Plan Review Details - Permit 00060037
Plan Review Stops For Permit 00060037
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-03 Cont ID  
Sent By hpiskura Date 2000-07-03 Time 14:26 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-08-29 Cont ID  
Sent By dpalmer Date 2000-08-29 Time 19:36 Rev Time 0.00
Received By dpalmer Date 2000-08-29 Time 19:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-22 Cont ID  
Sent By dpalmer Date 2000-06-22 Time 19:00 Rev Time 0.00
Received By dpalmer Date 2000-06-22 Time 19:00 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AND PROVIDE PANEL
 SCHEDULES FOR EXISTING PANELS WITH ALL
 BRANCH CIRCUITS SHOWN.
  
 2)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS
 INCLUDING ALL NEW EQUIPMENT LOADS AND
 ALL EXISTING LOADS.215-5
 LOADS FOR CONTINUOUS LOADS TO BE FIGURED
 AT 125%. PLEASE SHOW.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-09 Cont ID  
Sent By rturnque Date 2000-06-09 Time 10:55 Rev Time 0.30
Received By rturnque Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-08-30 Cont ID  
Sent By ndenmark Date 2000-08-30 Time 14:31 Rev Time 1.00
Received By ndenmark Date 2000-08-30 Time 14:31 Sent To  
Notes
2001-01-08 00:00:00PREVIOUS COMMENTS ADDRESSED SATISFACTOR-
 ILY. SEE REVISION 8/2/00 AND STANDROD
 ENGINEERING COMMENT SHEETS DATED 7/17/00
 (8/02/00) SIGNED MARCUS STANDROD P.E.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-26 Cont ID  
Sent By ndenmark Date 2000-06-26 Time 10:12 Rev Time 1.00
Received By ndenmark Date 2000-06-26 Time 10:12 Sent To  
Notes
2001-01-08 00:00:00***********DENIED**********************
  
 1. 1997 SMC 509.9.2 REQUIRES THE GREASE
 EXHAUST DUCT TO BE ENCLOSED BY AN ENCL-
 OSURE EXCLUSIVELY FOR THE GREASE EXHAUST
 DUCT AND SHALL BE USED FOR NO OTHER PUR-
 POSE. K-5 SHOWS MAKE UP AIR DUCT IN WITH
 GREASE EXHAUST DUCT.
 2. 1997 SMC 304.2.5 (MODEL COUNTYWIDE
 AMENDMENTS AS ADOPTED BY THE CITY OF
 WEST PALM BEACH) REQUIRES MIN. 18" OF
 CLEARANCE UNDER MECHANICAL EQUIPMENT ON
 ROOF. MEASURE FROM BOTTOM OF SUPPORT
 STRUCTURE TO FINISH SURFACE OF ROOF.
 3. EXHAUST FAN TERMINATION ABOVE ROOF IS
 FROM THE EXHAUST OUTLET OF THE FAN
 4. STATE OF FLORIDA ENERGY EFFICIENCY
 CODE PROHIBITS CONDENSING UNITS FROM
 BEING PLACED IN THE COOL AIR STREAM OF
 ANOTHER UNIT. WHERE ARE WALK- IN COOLER
 FREEZER CONDENSING UNITS?
 5. PROVIDE ROOF TOP PLAN SHOWING PLACE-
 MENT OF EQUIPMENT FOR REVIEW PURPOSES
 6. PROVIDE OUTSIDE AIR CALCULATIONS PER
 ASHRAE 62-89
 7. SEPARATE PERMIT REQUIRED FOR KITCHEN
 HOOD. PROVIDE PLANS FOR HOODS,DUCT, FANS
 ETC. AT TIME OF MECHANICAL PERMIT APPL
 FOR HOODS
 8. SEPARATE PERMITS REQUIRED FOR WALK IN
 COOLERS/ FREEZERS. PROVIDE PLANS AT TIME
 OF PERMIT APPLICATION
 9. PROVIDE DETAILS ONSOURCE OF TEMPER-
 ED AIR TO BE SUPPLIED TO HOOD FROM MC
 AS SHOWN ON PLAN (M-4)

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-10-26 Cont ID  
Sent By tlarge Date 2000-10-26 Time 09:26 Rev Time 0.75
Received By tlarge Date 2000-10-26 Time 09:20 Sent To  
Notes
2001-01-08 00:00:001)INDIRECT WASTES SHALL DISCHARGE INTO A
 FLOOR SINK PER SPC SEC.804.1
  
 2)SYSTEM OF FLOOR DRAINS AND FLOOR SINKS
 SHALL BE INSTALLED ON A HORIZONTAL
 COMBINATION WASTE AND VENT SYSTEM PER
 SPC SEC.921.4.AS DESIGNED FIXTURES ARE
 NOT PROPERLY VENTED.
  
 3)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY ORDINANCE.
  
 4)SUBMIT WATER RISER DIAGRAM FOR ALL NEW
 WORK.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 5)SIZE VENT FOR NEW HAND SINK.COMPLY W/
 SPC TABLE 920.2.
  
 6)SUBMIT MANUF.DATA ON PROVENT.SPC 303.1
 303.5.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-08-21 Cont ID  
Sent By tlarge Date 2000-08-21 Time 15:38 Rev Time 0.33
Received By tlarge Date 2000-08-21 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-07-05 Cont ID  
Sent By tlarge Date 2000-07-05 Time 08:16 Rev Time 0.75
Received By tlarge Date 2000-07-05 Time 06:55 Sent To  
Notes
2001-01-08 00:00:00SUBMIT COMPLETE PLUMBING AND GAS DRAWING
 FOR ALL WORK TO BE PERFORMED UNDER THIS
 PERMIT.COUNTYWIDE AMENDMENTS 104.2.1.
  
 SUBMIT MANUF.SHEETS FOR ANY NEW GAS
 EQUIPMENT TO BE INSTALLED.SGC SEC.402.1