Plan Review Details - Permit 00060121
Plan Review Stops For Permit 00060121
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-09-01 Cont ID  
Sent By bstaples Date 2000-09-01 Time 15:40 Rev Time 1.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISION 8/23/00 NUMBER 4 DENIED FIRE
 AND BUILDING.
 VIOLATION OF CHAPTER 30 SECTION 3003.1
 AND CHAPTER 7, TABLE 705.1.2.
 FIRE RATINGS FOR EXIT AND SHAFT FOR
 ELEVATOR AND ELEVATOR MACHINE ROOM DO
 NOT COMPLY WITH 1997 SBC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2000-08-10 Cont ID  
Sent By drunnels Date 2000-08-10 Time 15:12 Rev Time 1.00
Received By drunnels Date 2000-08-10 Time 15:12 Sent To  
Notes
2001-01-08 00:00:00PREVIOUS COMMENT#4-REF. FHC 4.1.2
 EXCEPTION #3

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-25 Cont ID  
Sent By drunnels Date 2000-07-25 Time 12:56 Rev Time 0.00
Received By drunnels Date 2000-07-25 Time 13:33 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
 1. PROVIDE COMPLETED FLORIDA ENERGY
 SHEETS SIGNED AND SEALED BY DESIGNER
 OF RECORD AS PER FLORIDE STSTUTE.
 2. FIRE SPRINKLER CONTRACTOR MUST SECURE
 PERMIT PRIOR TO ISSURANCE OF THE
 BUILDING PERMIT.
 3. SHOW THAT ESCULATOR COMPLIES WITH
 SECTION 705.2.2 1997 SBC.
 4. DJ BOOTH MUST BE ACCESSABLE AS
 REQUIRED BY THE FLORIDA ACCESSABILITY
 CODE FOR BUILDING CONSTRUCTION CODE
 EDITION 1997.RE DOORS SEE FIGURE 25,
 STAIR RAILING SEE FIGURE 19, DJ BOOTH
 SEE CHAPTER 4.
 6.
  
  
 PROVISO
  
 1.HEALTH DEPARTMENT APPROVAL REQUIRED
 FOR FOOD SERVICE AREA.
 2.SUBMIT EFIS PRODUCT APPROVAL FOR
 WIND LOADS CHAPTER 1606, AND FIRE
 RESISTANCE CHAPTER 26, 1997 SBC
 3.SUBMIT EXTERIOR GLAZING PRODUCT
 APPROVAL INFORMATIOM, COMPLY WITH 1997
 STANDARD BUILDING CODE SSTD 12-97 OR
 METRO DADE COUNTY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-07 Cont ID  
Sent By bstaples Date 2000-06-07 Time 13:28 Rev Time 2.50
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00FIRST REVIEW
 1. PROVIDE COMPLETED FLORIDA ENERGY
 SHEETS SIGNED AND SEAL BY DESIGNER OF
 RECORD AS PER FLORIDA STATUTE.
 2. FIRE SPRINKLER CONTRACTOR MUST
 SECURE PERMIT PRIOR TO ISSUANCE OF THE
 BUILDING PERMIT.
 3. PLANS REQUIRE THE SEAL AND SIGNATURE
 OF A LICENSED FLORIDA ARC OR ENG.
 4. HEALTH DEPARTMNET APPROVAL REQUIRED
 FOR FOOD SERVICE AREA.
 5. SEE FLORIDA ACCESSABILITY CODE FOR
 BUILDING CONSTRUCTION RE DOORS SEE
 FIGURE 25, STAIR RAILINGS SEE FIGURE 19,
 FOR DJ BOOTH SEE CHAPTER 4. DJ BOOTH
 TO ACCESSABLE. CODE EDITION IS 1997.
 6. EIFS, SUBMIT PRODUCT APPROVAL FOR
 WIND LOADS CHAPTER 1606, AND FIRE
 RESISTANCE CHAPTER 26, 1997 STANDARD
 BUILDING CODE.
 7. EXTERIOR GLAZING: PROVIDE PRODUCT
 APPROVAL INFORMATION, COMPLY WITH 1997
 STANDARD BUILDING CODE SSTD 12-97 OR
 METRO DADE COUNTY.
 8. ESCULATOR SHALL COMPLY WITH CHAPTER
 30, 1997 SBC.
 9. EXITING ON SECOND FLOOR SHALL COMPLY
 WITH CHAPTER 10 OF 1997 SBC. REMOTE EXIT
 REQUIRED.
 10. SIGNS ARE NOT COVERED BY THIS
 PERMIT APPLICATION.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2000-08-28 Cont ID  
Sent By dpalmer Date 2000-08-28 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2000-08-28 Time 12:18 Sent To  
Notes
2001-01-08 00:00:00REV FOR ELEC ON FANONLY ON SHEET E 2.02

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2000-08-15 Cont ID  
Sent By dpalmer Date 2000-08-15 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2000-08-15 Time 19:13 Sent To  
Notes
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: PANEL SCHEDULES ON E.02 STILL
 DOES NOT CORRELATE WITH RISER/LINE
 DIAGRAM ON E 2.02
 PLEASE,,,ONE SHOWS THE MCB BEING 1000AMP
 AND THE OTHER SHOWS IT BEING 1200AMP??
 PLEASE MAKE THE NESS. CHANGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN. IF THERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2000-08-07 Cont ID  
Sent By dpalmer Date 2000-08-07 Time 16:38 Rev Time 0.00
Received By dpalmer Date 2000-08-07 Time 16:38 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SEE ALL NOTES FROM OTHER
 REVIEWS.
  
 2)NOTE: PLEASE NOTE THAT RISER SHOWS
 1000MCB AND PANEL SCHEDULE FOR "BDP"
 SHOWS 1200MCB.
 3)NOTE: COLOR CODING OF FEEDERS PER
 LOCAL AMENDMENTS. ART215. FOR 277/480
  
 PLEASE ADDRESS ALL NOTES PREVIOUS AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY QUES
 -TIONS PLEASE CALL.
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2000-07-18 Cont ID  
Sent By dpalmer Date 2000-07-18 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2000-07-18 Time 12:46 Sent To  
Notes
2001-01-08 00:00:00NO E- SHEETS SUBMITTED???/

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-07 Cont ID  
Sent By dpalmer Date 2000-06-07 Time 21:03 Rev Time 0.00
Received By dpalmer Date 2000-06-07 Time 21:03 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE COMPLETE AND SHOW LOAD
 CALCULATIONS ON EACH PANEL.
 ALL CONTIUOUS LOADS (LIGHTING ETC)
 ARE TO SHOWN IN LOAD CALCS AT 125%
  
 2)NOTE: PLEASE SUBMIT AND SHOW THE AIC
 RATINGS FOR EACH PANEL/MAIN DISCONNECT.
 MAINS/PANELS ARE TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT.110-9/215-5
 PLEASE PLACE RATING FOR EACH.
  
 3)NOTE: YOU ARE SHOWING ON YOUR NOTES
 THAT SIMULATORS AND OTHER EQUIPMENT
 LOADS ARE ESTIMATED.? THIS WILL NOT
 BE ACCEPTED. PLEASE FIND OUT LOADS AND
 SUBMIT FOR LOAD CALCULATIONS. 215-5
  
 4)NOTE:PLEASE GIVE BREAKDOWN ON TRACK
 LIGHTING LOAD CALCUALTIONS 220-12-B
  
 5)NOTE: PLEASE SEE 450-21-B PLEASE GIVE
 MORE DETAIL ON ROOM AND /OR CLASS OF
 TRANSFORMER?
  
 6)NOTE: PLEASE SEE THE REQ`MENTS FOR
 GROUNDING ELECTRODE SYSTEM 250-50.
 COLD WATER BOND, AND BONDING GROUNDING
 ELECTRODES TOGETHER PER NEC. 250
  
 7)NOTE: PANEL LOAD ARE TO BE VERIFIED
 UPON COMPLETION OD LOAD CALCULATIONS.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-21 Cont ID  
Sent By mcarsill Date 2000-08-21 Time 10:24 Rev Time 0.00
Received By mcarsill Date 2000-08-21 Time 10:24 Sent To  
Notes
2001-01-08 00:00:001) PLEASE PROVIDE FLAME SPREAD DATA ON
 ROCK CLIMBING WALL.
 2) PLEASE ENSURE THAT A DRAFT STOP AT
 LEAST 18" DEEP IS PROVIDED AT THE
 ESCALATOR OPENING IN ADDITION TO THE
 WATER CURTAIN FIRE SPRINKLER SYSTEM.
 3) ELEVATOR SHAFT AND ELEVATOR EQUIPMENT
 ROOM TO COMPLY WITH UNIFORM FIRE SAFETY
 RULES AND STANDARDS 4A-47.
 4) PROVIDE COMPLETE FIRE ALARM DRAWINGS
 FOR THE FIRE ALARM DEVICES SHOWN ON
 PLANS. A SEPARATE PLAN AND PERMIT IS
 REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-10 Cont ID  
Sent By mcarsill Date 2000-08-10 Time 14:06 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) EXIT SIGN ABOVE ESCALATOR OPENING
 ON SECOND FLOOR APPEARS TO DIRECT
 PERSONS DOWN ESCALATOR. EXIT SIGN IS
 NEEDED NEAR ESCALATOR BUT IT SHOULD
 DIRECT PERSONS AWAY FROM ESCALATOR
 TOWARDS EXIT LOCATIONS.
 2) PROVIDE FIRE ALARM SYSTEM DRAWINGS
 FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS.
 A SEPARATE PERMIT IS REQUIRED.
 3) EXISTING ELEVATOR SHAFT TO BE
 FIRE SPRINKLER PROTECTED.
 4) IF COOKING THAT PRODUCES SMOKE OR
 GREASE LADEN VAPORS IS DONE, THEN A
 HOOD, DUCT AND EXTINGUISHING SYSTEM
 IS REQUIRED. PLANS AND PERMIT REQUIRED.
 5) THIS OFFICE STILL HAS NOT RECEIVED
 FLAME SPREAD INFORMATION ON ROCK
 CLIMBING WALL.
 6) PLEASE INDICATE FLAME SPREAD OF
 INTERIOR FINISHES USED WITHIN THE
 SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2000-06-07 Cont ID  
Sent By rturnque Date 2000-06-07 Time 14:07 Rev Time 1.00
Received By rturnque Date   Time   Sent To  
Notes
2001-01-08 00:00:001) INTERIOR FINISH SHALL BE CLASS A OR
 B.
 2) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER DRAWINGS. A SEPARATE
 PERMIT IS REQUIRED FOR INSTALLTION OF
 THIS SYSTEM.
 3) PROVIDE DETAILS ON CONSTRUCTION OF
 ROCK CLIMBING WALL.
 4) WHAT IS THE ELECTRIC GRILL FOR. ANY
 COOKING THAT PRODUCES SMOKE OR GREASE
 LADEN VAPORS IS TO BE PROTECTED BY A
 HOOD, DUCT AND EXTINGUISHING SYSTEM. A
 SEPARATE PERMIT IS REQUIRED.
 5) EXITS FROM THE SECOND FLOOR NOT
 PROPER. EXITS ARE TO BE SEPARATED FROM
 ONE ANOTHER BY AT LEAST 1/2 OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF
 THE SPACE.
 6) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE FIRE ALARM
 SYSTEM EQUIPMENT. CUT SHEETS NEEDED ON
 ALL DEVICES PLANNED FOR USE.
 7) PORTABLE FIRE EXTINGUISHERS REQUIRED
 THROUGHOUT PREMISES.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2000-08-24 Cont ID  
Sent By ndenmark Date 2000-08-24 Time 13:34 Rev Time 0.33
Received By ndenmark Date 2000-08-24 Time 13:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2000-08-21 Cont ID  
Sent By ndenmark Date 2000-08-21 Time 13:19 Rev Time 0.33
Received By ndenmark Date 2000-08-21 Time 13:19 Sent To  
Notes
2001-01-08 00:00:00****************DENIED******************
 1.FIRE DAMPER LOCATION REQUIRED TO BE
 INDICATED ON PLAN AT ANY REQUIRED LOCA-
 TION 1997 SMC 610
  
  
 3 PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 4. SPECIFY DUCT MATERIAL TO BE USED
 FOR REVIEW OF REQUIRED R- VALUE OF
 INSULATION
 NOTE: DUCT SMOKE DETECTOR TO BE TIED
 TO BUILDING FIRE ALARM OR HORN AND STROB
 FOR NOTIFICATION PER NFPA 90A 4-4.4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2000-08-07 Cont ID  
Sent By cthirben Date 2000-08-07 Time 16:01 Rev Time 1.00
Received By cthirben Date 2000-08-07 Time 15:45 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 REQUIRE DAMPER AT RATED WALLS AND SUBMIT
 DETAIL OF DAMPERS 1997 SMC 610.1.2....
 *PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2...
 *PROVIDE OUTSIDE AIR CALCULATIONS AS PER
 ASHRAE 62-89.
 *REQUIRE A DUCT MATERIAL SCHEDULE AS PER
 FLORIDA ENERGY CODE.
 *GRILLE, DIFFUSERS AND REGISTER SCHEDULE
 TO BE SUBMITTED.
 *PROVIDE DETAIL OF FLEX DUCT CONNECTION.
 *FAN SHUT-DOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION BY FIRE ALARM SYSTEM
 OR TIED-IN TO HORN AND STROBE AS PER
 NFPA 90A 4.4.4.2 AND 4.4.4.3....
 * MINIMUM OF 10' CLEARANCE BETWEEN OUT-
 AIR AND EXHAUST AIR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2000-07-19 Cont ID  
Sent By cthirben Date 2000-07-19 Time 16:15 Rev Time 1.00
Received By cthirben Date 2000-07-19 Time 16:15 Sent To  
Notes
2001-01-08 00:00:00DENIED:
 NO MECHANICAL SUBMITTED WITH THIS REVIEW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By cthirben Date 2000-06-06 Time 14:08 Rev Time 1.00
Received By cthirben Date 2000-06-06 Time 14:02 Sent To  
Notes
2001-01-08 00:00:00*****************DENIED*****************
 1. RAISED SEAL REQUIRED ON PLANS.
 2. PROVIDE OUTSIDE AIR PER ASHRAE 62-89.
 3. AIR BALANCE SCHEDULE PER 1997 SMC
 501.2
 4. ADDITIONAL MECHANICAL PERMIT REQUIRED
 FOR FIRE SUPPRESSION AND HOOD IF
 THESE ARE TO BE INSTALLED IN BUILDING

Review Stop P PLUMBING
Rev No 9 Status P Date 2000-09-23 Cont ID  
Sent By tlarge Date 2000-09-23 Time 11:39 Rev Time 1.00
Received By tlarge Date 2000-09-23 Time 11:39 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
 1)VENTS ON FLOOR DRAINS SHALL COMPLY W/
 SPC SEC.906.2.1.NOTE:VENTS ARE NOT REQD.
 ON THE DRAINS.
  
 2)SHOW PIPE SIZES ON THE WATER RISER
 DIAGRAMS.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 8 Status F Date 2000-09-09 Cont ID  
Sent By tlarge Date 2000-09-09 Time 07:11 Rev Time 1.00
Received By tlarge Date 2000-09-09 Time 06:45 Sent To  
Notes
2001-01-08 00:00:001)SUBMIT ARCHITECTURAL FLOOR PLANS THAT
 SHOW THE CORRECT LAYOUT OF THE FIXTURES
 IN THE HANDICAP STALL IN THE MEN'S
 TOILET ROOM.COUNTYWIDE AMENDMENTS TO SPC
 SEC.102.4.1.
  
 2)AN ADDITIONAL STALL IN THE WOMEN'S
 RESTROOM SHALL COMPLY W/FACBC SEC.4.22.4
 (STALL SHALL BE 36" WIDE W/GRAB BARS ON
 BOTH SIDES AND AN OUTWARD SWINGING DOOR)
  
 3)SUBMIT A REVISED SANITARY AND WATER
 DIAGRAM FOR THE RELOCATED LAV.AND WATER
 CLOSET.
  
 4)SUBMIT A SANITARY AND WATER RISER FOR
 THE NEW PLUMBING WORK ON THE FIRST
 FLOOR.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 5)VACUUM RELIEF INSTALLATION SHALL
 COMPLY W/SPC SEC.507.1.2.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 7 Status P Date 2000-08-31 Cont ID  
Sent By tlarge Date 2000-08-31 Time 19:27 Rev Time 0.50
Received By tlarge Date 2000-08-31 Time 19:27 Sent To  
Notes
2001-01-08 00:00:00******************PROVISO***************
  
 FOR THE SEVENTH TIME!!!!!!!!!!!!!!!!!!!!
 THE SINK IN THE EMPLOYEE LUNCH ROOM
 SHALL COMPLY WITH THE FLORIDA ACCESS-
 IBILITY CODE FOR BUILDING CONSTRUCTION
 SEC.4.24.1- 4.24.7!!

Review Stop P PLUMBING
Rev No 6 Status N Date 2000-08-25 Cont ID  
Sent By tlarge Date 2000-08-25 Time 09:05 Rev Time 0.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00REVISIONS REQD.FOR HANDICAP COMPLIANCE
 AND PLUMBING RISERS.

Review Stop P PLUMBING
Rev No 5 Status F Date 2000-08-24 Cont ID  
Sent By tlarge Date 2000-08-24 Time 15:29 Rev Time 0.65
Received By tlarge Date 2000-08-24 Time 14:08 Sent To  
Notes
2001-01-08 00:00:00COMPLY WITH ALL PREVIOUS COMMENTS.
 FOR THE FIFTH TIME!!!!!!

Review Stop P PLUMBING
Rev No 4 Status F Date 2000-08-18 Cont ID  
Sent By tlarge Date 2000-08-18 Time 10:24 Rev Time 2.00
Received By tlarge Date 2000-08-18 Time 08:14 Sent To  
Notes
2001-01-08 00:00:001)SINK IN LUNCH ROOM SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 2)THE WIDTH OF THE ACCESSIBLE TOILET
 STALL IN THE MEN'S RESTROOM SHALL COMPLY
 W/FACBC SEC.4.17.3.
  
 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR
 ALL HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/ALL APPLICABLE SECTIONS OF THE
 FLA.ACCESSIBILITY CODE.
  
 4)THE SANITARY AND WATER RISER DIAGRAMS
 SHALL CORRELATE W/THE FLOOR PLAN.
  
 5)PRIVACY SCREENS ARE REQD.BETWEEN
 URINALS.SPC SEC.404.3.
  
 6)FLOOR DRAINS ARE REQD.IN THE 1ST FLR.
 TOILET ROOM.(NOT SHOWN ON SAN.RISER.)
 SPC SEC.409.4.1.1.
  
 7)FIXTURE BRANCHES AND WATER CLOSETS ARE
 NOT PERMITTED ON WET VENTS.IF DESIGNING
 FOR A CIRCUIT AND LOOP SYSTEM COMPLY W/
 SPC SEC.914.1
  
 8)NOTE ON THE PLANS THE NUMBER OF
 SEATS IN THE CAFE AREA AND SQUARE FEET
 OF HABITABLE FLOOR SPACE FOR THE TOTAL
 SALES AREA TO ENSURE COMPLIANCE W/SPC
 TABLE 407 FOR MIN.SANITARY REQS..
  
 9)DRINKING FOUNTAINS SHALL NOT REDUCE
 THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE.
 FACBC SEC.4.4.1.
  
 10)WATER RISER MISSING SIZES ON LINES.
 PLEASE ADDRESS THESE AREAS SO THEY CAN
 BE REVIEWED FOR COMPLIANCE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-08-08 Cont ID  
Sent By tlarge Date 2000-08-08 Time 15:27 Rev Time 2.50
Received By tlarge Date 2000-08-08 Time 14:24 Sent To  
Notes
2001-01-08 00:00:001)SINK IN LUNCH ROOM SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7
  
 2)SIZE OF ACCESSIBLE STALL IN MEN'S REST
 ROOM SHALL COMPLY W/FACBC SEC.4.17.3.
 (MIN.SIZE SHALL BE 83" WIDE).
  
 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR
 ALL HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/ALL APPLICABLE SECTIONS OF THE
 FACBC.
  
 4)TWO DRINKING FOUNTAINS ARE REQD.PER
 SPC TABLE 407 OF SPC AND SHALL BE H.C.
 ACCESSIBLE PER FACBC 4.1.3(10)(A).
 DRINKING FOUNTAINS ARE REQD.ON EACH
 FLOOR.
  
 5)SANITARY AND WATER RISER DIAGRAMS
 SHALL CORRELATE W/THE FLOOR PLAN.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 6)INDICATE ON THE PLANS THE TYPE OF
 FOOD ITEMS TO BE SOLD AT THE CAFE.CLEAR-
 LY SHOW THE FOOD PREPARATION AND KITCHEN
 AREAS ON THE PLANS.
  
 7)PARTITIONS ARE REQD.BETWEEN URINALS.
 SPC SEC.404.3.
  
  
 8)FLOOR DRAINS ARE REQD.IN THE 1ST.FLR.
 TOILET ROOMS PER SPC SEC.409.4.1.1.
  
 9)FIXTURE BRANCHES AND WATER CLOSETS NOT
 PERMITTED ON WET VENTS PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.SEE SEC.
 914.1 FOR CIRCUIT AND LOOP VENTING
 SYSTEM.SEE 2ND FLR.TOILET ROOMS.
  
 10)NOTE NUMBER OF SEATS IN THE CAFE AREA
 AND THE HABITABLE FLOOR SPACE FOR THE
 TOTAL SALES AREA TO ENSURE COMPLIANCE W/
 SPC TABLE 407 FOR MIN.SANITARY REQS.
  
 NOTE:THIS IS THE THIRD REVIEW AND THE
 MAJORITY OF THE COMMENTS ARE THE SAME
 FROM THE FIRST REVIEW AND HAVE NOT BEEN
 PROPERLY ADDRESSED OR NOT NOT ADDRESSED
 AT ALL.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-15 Cont ID  
Sent By pschmitz Date 2000-07-15 Time 12:02 Rev Time 1.50
Received By pschmitz Date 2000-07-15 Time 12:02 Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) PLUMBING PLAN REVIEW OF 06-06-2000,
 16 ITEMS SHOWN,11 ADDRESSED 06-27-2000
 COMMENTS
 (2) PLANS NOT SIGNED AND SEALED.
 (3)AREA ON 1ST FLR NOT CLEARLY STATED
 AS A FOOD PREPRATION, SERVING FOOD TO
 PUBLIC,KITCHEN WASTE TO GREASE WASTE.
 (4) SUBMITT 3 SETS OF PLANS TO HOTEL
 BUSINESS REGULATION, FOR THEIR REVIEW.
 CONTACT M'S GIBSON 954-958-5520, PRIOR
 TO PLUMBING PLAN REVIEW.
 (5 ALL ITEMS NEED TO BE ADDRESSED.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By tlarge Date 2000-06-06 Time 09:48 Rev Time 2.50
Received By tlarge Date 2000-06-06 Time 09:48 Sent To  
Notes
2001-01-08 00:00:00SINK IN LUNCH ROOM SHALL COMPLY W/FACBC
 SECS.4.24.1.-4.24.7.
  
 LAVATORIES ARE REQD.WITHIN THE H.C.
 ACCESSIBLE STALLS PER FACBC SEC.4.17.3.
 (SEE EXCEPTION:NEW CONSTRUCTION.)SIZE OF
 HANDICAP STALLS SHALL COMPLY W/4.17.3.
  
 SUBMIT DETAILS/MOUNTING HEIGHTS FOR ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 TWO DRINKING FOUNTAINS ARE REQD.PER
 TABLE 407 OF SPC.AND SHALL BE H.C.ACCES-
 IBLE PER FACBC SEC.4.1.3(10)(A).
 PROVISIONS SHALL BE MADE FOR PEOPLE WHO
 HAVE TROUBLE BENDING OR STOOPING.
  
 WATER HEATER SHALL BE EQUIPPED W/DRAIN
 PAN AND RELIEF DRAIN AND PAN DRAIN SHALL
 DISCHARGE TO EXTERIOR PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.6.
  
 SHT.P3.01-PLUMBING GENERAL NOTES #5-
 DELETE REFERENCE TO MASS.ACCESS BOARD.
 ACCESSIBILITY SHALL BE DESIGNED TO
 STANDARDS PER FLA.DEPT.OF COMMUNITY
 AFFAIRS AND FLA.STATUTE.
  
 A GATE VALVE IS REQD.ON THE INLET TO THE
 WATER HEATER PER SPC SEC.506.1.
  
 OVER 2 FIXTURES ARE SUPPLIED BY 1/2"C.W.
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.607.7.(SEE 2ND. FLR.)
  
 FLAT DRY VENTS NOT PERMITTED PER SPC SEC
 906.2.1.
  
 SANITARY AND WATER RISER DIAGRAMS SHALL
 CORRELATE W/THE FLOOR PLAN.COUNTYWIDE
 AMENDMENTS TO SPC SEC.104.2.1.
  
 INDICATE ON PLANS THE TYPE OF ITEMS TO
 BE SOLD AT THE CAFE.APPROVAL FROM THE
 DEPT. OF BUSINESS REGULATION AND THE
 INSTALLATION OF A GREASE TRAP MAY BE
 REQD.COUNTYWIDE AMENDMENTS TO SPC SEC.
 101.4.7,SPC SEC.1004.4.
  
 CLEANOUTS SHALL BE INSTALLED PER SPC
 710.2.
  
 FLOOR DRAINS SHALL HAVE TRAP PRIMERS
 PER 409.4.1.1.
  
 ALL SHEETS SHALL BEAR THE DATE,SIGNATURE
 AND RAISED SEAL OF THE DESIGN
 PROFESSION OF RECORD PER F.S.481.221,&
 FLA.RULE 61G15-23.002.
  
 SHT.P3.03-DESIGN OF SANITARY SYSTEM
 SHALL COMPLY W/SPC SEC.914.1-914.2.FOR
 A CIRCUIT AND LOOP SYSTYEM.
  
 VENTING OF WATER CLOSETS IN 2ND.FLR.
 TOILET ROOM SHALL COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.3.