| Plan Review Stops For Permit 00060121 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2000-09-01 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-09-01 |
Time |
15:40 |
Rev Time |
1.50 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISION 8/23/00 NUMBER 4 DENIED FIRE | | | AND BUILDING. | | | VIOLATION OF CHAPTER 30 SECTION 3003.1 | | | AND CHAPTER 7, TABLE 705.1.2. | | | FIRE RATINGS FOR EXIT AND SHAFT FOR | | | ELEVATOR AND ELEVATOR MACHINE ROOM DO | | | NOT COMPLY WITH 1997 SBC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-10 |
Time |
15:12 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-10 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PREVIOUS COMMENT#4-REF. FHC 4.1.2 | | | EXCEPTION #3 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-25 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-07-25 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
drunnels |
Date |
2000-07-25 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | 1. PROVIDE COMPLETED FLORIDA ENERGY | | | SHEETS SIGNED AND SEALED BY DESIGNER | | | OF RECORD AS PER FLORIDE STSTUTE. | | | 2. FIRE SPRINKLER CONTRACTOR MUST SECURE | | | PERMIT PRIOR TO ISSURANCE OF THE | | | BUILDING PERMIT. | | | 3. SHOW THAT ESCULATOR COMPLIES WITH | | | SECTION 705.2.2 1997 SBC. | | | 4. DJ BOOTH MUST BE ACCESSABLE AS | | | REQUIRED BY THE FLORIDA ACCESSABILITY | | | CODE FOR BUILDING CONSTRUCTION CODE | | | EDITION 1997.RE DOORS SEE FIGURE 25, | | | STAIR RAILING SEE FIGURE 19, DJ BOOTH | | | SEE CHAPTER 4. | | | 6. | | | | | | | | | PROVISO | | | | | | 1.HEALTH DEPARTMENT APPROVAL REQUIRED | | | FOR FOOD SERVICE AREA. | | | 2.SUBMIT EFIS PRODUCT APPROVAL FOR | | | WIND LOADS CHAPTER 1606, AND FIRE | | | RESISTANCE CHAPTER 26, 1997 SBC | | | 3.SUBMIT EXTERIOR GLAZING PRODUCT | | | APPROVAL INFORMATIOM, COMPLY WITH 1997 | | | STANDARD BUILDING CODE SSTD 12-97 OR | | | METRO DADE COUNTY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-07 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-07 |
Time |
13:28 |
Rev Time |
2.50 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | FIRST REVIEW | | | 1. PROVIDE COMPLETED FLORIDA ENERGY | | | SHEETS SIGNED AND SEAL BY DESIGNER OF | | | RECORD AS PER FLORIDA STATUTE. | | | 2. FIRE SPRINKLER CONTRACTOR MUST | | | SECURE PERMIT PRIOR TO ISSUANCE OF THE | | | BUILDING PERMIT. | | | 3. PLANS REQUIRE THE SEAL AND SIGNATURE | | | OF A LICENSED FLORIDA ARC OR ENG. | | | 4. HEALTH DEPARTMNET APPROVAL REQUIRED | | | FOR FOOD SERVICE AREA. | | | 5. SEE FLORIDA ACCESSABILITY CODE FOR | | | BUILDING CONSTRUCTION RE DOORS SEE | | | FIGURE 25, STAIR RAILINGS SEE FIGURE 19, | | | FOR DJ BOOTH SEE CHAPTER 4. DJ BOOTH | | | TO ACCESSABLE. CODE EDITION IS 1997. | | | 6. EIFS, SUBMIT PRODUCT APPROVAL FOR | | | WIND LOADS CHAPTER 1606, AND FIRE | | | RESISTANCE CHAPTER 26, 1997 STANDARD | | | BUILDING CODE. | | | 7. EXTERIOR GLAZING: PROVIDE PRODUCT | | | APPROVAL INFORMATION, COMPLY WITH 1997 | | | STANDARD BUILDING CODE SSTD 12-97 OR | | | METRO DADE COUNTY. | | | 8. ESCULATOR SHALL COMPLY WITH CHAPTER | | | 30, 1997 SBC. | | | 9. EXITING ON SECOND FLOOR SHALL COMPLY | | | WITH CHAPTER 10 OF 1997 SBC. REMOTE EXIT | | | REQUIRED. | | | 10. SIGNS ARE NOT COVERED BY THIS | | | PERMIT APPLICATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2000-08-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-28 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-28 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REV FOR ELEC ON FANONLY ON SHEET E 2.02 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-15 |
Time |
19:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-15 |
Time |
19:13 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ************** PROVISO ***************** | | | | | | 1)NOTE: PANEL SCHEDULES ON E.02 STILL | | | DOES NOT CORRELATE WITH RISER/LINE | | | DIAGRAM ON E 2.02 | | | PLEASE,,,ONE SHOWS THE MCB BEING 1000AMP | | | AND THE OTHER SHOWS IT BEING 1200AMP?? | | | PLEASE MAKE THE NESS. CHANGES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | | INSPECTION IS CALLED IN. IF THERE ARE | | | ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2000-08-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-07 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-07 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SEE ALL NOTES FROM OTHER | | | REVIEWS. | | | | | | 2)NOTE: PLEASE NOTE THAT RISER SHOWS | | | 1000MCB AND PANEL SCHEDULE FOR "BDP" | | | SHOWS 1200MCB. | | | 3)NOTE: COLOR CODING OF FEEDERS PER | | | LOCAL AMENDMENTS. ART215. FOR 277/480 | | | | | | PLEASE ADDRESS ALL NOTES PREVIOUS AND | | | SUBMIT FOR REVIEW. IF THERE ARE ANY QUES | | | -TIONS PLEASE CALL. | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-18 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-18 |
Time |
12:46 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NO E- SHEETS SUBMITTED???/ |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-07 |
Time |
21:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-06-07 |
Time |
21:03 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE COMPLETE AND SHOW LOAD | | | CALCULATIONS ON EACH PANEL. | | | ALL CONTIUOUS LOADS (LIGHTING ETC) | | | ARE TO SHOWN IN LOAD CALCS AT 125% | | | | | | 2)NOTE: PLEASE SUBMIT AND SHOW THE AIC | | | RATINGS FOR EACH PANEL/MAIN DISCONNECT. | | | MAINS/PANELS ARE TO BE RATED FOR THE | | | AVAILABLE FAULT CURRENT.110-9/215-5 | | | PLEASE PLACE RATING FOR EACH. | | | | | | 3)NOTE: YOU ARE SHOWING ON YOUR NOTES | | | THAT SIMULATORS AND OTHER EQUIPMENT | | | LOADS ARE ESTIMATED.? THIS WILL NOT | | | BE ACCEPTED. PLEASE FIND OUT LOADS AND | | | SUBMIT FOR LOAD CALCULATIONS. 215-5 | | | | | | 4)NOTE:PLEASE GIVE BREAKDOWN ON TRACK | | | LIGHTING LOAD CALCUALTIONS 220-12-B | | | | | | 5)NOTE: PLEASE SEE 450-21-B PLEASE GIVE | | | MORE DETAIL ON ROOM AND /OR CLASS OF | | | TRANSFORMER? | | | | | | 6)NOTE: PLEASE SEE THE REQ`MENTS FOR | | | GROUNDING ELECTRODE SYSTEM 250-50. | | | COLD WATER BOND, AND BONDING GROUNDING | | | ELECTRODES TOGETHER PER NEC. 250 | | | | | | 7)NOTE: PANEL LOAD ARE TO BE VERIFIED | | | UPON COMPLETION OD LOAD CALCULATIONS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-21 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2000-08-21 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE FLAME SPREAD DATA ON | | | ROCK CLIMBING WALL. | | | 2) PLEASE ENSURE THAT A DRAFT STOP AT | | | LEAST 18" DEEP IS PROVIDED AT THE | | | ESCALATOR OPENING IN ADDITION TO THE | | | WATER CURTAIN FIRE SPRINKLER SYSTEM. | | | 3) ELEVATOR SHAFT AND ELEVATOR EQUIPMENT | | | ROOM TO COMPLY WITH UNIFORM FIRE SAFETY | | | RULES AND STANDARDS 4A-47. | | | 4) PROVIDE COMPLETE FIRE ALARM DRAWINGS | | | FOR THE FIRE ALARM DEVICES SHOWN ON | | | PLANS. A SEPARATE PLAN AND PERMIT IS | | | REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-10 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) EXIT SIGN ABOVE ESCALATOR OPENING | | | ON SECOND FLOOR APPEARS TO DIRECT | | | PERSONS DOWN ESCALATOR. EXIT SIGN IS | | | NEEDED NEAR ESCALATOR BUT IT SHOULD | | | DIRECT PERSONS AWAY FROM ESCALATOR | | | TOWARDS EXIT LOCATIONS. | | | 2) PROVIDE FIRE ALARM SYSTEM DRAWINGS | | | FOR FIRE ALARM EQUIPMENT SHOWN ON PLANS. | | | A SEPARATE PERMIT IS REQUIRED. | | | 3) EXISTING ELEVATOR SHAFT TO BE | | | FIRE SPRINKLER PROTECTED. | | | 4) IF COOKING THAT PRODUCES SMOKE OR | | | GREASE LADEN VAPORS IS DONE, THEN A | | | HOOD, DUCT AND EXTINGUISHING SYSTEM | | | IS REQUIRED. PLANS AND PERMIT REQUIRED. | | | 5) THIS OFFICE STILL HAS NOT RECEIVED | | | FLAME SPREAD INFORMATION ON ROCK | | | CLIMBING WALL. | | | 6) PLEASE INDICATE FLAME SPREAD OF | | | INTERIOR FINISHES USED WITHIN THE | | | SPACE. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2000-06-07 |
|
|
Cont ID |
|
| Sent By |
rturnque |
Date |
2000-06-07 |
Time |
14:07 |
Rev Time |
1.00 |
| Received By |
rturnque |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) INTERIOR FINISH SHALL BE CLASS A OR | | | B. | | | 2) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER DRAWINGS. A SEPARATE | | | PERMIT IS REQUIRED FOR INSTALLTION OF | | | THIS SYSTEM. | | | 3) PROVIDE DETAILS ON CONSTRUCTION OF | | | ROCK CLIMBING WALL. | | | 4) WHAT IS THE ELECTRIC GRILL FOR. ANY | | | COOKING THAT PRODUCES SMOKE OR GREASE | | | LADEN VAPORS IS TO BE PROTECTED BY A | | | HOOD, DUCT AND EXTINGUISHING SYSTEM. A | | | SEPARATE PERMIT IS REQUIRED. | | | 5) EXITS FROM THE SECOND FLOOR NOT | | | PROPER. EXITS ARE TO BE SEPARATED FROM | | | ONE ANOTHER BY AT LEAST 1/2 OF THE | | | MAXIMUM OVERALL DIAGONAL DIMENSION OF | | | THE SPACE. | | | 6) PROVIDE COMPLETE SHOP DRAWINGS FOR | | | THE INSTALLATION OF THE FIRE ALARM | | | SYSTEM EQUIPMENT. CUT SHEETS NEEDED ON | | | ALL DEVICES PLANNED FOR USE. | | | 7) PORTABLE FIRE EXTINGUISHERS REQUIRED | | | THROUGHOUT PREMISES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-24 |
Time |
13:34 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-24 |
Time |
13:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2000-08-21 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-08-21 |
Time |
13:19 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2000-08-21 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ****************DENIED****************** | | | 1.FIRE DAMPER LOCATION REQUIRED TO BE | | | INDICATED ON PLAN AT ANY REQUIRED LOCA- | | | TION 1997 SMC 610 | | | | | | | | | 3 PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 4. SPECIFY DUCT MATERIAL TO BE USED | | | FOR REVIEW OF REQUIRED R- VALUE OF | | | INSULATION | | | NOTE: DUCT SMOKE DETECTOR TO BE TIED | | | TO BUILDING FIRE ALARM OR HORN AND STROB | | | FOR NOTIFICATION PER NFPA 90A 4-4.4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2000-08-07 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-07 |
Time |
16:01 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-08-07 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | REQUIRE DAMPER AT RATED WALLS AND SUBMIT | | | DETAIL OF DAMPERS 1997 SMC 610.1.2.... | | | *PROVIDE AIR BALANCE SCHEDULE AS PER | | | 1997 SMC 501.2... | | | *PROVIDE OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | *REQUIRE A DUCT MATERIAL SCHEDULE AS PER | | | FLORIDA ENERGY CODE. | | | *GRILLE, DIFFUSERS AND REGISTER SCHEDULE | | | TO BE SUBMITTED. | | | *PROVIDE DETAIL OF FLEX DUCT CONNECTION. | | | *FAN SHUT-DOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION BY FIRE ALARM SYSTEM | | | OR TIED-IN TO HORN AND STROBE AS PER | | | NFPA 90A 4.4.4.2 AND 4.4.4.3.... | | | * MINIMUM OF 10' CLEARANCE BETWEEN OUT- | | | AIR AND EXHAUST AIR. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-19 |
Time |
16:15 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-07-19 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED: | | | NO MECHANICAL SUBMITTED WITH THIS REVIEW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-06-06 |
Time |
14:08 |
Rev Time |
1.00 |
| Received By |
cthirben |
Date |
2000-06-06 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *****************DENIED***************** | | | 1. RAISED SEAL REQUIRED ON PLANS. | | | 2. PROVIDE OUTSIDE AIR PER ASHRAE 62-89. | | | 3. AIR BALANCE SCHEDULE PER 1997 SMC | | | 501.2 | | | 4. ADDITIONAL MECHANICAL PERMIT REQUIRED | | | FOR FIRE SUPPRESSION AND HOOD IF | | | THESE ARE TO BE INSTALLED IN BUILDING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
P |
Date |
2000-09-23 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-23 |
Time |
11:39 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-09-23 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | 1)VENTS ON FLOOR DRAINS SHALL COMPLY W/ | | | SPC SEC.906.2.1.NOTE:VENTS ARE NOT REQD. | | | ON THE DRAINS. | | | | | | 2)SHOW PIPE SIZES ON THE WATER RISER | | | DIAGRAMS. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
F |
Date |
2000-09-09 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-09-09 |
Time |
07:11 |
Rev Time |
1.00 |
| Received By |
tlarge |
Date |
2000-09-09 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SUBMIT ARCHITECTURAL FLOOR PLANS THAT | | | SHOW THE CORRECT LAYOUT OF THE FIXTURES | | | IN THE HANDICAP STALL IN THE MEN'S | | | TOILET ROOM.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.102.4.1. | | | | | | 2)AN ADDITIONAL STALL IN THE WOMEN'S | | | RESTROOM SHALL COMPLY W/FACBC SEC.4.22.4 | | | (STALL SHALL BE 36" WIDE W/GRAB BARS ON | | | BOTH SIDES AND AN OUTWARD SWINGING DOOR) | | | | | | 3)SUBMIT A REVISED SANITARY AND WATER | | | DIAGRAM FOR THE RELOCATED LAV.AND WATER | | | CLOSET. | | | | | | 4)SUBMIT A SANITARY AND WATER RISER FOR | | | THE NEW PLUMBING WORK ON THE FIRST | | | FLOOR.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | 5)VACUUM RELIEF INSTALLATION SHALL | | | COMPLY W/SPC SEC.507.1.2. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2000-08-31 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-31 |
Time |
19:27 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
2000-08-31 |
Time |
19:27 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | | | | FOR THE SEVENTH TIME!!!!!!!!!!!!!!!!!!!! | | | THE SINK IN THE EMPLOYEE LUNCH ROOM | | | SHALL COMPLY WITH THE FLORIDA ACCESS- | | | IBILITY CODE FOR BUILDING CONSTRUCTION | | | SEC.4.24.1- 4.24.7!! |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
N |
Date |
2000-08-25 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-25 |
Time |
09:05 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | REVISIONS REQD.FOR HANDICAP COMPLIANCE | | | AND PLUMBING RISERS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2000-08-24 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-24 |
Time |
15:29 |
Rev Time |
0.65 |
| Received By |
tlarge |
Date |
2000-08-24 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | COMPLY WITH ALL PREVIOUS COMMENTS. | | | FOR THE FIFTH TIME!!!!!! |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2000-08-18 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-18 |
Time |
10:24 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-08-18 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SINK IN LUNCH ROOM SHALL COMPLY W/ | | | FACBC SECS.4.24.1-4.24.7. | | | | | | 2)THE WIDTH OF THE ACCESSIBLE TOILET | | | STALL IN THE MEN'S RESTROOM SHALL COMPLY | | | W/FACBC SEC.4.17.3. | | | | | | 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR | | | ALL HANDICAP FIXTURES AND APPURTENANCES. | | | COMPLY W/ALL APPLICABLE SECTIONS OF THE | | | FLA.ACCESSIBILITY CODE. | | | | | | 4)THE SANITARY AND WATER RISER DIAGRAMS | | | SHALL CORRELATE W/THE FLOOR PLAN. | | | | | | 5)PRIVACY SCREENS ARE REQD.BETWEEN | | | URINALS.SPC SEC.404.3. | | | | | | 6)FLOOR DRAINS ARE REQD.IN THE 1ST FLR. | | | TOILET ROOM.(NOT SHOWN ON SAN.RISER.) | | | SPC SEC.409.4.1.1. | | | | | | 7)FIXTURE BRANCHES AND WATER CLOSETS ARE | | | NOT PERMITTED ON WET VENTS.IF DESIGNING | | | FOR A CIRCUIT AND LOOP SYSTEM COMPLY W/ | | | SPC SEC.914.1 | | | | | | 8)NOTE ON THE PLANS THE NUMBER OF | | | SEATS IN THE CAFE AREA AND SQUARE FEET | | | OF HABITABLE FLOOR SPACE FOR THE TOTAL | | | SALES AREA TO ENSURE COMPLIANCE W/SPC | | | TABLE 407 FOR MIN.SANITARY REQS.. | | | | | | 9)DRINKING FOUNTAINS SHALL NOT REDUCE | | | THE CLEAR WIDTH OF AN ACCESSIBLE ROUTE. | | | FACBC SEC.4.4.1. | | | | | | 10)WATER RISER MISSING SIZES ON LINES. | | | PLEASE ADDRESS THESE AREAS SO THEY CAN | | | BE REVIEWED FOR COMPLIANCE. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-08-08 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-08-08 |
Time |
15:27 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-08-08 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1)SINK IN LUNCH ROOM SHALL COMPLY W/ | | | FACBC SECS.4.24.1-4.24.7 | | | | | | 2)SIZE OF ACCESSIBLE STALL IN MEN'S REST | | | ROOM SHALL COMPLY W/FACBC SEC.4.17.3. | | | (MIN.SIZE SHALL BE 83" WIDE). | | | | | | 3)SUBMIT DETAILS/MOUNTING HEIGHTS FOR | | | ALL HANDICAP FIXTURES AND APPURTENANCES. | | | COMPLY W/ALL APPLICABLE SECTIONS OF THE | | | FACBC. | | | | | | 4)TWO DRINKING FOUNTAINS ARE REQD.PER | | | SPC TABLE 407 OF SPC AND SHALL BE H.C. | | | ACCESSIBLE PER FACBC 4.1.3(10)(A). | | | DRINKING FOUNTAINS ARE REQD.ON EACH | | | FLOOR. | | | | | | 5)SANITARY AND WATER RISER DIAGRAMS | | | SHALL CORRELATE W/THE FLOOR PLAN.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.104.2.1. | | | | | | 6)INDICATE ON THE PLANS THE TYPE OF | | | FOOD ITEMS TO BE SOLD AT THE CAFE.CLEAR- | | | LY SHOW THE FOOD PREPARATION AND KITCHEN | | | AREAS ON THE PLANS. | | | | | | 7)PARTITIONS ARE REQD.BETWEEN URINALS. | | | SPC SEC.404.3. | | | | | | | | | 8)FLOOR DRAINS ARE REQD.IN THE 1ST.FLR. | | | TOILET ROOMS PER SPC SEC.409.4.1.1. | | | | | | 9)FIXTURE BRANCHES AND WATER CLOSETS NOT | | | PERMITTED ON WET VENTS PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1.SEE SEC. | | | 914.1 FOR CIRCUIT AND LOOP VENTING | | | SYSTEM.SEE 2ND FLR.TOILET ROOMS. | | | | | | 10)NOTE NUMBER OF SEATS IN THE CAFE AREA | | | AND THE HABITABLE FLOOR SPACE FOR THE | | | TOTAL SALES AREA TO ENSURE COMPLIANCE W/ | | | SPC TABLE 407 FOR MIN.SANITARY REQS. | | | | | | NOTE:THIS IS THE THIRD REVIEW AND THE | | | MAJORITY OF THE COMMENTS ARE THE SAME | | | FROM THE FIRST REVIEW AND HAVE NOT BEEN | | | PROPERLY ADDRESSED OR NOT NOT ADDRESSED | | | AT ALL. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-07-15 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-15 |
Time |
12:02 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
2000-07-15 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) PLUMBING PLAN REVIEW OF 06-06-2000, | | | 16 ITEMS SHOWN,11 ADDRESSED 06-27-2000 | | | COMMENTS | | | (2) PLANS NOT SIGNED AND SEALED. | | | (3)AREA ON 1ST FLR NOT CLEARLY STATED | | | AS A FOOD PREPRATION, SERVING FOOD TO | | | PUBLIC,KITCHEN WASTE TO GREASE WASTE. | | | (4) SUBMITT 3 SETS OF PLANS TO HOTEL | | | BUSINESS REGULATION, FOR THEIR REVIEW. | | | CONTACT M'S GIBSON 954-958-5520, PRIOR | | | TO PLUMBING PLAN REVIEW. | | | (5 ALL ITEMS NEED TO BE ADDRESSED. | | | END OF COMMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-06 |
Time |
09:48 |
Rev Time |
2.50 |
| Received By |
tlarge |
Date |
2000-06-06 |
Time |
09:48 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SINK IN LUNCH ROOM SHALL COMPLY W/FACBC | | | SECS.4.24.1.-4.24.7. | | | | | | LAVATORIES ARE REQD.WITHIN THE H.C. | | | ACCESSIBLE STALLS PER FACBC SEC.4.17.3. | | | (SEE EXCEPTION:NEW CONSTRUCTION.)SIZE OF | | | HANDICAP STALLS SHALL COMPLY W/4.17.3. | | | | | | SUBMIT DETAILS/MOUNTING HEIGHTS FOR ALL | | | HANDICAP FIXTURES AND APPURTENANCES. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | TWO DRINKING FOUNTAINS ARE REQD.PER | | | TABLE 407 OF SPC.AND SHALL BE H.C.ACCES- | | | IBLE PER FACBC SEC.4.1.3(10)(A). | | | PROVISIONS SHALL BE MADE FOR PEOPLE WHO | | | HAVE TROUBLE BENDING OR STOOPING. | | | | | | WATER HEATER SHALL BE EQUIPPED W/DRAIN | | | PAN AND RELIEF DRAIN AND PAN DRAIN SHALL | | | DISCHARGE TO EXTERIOR PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.507.6. | | | | | | SHT.P3.01-PLUMBING GENERAL NOTES #5- | | | DELETE REFERENCE TO MASS.ACCESS BOARD. | | | ACCESSIBILITY SHALL BE DESIGNED TO | | | STANDARDS PER FLA.DEPT.OF COMMUNITY | | | AFFAIRS AND FLA.STATUTE. | | | | | | A GATE VALVE IS REQD.ON THE INLET TO THE | | | WATER HEATER PER SPC SEC.506.1. | | | | | | OVER 2 FIXTURES ARE SUPPLIED BY 1/2"C.W. | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.607.7.(SEE 2ND. FLR.) | | | | | | FLAT DRY VENTS NOT PERMITTED PER SPC SEC | | | 906.2.1. | | | | | | SANITARY AND WATER RISER DIAGRAMS SHALL | | | CORRELATE W/THE FLOOR PLAN.COUNTYWIDE | | | AMENDMENTS TO SPC SEC.104.2.1. | | | | | | INDICATE ON PLANS THE TYPE OF ITEMS TO | | | BE SOLD AT THE CAFE.APPROVAL FROM THE | | | DEPT. OF BUSINESS REGULATION AND THE | | | INSTALLATION OF A GREASE TRAP MAY BE | | | REQD.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 101.4.7,SPC SEC.1004.4. | | | | | | CLEANOUTS SHALL BE INSTALLED PER SPC | | | 710.2. | | | | | | FLOOR DRAINS SHALL HAVE TRAP PRIMERS | | | PER 409.4.1.1. | | | | | | ALL SHEETS SHALL BEAR THE DATE,SIGNATURE | | | AND RAISED SEAL OF THE DESIGN | | | PROFESSION OF RECORD PER F.S.481.221,& | | | FLA.RULE 61G15-23.002. | | | | | | SHT.P3.03-DESIGN OF SANITARY SYSTEM | | | SHALL COMPLY W/SPC SEC.914.1-914.2.FOR | | | A CIRCUIT AND LOOP SYSTYEM. | | | | | | VENTING OF WATER CLOSETS IN 2ND.FLR. | | | TOILET ROOM SHALL COMPLY W/COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.3. |
|
|