Plan Review Details - Permit 00060130
Plan Review Stops For Permit 00060130
Review Stop E ELECTRICAL
Rev No 8 Status P Date 2005-06-03 Cont ID  
Sent By btrobaug Date 2005-06-03 Time 12:21 Rev Time 0.75
Received By btrobaug Date 2005-06-03 Time 08:56 Sent To PC
Notes
2005-06-03 00:00:00SPOKE WITH PETER ADLER. ELECTRICAL
 INSPECTIONS WILL BE CALLED UPON RECEIPT
 OF THE REVISIONS REVIEWED TODAY./WRT

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2005-04-11 Cont ID  
Sent By dpalmer Date 2005-04-11 Time 11:00 Rev Time 1.50
Received By dpalmer Date 2005-04-11 Time 11:00 Sent To P
Notes
2005-04-11 00:00:00************ UNSAT *************
  
 *** PLEASE SEE ATTACHED NOTES FROM
 8/27/04 AND PLEASE SEE NEW NOTES DUE TO
 MAJOR CHANGES IN PLANS.
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 2)NOTE: PLEASE SEE ALL OUTSIDE AND BATH
 RECEPTS ARE ALSO TO BE GFI/GFI
 PROTECTED.
 210.8
  
 3)NOTE: PLEASE SEE REVISIONS FOR SERVICE
 ARE NOW CHANGING FROM THE LAST THREE
 REVISIONS SUBMITTED??
 PLEASE SEE PLANS SHOW A "PANEL C" TO BE
 FED YET, PLANS AND RISER DO NOT SHOW
 THIS PANEL?
 215.5
  
 4)NOTE: PLEASE SEE RISER NOW INDICATES A
 350A SERVICE, PLEASE SEE 250.66, A MIN
 OF #2 FOR GROUNDING ELECTRODE CONDUCTOR
 IS REQUIRED.
  
 5)NOTE: PLEASE SUBMIT COMPLETE PANEL
 SCHEDULES INCLUDING ALL OCP AND AWG'S
 FOR ALL BRANCH CIRCUITS.
 215.5
  
 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER NEC 220.31/220.31B
  
 7)NOTE: PLEASE SEE MISSINF RECEPTS PER
 210.52E/210.8
  
 8)NOTE: PLEASE SEE SERVICE CLEARENCES DO
 NOT MEET 110.26, AS PER CONVERSATION
 OVER A YEAR AGO, WALL WAS GOING TO BE
 MOVED TO MEET MIN 110.26, YET PLANS DO
 NOT CORRELATE WITH THIS CHANGE.
  
 9)NOTE: PLEASE SEE SD'S SHOWN BOTH
 INSIDE MASTER BEDROOM.
 PLEASE SEE NFPA-72 8-1.4.1.6.2
  
 10)NOTE: PLEASE CORRELATE ELECTRICAL
 LOAD CALCS, PLANS AND MECH PLANS FOR
 SIZE OF A/C UNITS/ HEAT STRIPS ETC.
 215.5
  
 11)NOTE: PLEASE SEE SEC'S ARE SHOWN AS
 2/0'S, PLEASE SEE 310.15B6 FOR MIN
 SIZING. IF THESE ARE FPL CONDUCTORS,
 PLEASE DO NOT INDICATE SIZE, (ONLY IF
 FPL OWNED CONDUCTORS).
  
 12)NOTE: PLEASE CORRELATE REV DATES ON
 TITLE BLOCK WITH PLANS. PLEASE SEE PLANS
 INDICATE LAST REVISED DATE OF 4/01 ??
  
 13)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 IF PLANS COME BACK WITH "ANY" OF THE
 SAME COMMENTS FROM PREVIOUS REVIEWS NOT
 ADDRESSED, A 4X FEE SHALL BE ACCESSSED
 TO THE DESIGN PROFESSIONAL.
  
 14)NOTE: PLEASE SEE AS PER PER OUR
 RECORDS, NO ELECTRICAL ROUGH INSPECTIONS
 WERE EVER MADE UNDER PREVIOUS OR NEW
 ELECTRICAL PERMIT. PLEASE SEE 105.6 FBC
 FOR REQUIRED INSPECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-08-27 Cont ID  
Sent By dpalmer Date 2004-08-27 Time 10:42 Rev Time 2.00
Received By dpalmer Date 2004-08-27 Time 10:42 Sent To  
Notes
2004-08-27 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE AN ADDITION FOR AHU AND
 WH IS NOW BEING SHOWN AS BUILT INFRONT
 OF ELECTRICAL SERVICE W/OUT MEETING
 CLEARENCE REQUIRED PER 110.26
 PLEASE NOTE: THIS ADDITION WILL BE
 REQUIRED MOVED TO MEET 110.26
  
 2)NOTE: PLEASE SEE THERE IS NOW MORE
 A/C SYSTEMS BEING ADDED.
 PLEASE PROVIDE COMPLETE LOAD CALCULATION
 -S FOR SERVICE. PLEASE ALSO PROVIDE
 PANEL SCHEDULES W/ MIN CIRCUITS REQUIRED
 215.5/ 220.31B
  
 3)NOTE: PLEASE SEE 210.8 FOR REQUIRED
 GFI RECETPS FOR OUTSIDE.
 PLEASE ALSO SEE BATHS ETC.
  
 4)NOTE: PLEASE SEE 210.52D FOR MISSING
 REQUIRED RECEPT IN BATH.
  
 PLEASE SEE THAT THE REQUIRED INSPECTIONS
 MUST BE CALLED IN FOR ANY ELECTRICAL
 WORK AND OTHER TRADES ALSO.
 FBC 105.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2004-08-25 Cont ID  
Sent By dpalmer Date 2004-08-25 Time 16:59 Rev Time 1.50
Received By dpalmer Date 2004-08-25 Time 16:32 Sent To  
Notes
2004-08-25 00:00:00ON HOLD
 NO REVIEWS TO BE DONE AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2001-04-17 Cont ID  
Sent By csiegber Date 2004-08-24 Time 13:56 Rev Time 0.00
Received By dpalmer Date 2001-04-17 Time 16:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2001-04-05 Cont ID  
Sent By dpalmer Date 2001-04-05 Time 19:46 Rev Time 0.00
Received By dpalmer Date 2001-04-05 Time 19:46 Sent To  
Notes
2001-04-05 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT SAME NOTES ?
 DIFFERENT PLANS???
 AS ON ALL PREVIOUS NOTES, IF THERE ARE
 ANY QUESTIONS OR IF CLARIFICATION IS
 NEEDED? PLEASE CALL. IF A MEETING IS
 NEEDED TO GO OVER PLANS BEFORE
 SUBMITTING AGAIN. PLEASE CALL FOR A
 TIME TO MEET.
 IF GOING OVER NOTES ON THE PHONE IS
 BETTER, PLEASE CALL.
  
 2)NOTE: PLEASE NOTE THAT SOME NOTES ARE
 DONE, YET OTHERS?
  
  
 PLEASE SUBMIT INFORMATION FOR REVIEW
 THATS CORRELATES WITH THE NATIONAL
 ELECTRIC CODE. PLEASE CALL IF THERE ARE
 ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2001-03-23 Cont ID  
Sent By dpalmer Date 2001-03-23 Time 07:42 Rev Time 0.00
Received By dpalmer Date 2001-03-23 Time 07:30 Sent To  
Notes
2001-03-23 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ORIG PLANS
 WEREDONE BY ANOTHER ARCH/ENGINEER.
 PLANS NEED TO BE RE-DONE BY ORIG ARCH
 OF RECORD OR WE NEED A LETTER OF
 RELEASEEITHER FROM HOMEOWNER OR FROM
 ARCH OF
 RECORD. MUST BE A NOTORIZED LETTER.
  
 2)NOTE: PLEASE ALSO NOTE THAT ALL PLANS
 NEED TO BE SIGNED AND SEALED BY THE
 ARCH/ENGINEER OF RECORD. F.A.C. F.S.
 481.221 AND 471.025. THESE PLANS WERE
 NOT SIGNED OR SEALED.
  
 3)NOTE: PLEASE NOTE THAT NOT ALL NOTES
 FROM FRIST REVIEW/PROVISO WERE
 ADDRESSEDA NEW SERVICE RISER DIAGRAM IS
 NOW BEINGSHOWN. PANEL "B" IS SHOWN AT
 125A AND
 ON PLANS IT IS SHOWN AT 60A?
 STILL NEED PANEL SCHEDULES TO CLARIFY
 ALL REQ`D CIRCUITS.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLETS
 SERVINGKITCHEN COUNTERSPACE AS GFI/GFI
 PROTECT--ED PER 210-8-A-6.
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 7) NOTE: PLEASE SHOW GROUNDING
 ELECTRODEGOING TO BUILDING STEEL AND
 COLD WATER
 PER 250-50. FROM FIRST REVIEW.
  
 8)NOTE: PLEASE NOTE THAT AN EQUIPMENT GR
 OUNDING CONDUCTOR IS SHOWN FROM METER
 TO FIRST MEANS OF DISC. THIS IS NOT
 PERMITTED.
  
  
 PLEASE ADDRESS THE ABOVE COMMENTS.
 PLEASE SUBMIT INFORMATION FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By dpalmer Date 2000-06-06 Time 20:01 Rev Time 0.00
Received By dpalmer Date 2000-06-06 Time 20:01 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: PLEASE NOTE THAT REQ`MENTS FOR
 SMOKE DETECTORS FOR ENTIRE HOUSE WILL
 NEED TO BE BROUGHT UP TO CODE INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 NFPA-72
  
 2)NOTE: PLEASE NOTE 210-70 FOR EGRESS
 LIGHTING. SWITCHES MUST BE INSTALLED
 FOR EXISTING ROOMS EXITING OUTSIDE.
 SWITCH IS TO BE LOCATED IN EACH ROOM.
  
 3)NOTE;PLEASE SUBMIT PANEL
 SCHEDULES FOR BOTH PANELS.PLEASE INCLUDE
 ALL THE REQ`D CIRCUITS SHOWN.
 PLEASE LIST BATH(S) CIRCUIT(S) 210-11-C-
 -3.
  
 4)NOTE:PLEASE IDENTIFY THE OUTLET AT
 A/C CU LOCATIONS.??
  
 5)NOTE: PLEASE INCLUDE THE BLDG.STEEL
 OF NEW STRUCTURE AS PART OF THE GROUND-
 -ING ELECTRODE SYSTEM. AS REQ`D BY NEC
 ART;250-50. PLEASE SHOW ON RISER
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. PLEASE SUBMIT BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 FI THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-03-31 Cont ID  
Sent By adarroug Date 2005-03-31 Time 16:47 Rev Time 0.00
Received By adarroug Date 2005-03-31 Time 16:47 Sent To E
Notes
2005-03-31 00:00:00TO "DPALMER" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-08-24 Cont ID  
Sent By csiegber Date 2004-08-24 Time 13:56 Rev Time 0.00
Received By csiegber Date 2004-08-24 Time 13:56 Sent To E
Notes
2004-08-24 00:00:00TO DP DESK/REV

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-04-20 Cont ID  
Sent By prafter Date 2005-04-20 Time 11:43 Rev Time 1.50
Received By prafter Date 2005-04-20 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-08 Cont ID  
Sent By cthirben Date 2000-06-08 Time 10:07 Rev Time 1.00
Received By cthirben Date 2000-06-08 Time 10:04 Sent To  
Notes
2001-01-08 00:00:00PROVISO*********************************
 INDICATE RETURN AIR OF CABANA A/C UNIT
 ON PLANS.
 CFM VALUE OF THE SUPPLY DROPS.
 PROVIDE DUCT SIZES OF SUPPLY AND RETURN.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-06-02 Cont ID  
Sent By kstevens Date 2005-06-02 Time 06:43 Rev Time 1.00
Received By kstevens Date 2005-06-02 Time 06:43 Sent To E
Notes
2005-06-02 00:00:00REVISION OK - NO DEAD ENDS PER SECTION
 311.7.3

Review Stop P PLUMBING
Rev No 4 Status F Date 2005-04-15 Cont ID  
Sent By kstevens Date 2005-04-15 Time 15:06 Rev Time 1.25
Received By kstevens Date 2005-04-15 Time 15:05 Sent To M
Notes
2005-04-15 00:00:00DENIED
 REFERENCE: SBCCI-94 STANDARD PLUMBING
  
 CODE
 SBCCI-97 STANDARD BUILDING
 CODE
  
 1) SHT S-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A) THE FLOOR DRAINS SHALL HAVE A TRAP
 PER SECTION 409.4.1.2.
 B) WASH MACHINE SHALL NOT DRAIN THROUGH
 THE WET VENT FOR THE BATHROOM FIXTURES.
 SECTION 611.
 C) 3" VENT THROUGH THE TIE BEAM IS NOT
 APPROVED. SECTION 1907.3.6(3). MAXIMUM
 2" INSIDE DIAMETER NOMINAL.
 D) DEAD ENDS NOT APPROVED. SECTION
 311.7.3
 2) FLOOR PLAN SHOWS THE FLOOR DRAIN
 UNDER THE BATH TUB. THE FLOOR DRAIN
 SHALL BE ACCESSIBLE PER SECTION
 409.4.1.2.
 3) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 A SANITARY RISER DIAGRAM THAT REFLECTS
 THE FLOOR PLAN AND MEETS THE CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2001-04-14 Cont ID  
Sent By jleech Date 2001-04-14 Time 06:16 Rev Time 0.33
Received By jleech Date 2001-04-14 Time 06:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2001-03-12 Cont ID  
Sent By jleech Date 2001-03-12 Time 18:48 Rev Time 0.75
Received By jleech Date 2001-03-12 Time 18:48 Sent To  
Notes
2001-03-12 00:00:00DENIED;
  
 RISER DIAGRAM NOT TO CODE. HAVE PLUMBING
 CONTRACTOR DRAW PLUMBING RISER AND LINE
 DRAWING SHOWING HOW PLUMBING WILL BE
 INSTALLED.FLOOR DRAINS MUST HAVE TRAP
 PRIMERS, 3" STACK IS WERE W/M IS THAT
 PIPE BY CODE SHOULD HAVE A CLEAN OUT AT
 48" FROM THE FLOOR. CONTINUEING YOUR
 BUILDING DRAIN DRAIN IS NOT TO CODE.
  
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8377

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-06-07 Cont ID  
Sent By tlarge Date 2000-06-07 Time 20:08 Rev Time 0.33
Received By tlarge Date 2000-06-07 Time 20:08 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 5 Status P Date 2001-12-19 Cont ID  
Sent By rmcdouga Date 2001-12-19 Time 08:54 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-19 00:00:00TRUSSES OK 12-19-01

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status F Date 2001-12-03 Cont ID  
Sent By rmcdouga Date 2001-12-03 Time 10:14 Rev Time 1.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-12-03 00:00:00TRUSSES
 DENIED
  
 1) THE TRUSS LAYOUT MUST HAVE THE WET
 SIGNATURE, DATE AND EMBOSSED SEAL OF THE
 TRUSS ENGINEER. IT ALSO MUST BE REVIEWED
 AND SIGNED BY THE DESIGNER OF RECORD FOR
 THE STRUCTURE.
  
 2) THE TRUSS DRAWINGS MUST HAVE THE
 ORIGIONAL SIGNATURE, DATE AND EMBOSSED
 SEAL ON THEM. SIGNATURE STAMP IS NOT
 ACCEPTABLE.
  
 3) THE DESIGN CRITERIA GIVEN ON THE
 TRUSS DRAWINGS AND TRUSS LAYOUT AS
 ASCE 7-93 IS NOT ACCEPTABLE. TRUSSES
 MUST COMPLY WITH ASCE 7-95 OR 97 SBC
 SECTION 1606.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2001-09-20 Cont ID  
Sent By rmcdouga Date 2001-09-20 Time 16:47 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2001-08-13 Cont ID  
Sent By rmcdouga Date 2001-08-13 Time 13:54 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2001-08-13 00:00:00REVISION OK 8-13-01 RM

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2000-07-05 Cont ID  
Sent By fknapp Date 2000-07-05 Time 10:26 Rev Time 4.00
Received By fknapp Date 2000-06-30 Time 11:12 Sent To  
Notes
2001-01-08 00:00:00 
  
 ****************PROVISO*****************
  
 SBC 104.2.2
  
 1)PROVIDE 2 CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR:
 A)ALL EXTERIOR DOORS AND WINDOWS.
 B)ROOF COVERING UNDER SEPERATE PERMIT.
 C)STORM PANELS FOR ALL NON IMPACT
 GLASS WITH INSTALLATION SCHEDULE AND
 KEY PLAN WITH SPECIFIC ANCHORS USED.
  
 2)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO., THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2001-08-08 Cont ID  
Sent By sgraham Date 2001-08-08 Time 14:34 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By gjoyce Date 2000-06-06 Time 09:36 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2001-01-08 00:00:00ADDTION TO BE 5' FROM S P/L AND 9'6" FRO
 REAR GMJ