| Plan Review Stops For Permit 00060122 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-09-20 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-09-20 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-07-19 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-07-03 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2000-07-03 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************* | | | BUILDING REVIEW | | | ******************* | | | | | | 1]SUBMIT COUNTY IMPACT FEE RECEIPT, | | | REQUIRED WHEN CHANGING OCCUPANCY USE. | | | 2]DOOR D01 IS NOT ACCESSSIBLE,ONE LEAF | | | SHALL PROVIDE 32" CLEAR,SEE 4.13.4 AND | | | 4.13.5,FAC97,DOOR D07 SHALL COMPLY | | | WITH 4.3.8 {MAXIMUM LEVEL CHANGE 1/2"] | | | IS DOOR #D07 3'OR 5' WIDE? | | | 3]WINDOW IN BEDROOM SHALL MEET EMERGENCY | | | EGRESS,SUBMIT PRODUCT TESTING FOR ANY | | | NEW EXTERIOR WINDOWS AND DOORS. | | | | | | | | | | | | BUILDING REVIEW PERFORMED BY; | | | LUIS MARTINEZ 561-659-8096#8456 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-09-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-25 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-25 |
Time |
13:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-09-01 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-09-01 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: NOTES FROM PROVISO ON FIRST | | | REVIEW NOT ADDRESSED. PLEASE DO SO AND | | | RE-SUBMIT FOR REVIEW. | | | | | | PLEASE SUBMIT ALL THE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-06 |
Time |
19:21 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-06 |
Time |
19:21 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | O************* PROVISO ***************** | | | | | | 1)NOTE: PLEASE SUBMIT PLANS WITH ALL | | | BRANCH CIRCUIT #`S SHOWN. 215-5 | | | | | | 2)NOTE: PLEASE DO A RECOUNT ON OUTLETS | | | PER 220-13 | | | | | | 3)NOTE: PLEASE NOTE THAT PANEL SCHEDULE | | | SHOWS MLO, AND RISER DIAGRAM SHOWS MCB? | | | PLEASE CORRELATE. 215-5 | | | | | | 4)NOTE:PLEASE CHECK THE REQ`MENTS OF ART | | | 220-12-B FOR LOAD CALCULATIONS OF TRACK | | | LIGHTING. | | | ALSO PLEASE NOTE 125% FOR CONTINUOUS | | | LOADS (LIGHTING). PLEASE REFIGURE LOAD | | | CALCULATIONS TO REFLECT. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORAMTION | | | FOR REVIEW. PLEASE SUBMIT FOR REVIEW | | | BEFORE ANY ROUGH ELECTRICAL INSPECTION | | | IS CALLED IN. IF THERE ARE ANY QUESTIONS | | | PLEASECALL 659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-06-23 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-06-23 |
Time |
10:57 |
Rev Time |
0.20 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-09-01 |
Time |
10:22 |
Rev Time |
0.25 |
| Received By |
ndenmark |
Date |
2000-09-01 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO: | | | 1. DUCT SMOKE DETECTOR REQUIRED FOR FAN | | | SHUT DOWN | | | 2. NOTIFICATION OF FAN SHUT DOWN REQUIRE | | | PER NFPA 4-4.4 | | | 3.OVERFLOW PROTECTION REQUIRED FOR AHU | | | 4.COND. UNIT TO BE ON SOLID CONCRETE PAD | | | MIN. 3' ABOVE FINISHED GRADE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2000-06-28 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-28 |
Time |
11:03 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-28 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2000-08-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-06 |
Time |
08:36 |
Rev Time |
0.33 |
| Received By |
tlarge |
Date |
2000-08-06 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE | | | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING | | | OR STOOPING. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2000-07-12 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-12 |
Time |
08:54 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-07-12 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ***************PROVISO****************** | | | A DRINKING FOUNTAIN IS REQD.PER SPC SEC. | | | 407.FOUNTAIN SHALL COMPLY W/FACBC SEC. | | | 4.1.3.(10)(A).PROVISIONS SHALL BE MADE | | | FOR PEOPLE WHO HAVE TROUBLE BENDING OR | | | STOOPING. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-06-14 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-14 |
Time |
17:52 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-06-14 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | THIS APPEARS TO BE A CHANGE OF OCCUPANCY | | | FROM R-3 TO B.FULL COMPLIANCE W/FACBC | | | IS REQUIRED PER FACBC SEC.4.1.6.SHOW | | | COMPLIANCE ON PLANS. | | | | | | SINK SHALL COMPLY W/FACBC SEC.4.24.1- | | | 4.24.7. | | | | | | SUBMIT WATER RISER DIAGRAM FOR REVIEW. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | SHOW SQUARE FOOTAGE OF STRUCTURE ON PLAN | | | ADDITIONAL TOILET FACILITIES MAY BE | | | REQUIRED PER SPC TABLE 407. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2000-06-06 |
Time |
09:27 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|