| Plan Review Stops For Permit 00060130 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
P |
Date |
2005-06-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2005-06-03 |
Time |
12:21 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2005-06-03 |
Time |
08:56 |
Sent To |
PC |
|
| Notes |
| 2005-06-03 00:00:00 | SPOKE WITH PETER ADLER. ELECTRICAL | | | INSPECTIONS WILL BE CALLED UPON RECEIPT | | | OF THE REVISIONS REVIEWED TODAY./WRT |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2005-04-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-04-11 |
Time |
11:00 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2005-04-11 |
Time |
11:00 |
Sent To |
P |
|
| Notes |
| 2005-04-11 00:00:00 | ************ UNSAT ************* | | | | | | *** PLEASE SEE ATTACHED NOTES FROM | | | 8/27/04 AND PLEASE SEE NEW NOTES DUE TO | | | MAJOR CHANGES IN PLANS. | | | | | | 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 2)NOTE: PLEASE SEE ALL OUTSIDE AND BATH | | | RECEPTS ARE ALSO TO BE GFI/GFI | | | PROTECTED. | | | 210.8 | | | | | | 3)NOTE: PLEASE SEE REVISIONS FOR SERVICE | | | ARE NOW CHANGING FROM THE LAST THREE | | | REVISIONS SUBMITTED?? | | | PLEASE SEE PLANS SHOW A "PANEL C" TO BE | | | FED YET, PLANS AND RISER DO NOT SHOW | | | THIS PANEL? | | | 215.5 | | | | | | 4)NOTE: PLEASE SEE RISER NOW INDICATES A | | | 350A SERVICE, PLEASE SEE 250.66, A MIN | | | OF #2 FOR GROUNDING ELECTRODE CONDUCTOR | | | IS REQUIRED. | | | | | | 5)NOTE: PLEASE SUBMIT COMPLETE PANEL | | | SCHEDULES INCLUDING ALL OCP AND AWG'S | | | FOR ALL BRANCH CIRCUITS. | | | 215.5 | | | | | | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS | | | PER NEC 220.31/220.31B | | | | | | 7)NOTE: PLEASE SEE MISSINF RECEPTS PER | | | 210.52E/210.8 | | | | | | 8)NOTE: PLEASE SEE SERVICE CLEARENCES DO | | | NOT MEET 110.26, AS PER CONVERSATION | | | OVER A YEAR AGO, WALL WAS GOING TO BE | | | MOVED TO MEET MIN 110.26, YET PLANS DO | | | NOT CORRELATE WITH THIS CHANGE. | | | | | | 9)NOTE: PLEASE SEE SD'S SHOWN BOTH | | | INSIDE MASTER BEDROOM. | | | PLEASE SEE NFPA-72 8-1.4.1.6.2 | | | | | | 10)NOTE: PLEASE CORRELATE ELECTRICAL | | | LOAD CALCS, PLANS AND MECH PLANS FOR | | | SIZE OF A/C UNITS/ HEAT STRIPS ETC. | | | 215.5 | | | | | | 11)NOTE: PLEASE SEE SEC'S ARE SHOWN AS | | | 2/0'S, PLEASE SEE 310.15B6 FOR MIN | | | SIZING. IF THESE ARE FPL CONDUCTORS, | | | PLEASE DO NOT INDICATE SIZE, (ONLY IF | | | FPL OWNED CONDUCTORS). | | | | | | 12)NOTE: PLEASE CORRELATE REV DATES ON | | | TITLE BLOCK WITH PLANS. PLEASE SEE PLANS | | | INDICATE LAST REVISED DATE OF 4/01 ?? | | | | | | 13)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONAL. | | | IF PLANS COME BACK WITH "ANY" OF THE | | | SAME COMMENTS FROM PREVIOUS REVIEWS NOT | | | ADDRESSED, A 4X FEE SHALL BE ACCESSSED | | | TO THE DESIGN PROFESSIONAL. | | | | | | 14)NOTE: PLEASE SEE AS PER PER OUR | | | RECORDS, NO ELECTRICAL ROUGH INSPECTIONS | | | WERE EVER MADE UNDER PREVIOUS OR NEW | | | ELECTRICAL PERMIT. PLEASE SEE 105.6 FBC | | | FOR REQUIRED INSPECTIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
F |
Date |
2004-08-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-27 |
Time |
10:42 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2004-08-27 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2004-08-27 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE AN ADDITION FOR AHU AND | | | WH IS NOW BEING SHOWN AS BUILT INFRONT | | | OF ELECTRICAL SERVICE W/OUT MEETING | | | CLEARENCE REQUIRED PER 110.26 | | | PLEASE NOTE: THIS ADDITION WILL BE | | | REQUIRED MOVED TO MEET 110.26 | | | | | | 2)NOTE: PLEASE SEE THERE IS NOW MORE | | | A/C SYSTEMS BEING ADDED. | | | PLEASE PROVIDE COMPLETE LOAD CALCULATION | | | -S FOR SERVICE. PLEASE ALSO PROVIDE | | | PANEL SCHEDULES W/ MIN CIRCUITS REQUIRED | | | 215.5/ 220.31B | | | | | | 3)NOTE: PLEASE SEE 210.8 FOR REQUIRED | | | GFI RECETPS FOR OUTSIDE. | | | PLEASE ALSO SEE BATHS ETC. | | | | | | 4)NOTE: PLEASE SEE 210.52D FOR MISSING | | | REQUIRED RECEPT IN BATH. | | | | | | PLEASE SEE THAT THE REQUIRED INSPECTIONS | | | MUST BE CALLED IN FOR ANY ELECTRICAL | | | WORK AND OTHER TRADES ALSO. | | | FBC 105.6 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2004-08-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-08-25 |
Time |
16:59 |
Rev Time |
1.50 |
| Received By |
dpalmer |
Date |
2004-08-25 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2004-08-25 00:00:00 | ON HOLD | | | NO REVIEWS TO BE DONE AT THIS TIME. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2001-04-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-24 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-17 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2001-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-04-05 |
Time |
19:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-04-05 |
Time |
19:46 |
Sent To |
|
|
| Notes |
| 2001-04-05 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: PLEASE NOTE THAT SAME NOTES ? | | | DIFFERENT PLANS??? | | | AS ON ALL PREVIOUS NOTES, IF THERE ARE | | | ANY QUESTIONS OR IF CLARIFICATION IS | | | NEEDED? PLEASE CALL. IF A MEETING IS | | | NEEDED TO GO OVER PLANS BEFORE | | | SUBMITTING AGAIN. PLEASE CALL FOR A | | | TIME TO MEET. | | | IF GOING OVER NOTES ON THE PHONE IS | | | BETTER, PLEASE CALL. | | | | | | 2)NOTE: PLEASE NOTE THAT SOME NOTES ARE | | | DONE, YET OTHERS? | | | | | | | | | PLEASE SUBMIT INFORMATION FOR REVIEW | | | THATS CORRELATES WITH THE NATIONAL | | | ELECTRIC CODE. PLEASE CALL IF THERE ARE | | | ANY QUESTIONS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2001-03-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2001-03-23 |
Time |
07:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2001-03-23 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2001-03-23 00:00:00 | ****************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE THAT ORIG PLANS | | | WEREDONE BY ANOTHER ARCH/ENGINEER. | | | PLANS NEED TO BE RE-DONE BY ORIG ARCH | | | OF RECORD OR WE NEED A LETTER OF | | | RELEASEEITHER FROM HOMEOWNER OR FROM | | | ARCH OF | | | RECORD. MUST BE A NOTORIZED LETTER. | | | | | | 2)NOTE: PLEASE ALSO NOTE THAT ALL PLANS | | | NEED TO BE SIGNED AND SEALED BY THE | | | ARCH/ENGINEER OF RECORD. F.A.C. F.S. | | | 481.221 AND 471.025. THESE PLANS WERE | | | NOT SIGNED OR SEALED. | | | | | | 3)NOTE: PLEASE NOTE THAT NOT ALL NOTES | | | FROM FRIST REVIEW/PROVISO WERE | | | ADDRESSEDA NEW SERVICE RISER DIAGRAM IS | | | NOW BEINGSHOWN. PANEL "B" IS SHOWN AT | | | 125A AND | | | ON PLANS IT IS SHOWN AT 60A? | | | STILL NEED PANEL SCHEDULES TO CLARIFY | | | ALL REQ`D CIRCUITS. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLETS | | | SERVINGKITCHEN COUNTERSPACE AS GFI/GFI | | | PROTECT--ED PER 210-8-A-6. | | | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 7) NOTE: PLEASE SHOW GROUNDING | | | ELECTRODEGOING TO BUILDING STEEL AND | | | COLD WATER | | | PER 250-50. FROM FIRST REVIEW. | | | | | | 8)NOTE: PLEASE NOTE THAT AN EQUIPMENT GR | | | OUNDING CONDUCTOR IS SHOWN FROM METER | | | TO FIRST MEANS OF DISC. THIS IS NOT | | | PERMITTED. | | | | | | | | | PLEASE ADDRESS THE ABOVE COMMENTS. | | | PLEASE SUBMIT INFORMATION FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-06 |
Time |
20:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-06 |
Time |
20:01 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT REQ`MENTS FOR | | | SMOKE DETECTORS FOR ENTIRE HOUSE WILL | | | NEED TO BE BROUGHT UP TO CODE INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS. | | | NFPA-72 | | | | | | 2)NOTE: PLEASE NOTE 210-70 FOR EGRESS | | | LIGHTING. SWITCHES MUST BE INSTALLED | | | FOR EXISTING ROOMS EXITING OUTSIDE. | | | SWITCH IS TO BE LOCATED IN EACH ROOM. | | | | | | 3)NOTE;PLEASE SUBMIT PANEL | | | SCHEDULES FOR BOTH PANELS.PLEASE INCLUDE | | | ALL THE REQ`D CIRCUITS SHOWN. | | | PLEASE LIST BATH(S) CIRCUIT(S) 210-11-C- | | | -3. | | | | | | 4)NOTE:PLEASE IDENTIFY THE OUTLET AT | | | A/C CU LOCATIONS.?? | | | | | | 5)NOTE: PLEASE INCLUDE THE BLDG.STEEL | | | OF NEW STRUCTURE AS PART OF THE GROUND- | | | -ING ELECTRODE SYSTEM. AS REQ`D BY NEC | | | ART;250-50. PLEASE SHOW ON RISER | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. PLEASE SUBMIT BEFORE ROUGH | | | ELECTRICAL INSPECTION IS CALLED IN. | | | FI THERE ARE ANY QUESTIONS PLEASE CALL | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-03-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-03-31 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-03-31 |
Time |
16:47 |
Sent To |
E |
|
| Notes |
| 2005-03-31 00:00:00 | TO "DPALMER" DESK/REVISION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2004-08-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-08-24 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-08-24 |
Time |
13:56 |
Sent To |
E |
|
| Notes |
| 2004-08-24 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-04-20 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-04-20 |
Time |
11:43 |
Rev Time |
1.50 |
| Received By |
prafter |
Date |
2005-04-20 |
Time |
11:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-06-08 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-08 |
Time |
10:07 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-08 |
Time |
10:04 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO********************************* | | | INDICATE RETURN AIR OF CABANA A/C UNIT | | | ON PLANS. | | | CFM VALUE OF THE SUPPLY DROPS. | | | PROVIDE DUCT SIZES OF SUPPLY AND RETURN. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2005-06-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-06-02 |
Time |
06:43 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2005-06-02 |
Time |
06:43 |
Sent To |
E |
|
| Notes |
| 2005-06-02 00:00:00 | REVISION OK - NO DEAD ENDS PER SECTION | | | 311.7.3 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2005-04-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2005-04-15 |
Time |
15:06 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2005-04-15 |
Time |
15:05 |
Sent To |
M |
|
| Notes |
| 2005-04-15 00:00:00 | DENIED | | | REFERENCE: SBCCI-94 STANDARD PLUMBING | | | | | | CODE | | | SBCCI-97 STANDARD BUILDING | | | CODE | | | | | | 1) SHT S-1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. CORRECT THE | | | FOLLOWING: | | | A) THE FLOOR DRAINS SHALL HAVE A TRAP | | | PER SECTION 409.4.1.2. | | | B) WASH MACHINE SHALL NOT DRAIN THROUGH | | | THE WET VENT FOR THE BATHROOM FIXTURES. | | | SECTION 611. | | | C) 3" VENT THROUGH THE TIE BEAM IS NOT | | | APPROVED. SECTION 1907.3.6(3). MAXIMUM | | | 2" INSIDE DIAMETER NOMINAL. | | | D) DEAD ENDS NOT APPROVED. SECTION | | | 311.7.3 | | | 2) FLOOR PLAN SHOWS THE FLOOR DRAIN | | | UNDER THE BATH TUB. THE FLOOR DRAIN | | | SHALL BE ACCESSIBLE PER SECTION | | | 409.4.1.2. | | | 3) SEE ATTACHED SHEET FOR AN EXAMPLE OF | | | A SANITARY RISER DIAGRAM THAT REFLECTS | | | THE FLOOR PLAN AND MEETS THE CODE | | | REQUIREMENTS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2001-04-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-04-14 |
Time |
06:16 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2001-04-14 |
Time |
06:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2001-03-12 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2001-03-12 |
Time |
18:48 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2001-03-12 |
Time |
18:48 |
Sent To |
|
|
| Notes |
| 2001-03-12 00:00:00 | DENIED; | | | | | | RISER DIAGRAM NOT TO CODE. HAVE PLUMBING | | | CONTRACTOR DRAW PLUMBING RISER AND LINE | | | DRAWING SHOWING HOW PLUMBING WILL BE | | | INSTALLED.FLOOR DRAINS MUST HAVE TRAP | | | PRIMERS, 3" STACK IS WERE W/M IS THAT | | | PIPE BY CODE SHOULD HAVE A CLEAN OUT AT | | | 48" FROM THE FLOOR. CONTINUEING YOUR | | | BUILDING DRAIN DRAIN IS NOT TO CODE. | | | | | | PLUMBING PLAN REVIEW BY | | | JOHN LEECH | | | 659-8096 EXT. 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-07 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-07 |
Time |
20:08 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-06-07 |
Time |
20:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2001-12-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-12-19 |
Time |
08:54 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-19 00:00:00 | TRUSSES OK 12-19-01 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2001-12-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-12-03 |
Time |
10:14 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-12-03 00:00:00 | TRUSSES | | | DENIED | | | | | | 1) THE TRUSS LAYOUT MUST HAVE THE WET | | | SIGNATURE, DATE AND EMBOSSED SEAL OF THE | | | TRUSS ENGINEER. IT ALSO MUST BE REVIEWED | | | AND SIGNED BY THE DESIGNER OF RECORD FOR | | | THE STRUCTURE. | | | | | | 2) THE TRUSS DRAWINGS MUST HAVE THE | | | ORIGIONAL SIGNATURE, DATE AND EMBOSSED | | | SEAL ON THEM. SIGNATURE STAMP IS NOT | | | ACCEPTABLE. | | | | | | 3) THE DESIGN CRITERIA GIVEN ON THE | | | TRUSS DRAWINGS AND TRUSS LAYOUT AS | | | ASCE 7-93 IS NOT ACCEPTABLE. TRUSSES | | | MUST COMPLY WITH ASCE 7-95 OR 97 SBC | | | SECTION 1606. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2001-09-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-09-20 |
Time |
16:47 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2001-08-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2001-08-13 |
Time |
13:54 |
Rev Time |
2.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-08-13 00:00:00 | REVISION OK 8-13-01 RM |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2000-07-05 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-05 |
Time |
10:26 |
Rev Time |
4.00 |
| Received By |
fknapp |
Date |
2000-06-30 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | ****************PROVISO***************** | | | | | | SBC 104.2.2 | | | | | | 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR: | | | A)ALL EXTERIOR DOORS AND WINDOWS. | | | B)ROOF COVERING UNDER SEPERATE PERMIT. | | | C)STORM PANELS FOR ALL NON IMPACT | | | GLASS WITH INSTALLATION SCHEDULE AND | | | KEY PLAN WITH SPECIFIC ANCHORS USED. | | | | | | 2)BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH CO., THE PERMIT PLANS STAMPED BY | | | THEM AND THE RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2001-08-08 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2001-08-08 |
Time |
14:34 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-06-06 |
Time |
09:36 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ADDTION TO BE 5' FROM S P/L AND 9'6" FRO | | | REAR GMJ |
|
|