF COVER.
 2] PLANS SHALL REFERENCE ASCE 7-95 SEE
 NOTES ON S1.1.
 3] PROPOSED FIN. FLOOR 17.50' SHALL BE
 REFERENCED ON THE PLANS.
 4] IF THE CEILING WILL BE 1/2" DRYWALL
 PLEASE CHANGE THE DRAWINGS.
  
  
  
  
 REVIEWED BY;
 LUIS MARTINEZ
 659-8096 #8456

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-07-11 Cont ID  
Sent By hpiskura Date 2000-07-11 Time 14:45 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2000-10-03 Cont ID  
Sent By dpalmer Date 2000-10-03 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2000-10-03 Time 08:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 20:33 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE FIRST SET OF NOTES!!!
 LOAD CALCULATIONS HAVE STILL NOT BEEN
 SUBMITTED. SEE ART;215-5 OF THE NEC.
 PLEASE SUBMIT LOAD CALCULATIONS, LOADS
 AT 125% FOR CONTINUOUS LOADS AND FOR
 LARGEST MOTOR.
  
 2)NOTE: PLEASE SHOW BLDG.STEEL AND COLD
 WATER BOND FOR GROUNDING ELECTRODE
 SYSTEM. 250-50/215-5
  
 3)NOTE: AS PER CHANGES MADE TO SHEET
 E 2.2. PLEASE SEE FL ADMINISTRATIVE CODE
 AND COUNTY WIDE ADMIN. CODE 104.2 AND
 104.2.7. PLEASE RE-DO SHEET FOR CU DISC.
 CHANGES.
  
 4)NOTE: PLEASE SEE CIRCUIT 19/21PANEL
 "LA". SHOWS WIRE SIZE #12 W/ 25 OCP.AND
 #10 GROUND? PLEASE CLARIFY. SEE 240-3-D
 SEE CIRCUIT# 23/25
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL!!!!!
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-09-01 Cont ID  
Sent By dpalmer Date 2000-09-01 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2000-09-01 Time 09:09 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE FIRST REVIEW NOTES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-28 Cont ID  
Sent By dpalmer Date 2000-06-28 Time 20:03 Rev Time 0.00
Received By dpalmer Date 2000-06-28 Time 20:03 Sent To  
Notes
2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PROVIDE ONE LINE DIAGRAM OF
 RISER DIAGRAM.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCULATONS
 SHOWING WHERE THE TOTAL LOAD IS COMING
 FROM. PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN/FIGURED AT 125%
 PLEASE SHOW.
  
  
 3)NOTE PLEASE NOTE THE LOCATIONS OF A/C
 C.U. DISCONNECTS. REQ`D WITHIN 6`
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. 659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2000-06-26 Cont ID  
Sent By mgonzale Date 2000-06-26 Time 15:19 Rev Time 1.00
Received By mgonzale Date   Time   Sent To  
Notes
2001-01-08 00:00:00PASSEDE WITH PROVISOS ON PERMIT
 NUMBER 00041035 (SEE COPY ATTACHED)
  
 PLEASE PROVIDE PERVIOUS AND IMPERVIOUS
 CALCULATIONS ON 8 1/2 X 11 SHEET. SIGN
 AND SEALED BY CIVIL ENGINEER PLEASE ALSO
 INCLUDE ADDRESS AND PROPERTY CONTROL
 NUMBER.
  
 ALSO MUST HAVE ON PLAN SUNSHINE LOCATING
 NOTES AND CONTRACTOR SHALL CALL FOR
 LOCATING 48 HOURS PRIOR TO COMMENCEMENT.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-19 Cont ID  
Sent By rturnque Date 2000-07-19 Time 11:32 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-09-01 Cont ID  
Sent By ndenmark Date 2000-09-01 Time 08:48 Rev Time 0.50
Received By ndenmark Date 2000-09-01 Time 08:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-12 Cont ID  
Sent By cthirben Date 2000-07-12 Time 14:51 Rev Time 1.00
Received By cthirben Date 2000-07-12 Time 14:49 Sent To  
Notes
2001-01-08 00:00:00PROVISO:********************************
 FIRE DAMPERS REQUIRED WHERE DUCT PENE-
 TRATES RATED WALLS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-10-03 Cont ID  
Sent By tlarge Date 2000-10-03 Time 12:35 Rev Time 1.25
Received By tlarge Date 2000-10-03 Time 12:35 Sent To  
Notes
2001-01-08 00:00:00****************PROVISO*****************
 WATER CLOSETS AND FIXTURE BRANCHES NOT
 PERMITTED ON WET VENTS.SUBMIT REVISED
 SANITARY RISER PRIOR TO INSPECTION.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-09-12 Cont ID  
Sent By tlarge Date 2000-08-20 Time 10:04 Rev Time 0.50
Received By tlarge Date 2000-08-20 Time 09:50 Sent To  
Notes
2001-01-08 00:00:001)FLOOR DRAINS W/TRAP PRIMERS ARE REQD.
 IN THE TOILET ROOMS.SPC SEC.409.4.1.1.
  
 2)SUBMIT SIGNED AND SEALED WATER RISER
 DIAGRAM FOR ALL WORK BEING DONE.
  
 3)FIXTURE P-10 NOT ON PLUMBING RISER.
 SUBMIT SIGNED AND SEALED REVISED
 SANITARY RISER DIAGRAM.
  
 4)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SECS.4.1.3.,4.15.PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 5)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO A HEIGHT OF 4'PER SBC
 SEC.1204.2.
  
 *****NOTE:I WAS GOING TO APPROVE THIS
 PLAN W/PROVISOS BUT OTHER DISCIPLINES
 HAVE REJECTED THE PLANS.MAKE ALL THE
 REQUIRED PLUMBING CORRECTIONS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-17 Cont ID  
Sent By pschmitz Date 2000-06-17 Time 10:59 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PROVISO
 (1) COMPLY WITH FACBC 4.1.3(10)(A),
 4.15.1 SINGLE DRINKING FOUNTAIN.
 END OF COMMENTS

Review Stop Z ZONING
Rev No 1 Status P Date 2000-08-09 Cont ID  
Sent By hpiskura Date 2000-07-11 Time 14:45 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***