Plan Review Details - Permit 00060126
Plan Review Stops For Permit 00060126
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-09-11 Cont ID  
Sent By drunnels Date 2000-09-11 Time 09:54 Rev Time 1.00
Received By drunnels Date 2000-09-11 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By drunnels Date 2000-08-21 Time 16:16 Rev Time 1.00
Received By drunnels Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SUBMIT FIRE SPRINKLER PLANS AND
 PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-08 Cont ID  
Sent By bstaples Date 2000-06-08 Time 15:46 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. SIGNS ARE NOT INCLUDED WITH THIS
 PERMIT.
 2. FIRE SPRINKLER PERMIT REQUIRED, PRIOR
 TO ISSUANCE OF BUILDING PERMIT.
 3. FLORIDA ENERGY SHEETS COMPLY WITH
 1997 FLORIDA ENERGY CODE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-12 Cont ID  
Sent By dpalmer Date 2000-09-12 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2000-09-12 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-08-21 Cont ID  
Sent By dpalmer Date 2000-08-21 Time 20:02 Rev Time 0.00
Received By dpalmer Date 2000-08-21 Time 20:02 Sent To  
Notes
2001-01-08 00:00:00 
 ****************************************
  
 1)NOTE: PLEASE SHOW THE SQ.FT CALCULAT-
 -ION AS PER 220-3-A
  
 2)NOTE: PLEASE SHOW LOAD FOR TRACK LIGHT
 -ING PER 220-12-B
 SHOW LOAD FORWINDOW SPACE PER 220-3-A
  
 3)NOTE: PLEASE SHOW WIRE SIZE FOR PANEL
 (3) ON LINE DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. PLANS WOULD HAVE PASSED WITH
 PROVISOBUT WERE COMING BACK FOR OTHER
 COMMENTS. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372
  
 ALOS PLEASE SEE NOTES TO ART;250-66 OF
 NEC FOR GROUNDING ELECTRODE CONDUCTOR.
 12 1/2 % FOR COMBINED CONDUCTORS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-05 Cont ID  
Sent By dpalmer Date 2000-06-05 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2000-06-05 Time 17:49 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT A LIGHTING PLAN.
 PLEASE SHOW LIGHTING FIXTURE LAYOUT AND
 FIXTURE SCHEDULE GIVING FIXTURE LOCATION
 -S.
  
 2)NOTE:PLEASE SHOW AND/OR INDICATE ALL
 CONTINUOUS LOADS IN LOAD CALCULATIONS,
 LOADS FOR LIGHTING ETC. 3 OR MORE HOURS
 NEEDS TO BE SHOWN AT 125%.
 PLEASE SHOW THE ADDED 25% FOR THE LARGE-
 -ST MOTOR LOADS ON EACH PANEL.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2000-09-19 Cont ID  
Sent By mcarsill Date 2000-09-19 Time 08:56 Rev Time 0.00
Received By mcarsill Date 2000-09-19 Time 08:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-07 Cont ID  
Sent By rturnque Date 2000-06-07 Time 14:47 Rev Time 0.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001) EXIT DOOR LOCATIONS NOT CLEARLY
 SHOWN ON PLANS.
 2) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 3) NO ADDRESS SHOWN ON ELEVATION
 DRAWINGS.
 4) PROVIDE COMPLETE PLANS AND PERMITS
 FOR THE INSTALLATION OF THE HOOD, DUCT
 AND EXTINGUISHING SYSTEMS. SYSTEMS TO
 COMPLY WITH NFPA 96 AND 17A.
 5) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. CUT SHEETS ON DEVICES PLANNED
 FOR USE ARE NEEDED. FIRE ALARM SYSTEM
 IS TO BE AUDIBLE THROUGHOUT THE
 BUILDING WHEN ACTIVATED. WHEN ACTIVATED
 THE HOOD SYSTEM IS TO ACTIVATE THE
 FIRE ALARM SYSTEM.
 6) THE STORAGE OF CARTS ARE NOT TO
 INTERFERE WITH ANY EXIT ACCESS OR
 EXITING.
 7) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 8) LOOSE SEATING IS TO PROVIDE A
 MINIMUM OF 12 INCHES BETWEEN THE BACKS
 OF THE CHAIRS. SEATING SUBJECT TO
 APPROVAL.
 9) TRAVEL DISTANCES TO EXITS SHALL NOT
 EXCEED 150 FEET. TWO EXITS ARE REQUIRED
 FROM BOTH LEVELS.
 10) PORTABLE FIRE EXTINGUISHERS
 REQUIRED THROUGHOUT BUILDING.
 11) AISLES TO BE A MINIMUM OF 36 INCHES
 IN CLEAR WIDTH.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By ndenmark Date 2000-06-06 Time 14:04 Rev Time 1.00
Received By ndenmark Date 2000-06-06 Time 14:04 Sent To  
Notes
2001-01-08 00:00:00--------PROVISO-------------------------
  
 EQUIPMENT ON ROOF SHALL HAVE MINIMUM 18"
 CLEARANCE BETWEEN ROOF SURFACE AND
 BOTTOM OF SUPPORT STRUCTURE OF STAND
  
 SEPARATE PERMITS REQUIRED FOR HOODS,FIRE
 SUPPRESSION SYSTEMS,AND WALK IN COOLER/
 FREEZER. SUBMIT PLANS AT TIME OF PERMIT
 APPLICATION FOR THESE SYSTEMS

Review Stop P PLUMBING
Rev No 6 Status P Date 2000-10-21 Cont ID  
Sent By tlarge Date 2000-10-21 Time 08:05 Rev Time 1.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISE SANITARY AND GREASE.

Review Stop P PLUMBING
Rev No 5 Status P Date 2000-09-19 Cont ID  
Sent By tlarge Date 2000-09-19 Time 09:36 Rev Time 1.00
Received By tlarge Date 2000-09-19 Time 09:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-09-08 Cont ID  
Sent By tlarge Date 2000-09-08 Time 12:42 Rev Time 3.50
Received By tlarge Date 2000-09-08 Time 12:42 Sent To  
Notes
2001-01-08 00:00:001)CALCULATIONS FOR COMBUSTION AIR DO NOT
 COMPLY W/SGC SEC.402.4.4.4.SUBMIT
 REVISED CALCULATIONS.SHOW SIZE OF GRILL
 OPENING TOOUTDOORS FROM THE DUCT.
 ALLOW 60-75% FOR OPEN AREA FOR METAL AND
 20-25% FOR WOOD.
  
 2)SUBMIT DETAIL OF REQUIRED OPENINGS FOR
 COMBUSTION AIR.NOTE IF ONE OR TWO OPEN-
 INGS ARE USED AND COMPLY W/APPLICABLE
 CODE SECS(402.4.4.3 OR 402.4.4.4 OF SGC)
  
 3)THERE IS A CONFLICT BETWEEN THE PLBG.
 PLANS AND THE MECH.PLANS TO THE LOCATION
 OF THE GAS WATER HEATER.CLARIFY THE
 LOCATION FOR COMBUSTION AIR REQS.
  
 4)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY WIDE ORDINANCE.
 THIS IS NOT CLEARLY SHOWN ON THE PLANS.
  
 5)THE DESIGN OF THE GREASY WASTE SYSTEM
 AND THE SANITARY FOR RECEIVING THE
 INDIRECT WASTES SHALL COMPLY W/SPC
 SEC.921 FOR HORIZ.COMBINATION WASTE &
 VENT SYSTEM.
  
 6)SUBMIT SQ.FEET OF HABITABLE FLOOR
 SPACE AND OCCUPANT LOAD TO ENSURE
 COMPLIANCE W/SPC TABLE 407.SEE SPC SEC.
 407.1.3 FOR ALLOWED DEDUCTIBLE AREAS.
  
 7)CONTROL VALVES ARE REQD.ON THE WATER
 BRANCHES INTO THE SPACE PER SPC SEC.
 610.4.2.
  
 8)CONDENSATE DRAINS CANNOT DISCHARGE
 INTO THE ROOF DRAINS.THEY SHALL CONNECT
 TO THE COMMON CONDENSATE SYSTEM.SMC SEC.
 304.8.3.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 12:33 Rev Time 2.00
Received By tlarge Date 2000-08-17 Time 16:37 Sent To  
Notes
2001-01-08 00:00:001)CALCULATIONS FOR COMBUSTION AIR SHALL
 COMPLY W/SGC SECS.402.4.4.1-402.4.4.4.
  
 2)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY PER CITYWIDE ORDINANCE.
  
 3)THE DESIGN OF THE GREASY WASTE SYSTEM
 SHALL COMPLY W/SPC.SEC.921 FOR HORIZ.
 COMBINATION WASTE AND VENT SYSTEM.
  
 4)SHT.P-4. 4"DRAIN SHOWN DRAINING INTO
 3" LINE.(SEE MEAT PREP AREA.SPC SEC.
 307.5,709.1.
  
 5)SUBMIT SQ. FEET OF HABITABLE FLOOR
 SPACE TO ENSURE COMPLIANCE W/TABLE 407
 FOR MINIMUM PLBG.REQS.
  
 6)MAX.TEMP.OF WATER TO SANITARY SHALL BE
 140 DEGREES.SPC SEC.717.8.
  
 7)WATER SUPPLY CONTROL VALVES ARE REQD.
 ON THE BRANCH LINES PER SPC 610.4.2.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-08-08 Cont ID  
Sent By tlarge Date 2000-08-08 Time 10:29 Rev Time 0.50
Received By tlarge Date 2000-08-08 Time 09:55 Sent To  
Notes
2001-01-08 00:00:00PRIMARY STORM DRAINAGE SYSTEM SHALL BE
 DESIGNED PER TABLE 1108.2 OF THE SPC.
 RE:6" ROOF DRAINS AT END OF RUN.
  
 2)PLANS NOTE PIPING TO BE SLOPED AT 3/8"
 PER FT.THIS SLOPE IS NOT LISTED IN TABLE
 1108.2 OF THE SPC.
  
 3)THE LAYOUT OF THE PIPING ON THE PLAN
 SHALL CORRELATE W/THE RISER DIAGRAM.
 COUNTYWIDE AMENDMENT TO SPC SEC.104.2.1.

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-07 Cont ID  
Sent By tlarge Date 2000-06-07 Time 21:44 Rev Time 2.00
Received By tlarge Date 2000-06-07 Time 21:44 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 SHT.A-1-WIDTH OF HANDICAP STALLS SHALL
 COMPLY W/FACBC SEC.4.17.3.PRESENT DESIGN
 DOESN'T COMPLY FOR CLEAR FLOOR SPACE
 REQS.
  
 SUBMIT INFORMATION/DETAILS FOR ROOF
 DRAINAGE.COMPLY W/SPC SEC.1108.1,1108.2.
 INCLUDE INFO FOR SECONDARY DRAINAGE PER
 SPC SEC.1109.
  
 WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1, 615.2.
 SUBMIT MANUF.INFO.
  
 ALL WASTE FROM FLOOR SINKS, FLOOR DRAINS
 HAND SINKS,ETC.IN THE FOOD PREP AND
 SERVING AREA SHALL DISCHARGE THROUGH THE
 GREASE INTERCEPTOR PER SPC SEC.1004.4.
 DISHWASHER SHALL DRAIN TO SANITARY PER
 CITY OF WPB ORDINANCE.
  
 FLOOR SINKS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED AND EXCEED THE ALLOWABLE
 DISTANCE FROM A VENT PER COUNTYWIDE
 AMENDMENTS TO SPC TABLE 908.1.
  
 CLARIFY SLOPE OF PIPE FOR SANITARY AND
 GREASY WASTE.SHTS.P-4 & P-5 NOTE 1/4"
 AND P-1 NOTES 1/8" INCH.COMPLY W/TABLE
 714.1.
  
 SHT.P-4-SHOWS 4" LINE DISCHARGING INTO
 3" LINE.SEE MEAT PREP AREAS.SPC SEC.
 307.5,709.1.
  
 SHT.P-5-DRY VENTS NOT PERMITTED PER SPC
 906.2.1.(SEE CARTS AREA.)
  
 WATER HEATERS SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.SUPPLY PERMANENT
 LADDER OR RELOCATE WATER HEATERS TO
 FLOOR.
  
 PLANS SHOW WATER TEMP.AT 180 DEGREES.
 MAX.TEMP.SHALL BE 140 DEGREES PER SPC
 SEC.717.8.MAX.TEMP. OF WATER TO RESTROOM
 SHALL BE 110 DEGREES PER FL.ENERGY CODE
 SEC.412.1.ABCD.2.3.2.
  
 MAIN SHUTOFF VALVE REQD.ON THE WATER
 SUPPLY PER SPC SEC.610.1.
  
 WATER SUPPLY SYSTEM IS LACKING CONTROL
 VALVES.COMPLY W/SPC SEC.610.4.1.
  
 WATER SUPPLY CONTROL VALVES REQD.ON
 BRANCH LINES PER SPC SEC.610.4.2.
  
 SHT.P-6-CLARIFY INFO ON GAS LEGEND.GAS
 PRESSURE AND PRESSURE DROP IS SHOWN AS
 50" AND SPECIFIC GRAVITY IS SHOWN AS 60"
 COMPLY W/SGC SEC.305.4
  
 SUBMIT CALCULATIONS FOR COMBUSTION AIR
 FOR WATER HEATER.COMPLY W/SGC SEC.402.4.
  
 SUBMIT DETAIL OF GREASE INTERCEPTOR.
 CAPACITY SHALL BE APPROVED BTY CITY OF
 WPB UTILITIES.CONTACT R.COMPO AT 561-
 835 7423.
  
 MEZZANINE TOILET ROOMS-DOORS CANNOT
 SWING INTO CLEAR FLOOR SPACE REQD.FOR
 HANDICAP FIXTURES.COMPLY W/FACBC SEC.
 4.2.3.