| Plan Review Stops For Permit 00051840 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-08-15 |
Time |
12:50 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PRIVSO: | | | ALL EXTERIOR GLAZING WINDOWS AND DOORS | | | PROVIDE PRODUCT APPROVAL FOR WIND LOADS | | | 1997 SBC 110 MPH CHAPTER 16 AND IMPACT | | | PROTECTION AS PER SSTD 12-97 SBC OR | | | METRO DADE COUNTY. | | | APPLY FOR AND PAY FEES UNDER SEPERATE | | | PERMIT FOR GLAZING SYSTEM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-08-14 |
Time |
13:43 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-08-14 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | 1.PROVIDE FLORIDA ENERGY SHEETS SIGNED | | | BY OWNER/AGENT AND SIGNED AND SEALED BY | | | ENG. | | | 2. PROVIDE CURRENT COPIES OF SBCCI OR | | | METRO DADE COUNTY PRODUCT APPROVALS FOR | | | WINDOWS. | | | 3.PROVIDE WIND LOAD CALUCLATIONS THAT | | | COMPLY WITH 1997 BSC CHAPTER 16 FOR | | | STROEFRONT. | | | 4. FIRE RATING OF WALL ASSEMBLIES NOT | | | INDICATED, PROVIDE UL LISTING, SEE TABLE | | | 704.1 1997 SBC ASSEMBLEY TO OTHER | | | OCCUPANCIES, 1ST & 2ND FLOORS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2000-07-27 |
|
|
Cont ID |
|
| Sent By |
drunnels |
Date |
2000-07-27 |
Time |
11:32 |
Rev Time |
1.00 |
| Received By |
drunnels |
Date |
2000-07-27 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | | | | | | | | | | | | | 1. SUBMIT PLANS SHOWING THAT MEZZANIE | | | COMPLIES WITH 1997 SBC CHAPTER 5 | | | SECTION 505.2.3, & CHAPTER 10 SECTION | | | 1004.1.5, 1005.7, 1007.8 AND THE | | | 1997 FLORIDA HANDICAP CODE | | | 2. PROVIDE FLORIDA ENERGY CODE SHEETS | | | SIGNED BY THE OWNER. | | | 3. PROVIDE CURRENT COPIES OF SBCCI OR | | | METRO DADE COUNTY PRODUCT APPROVALS | | | FOR WINDOWS | | | 4. PROVIDE WIND LOAD CALUCLATIONS THAT | | | COMPLY WITH 1997 SBC CHAPTER 16 FOR | | | STOREFRONT. | | | 5. FIRE RATING OF WALL ASSEMBLIES NOT | | | INDICATED, PROVIDE LISTING, SEE TABLE | | | 704.1 1997 SBC, SMALL ASSEMBLEY TO | | | OTHER OCCUPANCIES.1ST & 2ND FLOOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
fknapp |
Date |
2000-07-19 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
fknapp |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | | | | **************REVIEW NOTES************** | | | | | | | | | 1)PROVIDE RAISE SEAL OF ENGINEER THAT | | | PREPARED ENERGY SHEETS. | | | | | | 2)FIRE SPRINKLER CONTRACTOR TO APPLY FOR | | | PERMIT PRIOR TO ISSUANCE BUILDING PERMIT | | | | | | | | | 3)PROVIDE WINDLOAD CALCULATIONS THAT | | | COMPLY WITH 1997 SBC CHAPTER 16 FOR | | | STORE FRONT. | | | | | | 4)PROVIDE CURRENT COPIES OF SBCCI OR | | | METRO DADE PRODUCT APPROVALS FOR WINDOWS | | | | | | 5)FABRIC TERRACE REQUIRES SEPARATE | | | PERMIT. | | | | | | 6)SIGNS REQUIRE SEPARATE PERMITS. | | | | | | 7)FIRE RATINGS OF WALL ASSEMBLIES NOT | | | INDICATED, PROVIDE LISTING, SEE TABLE | | | 704.1 1997 SBC SMALL ASSEMBLEY TO OTHER | | | OCCUPANCIES. FIRST AND SECOND FLOOR. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-29 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-29 |
Time |
13:31 |
Rev Time |
2.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1. FLORIDA ENERGY SHEETS SHOW COMPLIANCE | | | WITH 1997 FLORIDA ENERGY CODE. | | | 2. FIRE SPRINKLER PALNS AND CONTRACTOR | | | TO APPLY FOR PERMIT PRIOR TO ISSUANCE OF | | | THE BUILDING PERMIT. | | | 3. STORE FRONT, PROVIDE STRUCTURAL | | | DETAILS FOR STORE FRONT MEET 1997 SBC | | | CHAPTER 16. | | | 4. WINDOWS SHEET A3.1 PROVIDE PRODUCT | | | APPROVAL INFORMATION MEET SSTD12-97 OR | | | METRO DADE COUNTY. | | | 5. FABRIC TERRACE REQUIRES SEPERATE | | | PERMIT. | | | 6. SIGNS REQUIRE SEPERATE PERMITS. | | | 7. FIRE RATINGS OF WALL ASSEMBLIES NOT | | | INDICATED PROVIDE LISTING SEE TABLE | | | 704.1, 1997 SBC SMALL ASSEMBLEY TO | | | OTHER OCCUPANCIES. FIRST AND SECOND | | | FLOOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-08-14 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-08-14 |
Time |
12:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-07-19 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2000-07-19 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2000-06-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2000-06-05 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2000-08-18 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS OF ALL | | | MAIN DISCONNECTS/PANELS. MAINS/PANELS | | | MUST BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. 110-9/215-5 | | | | | | 2)NOTE: PLEASE NOTE YOU ARE SHOWING A | | | 150KVA TRANSFORMER WITH 150C TEMP RISE. | | | PLEASE SEE ART;450-21-B EXCEPT. #1 | | | MUST HAVE TEMP RISE 155 C. | | | PLEASE ADJUST OR TRANSFORMER MUST BE | | | INSTALLED IN TRANSFORMER VAULT/ROOM | | | UNDER NEC. REQ`MENTS. | | | | | | 3)NOTE: YOU SHOW PANEL "HVPP" ON SHEET | | | E-6. PLEASE INCLUDE THIS ON THE ONE-LINE | | | RISER DIAGRAM. 215-5 | | | | | | 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS! | | | LOAD CALCULATIONS TO MEET REQ`MENTS OF | | | THE NEC. ALSO PLEASE INCLUDE ALL LOADS | | | THAT MAY BE CONTINUOUS. (LIGHTING ETC) | | | PLEASE SUBMIT THE BREAK DOWN ON EACH | | | PANEL AND TOTAL LOAD ON MAIN LVMDP. | | | PLEASE SUBMIT THE LOAD CALCULATION FOR | | | PANEL "HVPP". SHOW BREAK DOWN ON LOADS | | | AND SHOW LOADS OF EQUIPMENT. | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW.IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2000-08-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-15 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) HANDRAILS AND GUARDS TO COMPLY WITH | | | NFPA 101, LIFE SAFETY CODE, 1985 EDITION | | | 2) SUBMIT COMPLETE FIRE ALARM SYSTEM | | | SHOP DRAWINGS FORT FIRE ALARM EQUIPMENT | | | SHOWN ON PLANS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2000-08-09 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2000-08-09 |
Time |
17:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | 1) ALL FABRIC AWNINGS ARE TO BE FLAME | | | RETARDANT. | | | 2) HYDRAULIC CALCULATION SUMMARY IS NOT | | | CORRECT. WHERE DID THESE FIGURES COME | | | FROM. | | | 3) GAS INSTALLATION TO COMPLY WITH | | | NFPA 54. | | | 4) PROVIDE FIRE ALARM SYSTEM DRAWINGS | | | FOR FIRE ALARM SYSTEM EQUIPMENT SHOWN | | | ON PLANS. A SEPARATE PLAN AND PERMIT | | | REQUIRED. | | | 5) OCCUPANT LOAD TO BE DETERMINED BY | | | THIS OFFICE. | | | 6) PORTABLE FIRE EXTINGUISHERS REQUIRED. | | | 7) PROVIDE COMPLETE HOOD, DUCT, AND | | | EXTINGUISHING PLANS. A SEPARATE PERMIT | | | IS REQUIRED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2000-06-29 |
|
|
Cont ID |
|
| Sent By |
bstaples |
Date |
2000-06-29 |
Time |
12:46 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PROVISO ATTACHED TO PLANS M. CARSILLO |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-08-14 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-08-14 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | SEPERATE PERMIT REQUIRED FOR HOODS, WALK | | | -IN COOLERS/FREEZERS AND SUPPRESSION | | | SYSTEM. SUBMIT PLANS AT TIME OF PERMIT | | | APPLICATION FOR THESE SYSTEM.... |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2000-07-18 |
|
|
Cont ID |
|
| Sent By |
cthirben |
Date |
2000-07-18 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
cthirben |
Date |
2000-07-18 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | NOTES: | | | COMMENTS ON REVIEW DATED 06.05.00 DONE | | | BY NCD HAS BEEN ADDRESSED ON THIS REVIEW | | | ***SEPERATE PERMITS REQUIRED FOR HOODS, | | | WALK-IN COOLERS/FREEZERS AND FIRE SUPPR- | | | ESSION SYSTEMS. SUBMIT PLANS AT TIME OF | | | PERMIT APPLICATION FOR THESE SYSTEMS. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-05 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2000-06-05 |
Time |
15:30 |
Rev Time |
1.00 |
| Received By |
bstaples |
Date |
2000-06-05 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | **************DENIED******************* | | | | | | 1) OUTSIDE AIR REQUIRED PER ASHRAE 62-89 | | | 2) PROVIDE AIR BALANCE SCHEDULE PER 1997 | | | 501.2 | | | 3) SPECIFY MATERIALS FOR AIR DUCTS | | | 4) DUCT SMOKE DETECTORS TO BE TIED TO | | | BUILDING FIRE ALARM SYSTEM PER NFPA 90A | | | 5) EQUIPMENT ON ROOF TO PROVIDE MIN. | | | CLEARANCE OF 18" BETWEEN SURFACE OF ROOF | | | AND BOTTOM OF SUPPORT STRUCTURE OF STAND | | | FOR ROOF ACCESS UNDER EQUIPMENT PER | | | LOCAL ORDINANCE | | | 6) SEPERATE PERMITS REQUIRED FOR HOODS, | | | WALKIN COOLERS/FREEZERS, AND SUPPRESSION | | | SYSTEMS. SUBMIT PLANS AT TIME OF PERMIT | | | APPLICATION FOR THESE SYSTEMS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2000-08-14 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-08-14 |
Time |
06:12 |
Rev Time |
3.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEWPROVISO: | | | REF SPC 94, SGC 97 | | | (1) | | | | | | | | | | | | | | | (2) SHT P-5 ANSUL VALVE FA TO BE | | | INSTALLED BELOW CEILING. | | | (3) SHT M-3 ALL A/C CONDENSATE DRAINS, | | | TO BE CONNECTED TO COMMON SYSTEM, | | | PROVIDED B/O. | | | END OF COMMENTS ANY QUESTIONS | | | CONTACT PAUL SCHMITZ 561-659-8096 X 8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2000-07-28 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-07-28 |
Time |
19:42 |
Rev Time |
2.00 |
| Received By |
tlarge |
Date |
2000-07-28 |
Time |
18:32 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLANS SHALL BE ROUTED TO DEPT.OF | | | BUSINESS REGULATION FOR REVIEW AND | | | APPROVAL.SUBMIT APPROVAL DOCUMENTATION | | | FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC | | | SEC.101.4.7. | | | | | | ALL FLOOR SINKS ,HAND SINKS,FLOOR DRAINS | | | ETC.IN THE FOOD PREP/KITCHEN/BAR AREAS | | | SHALL DISCHARGE THRU THE GREASY WASTE | | | SYSTEM EXCEPT THE DISHWASHER AND THE | | | FOOD WASTE GRINDER.SPC 1004.4. | | | | | | THE GAS MANIFOLD AT THE METER SHALL | | | COMPLY W/NFPA 54 FOR DISTANCE FROM | | | SOURCE OF IGNITION.THIS WILL BE SUBJECT | | | TO FIELD INSPECTION AND IF FOUND TO BE | | | IN VIOLATION SHALL BE RELOCATED.THIS | | | ISSUE WAS ADDRESSED ON THE SHELL | | | BUILDING AND REQUIRES COMPLIANCE. | | | | | | A SIGNED,SEALED AND DATED SANITARY AND | | | WATER ISOMETRIC DRAWING SHALL BE | | | SUBMITTED FOR REVIEW PRIOR TO PLUMBING | | | INSPECTION.THE DRAWINGS SHALL CORRELATE | | | WITH THE FLOOR PLANS AND COMPLY W/SPC | | | FOR DESIGN IN ALL RESPECTS.THERE ARE | | | TOO MANY VIOLATIONS OF THE CODE TO LIST. | | | SEE PREVIOUS COMMENTS.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC 507.1.SUPPLY FIXED LADDER OR | | | RELOCATE HEATER TO FLOOR.HEATERS LOCATED | | | ABOVE THE FIRST FLOOR CEILING SHALL | | | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC | | | SEC.507.8.1.LADDER IS NOT SHOWN ON ARCH. | | | DRAWINGS. | | | | | | SUBMIT COPY OF APPROVAL FROM WPB | | | UTILITIES DEPT.FOR GREASE TRAP.CONTACT | | | R.COMPO AT 561-835-7423. | | | | | | AN ADDITIONAL WATER CLOSET IS REQD.IN | | | MALE AND FEMALE RESTROOMS PER TABLE 407 | | | OF SPC AND SEC.407.2.2. | | | | | | SIZE DROPS TO GAS EQUIPMENT TO ENSURE | | | COMPLIANCE W/SGC TABLE 305.4(A).THE | | | TABLE REFERENCED ON THE PLANS DOES NOT | | | EXIST IN THE SGC. | | | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | | REACHED AT 561-659-8096,EXT.8377. | | | T.LARGE PLUMBING PLANS EXAMINER. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2000-07-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2000-07-19 |
Time |
09:01 |
Rev Time |
0.50 |
| Received By |
tlarge |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | PLUMBING PLAN REVIEW | | | (1) PREVIOUS COMMENTS DATED 06-06-00 | | | NOT ADDRESSED,(22) ITEMS. | | | END OF COMMENTS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
tlarge |
Date |
2000-06-06 |
Time |
17:48 |
Rev Time |
3.50 |
| Received By |
tlarge |
Date |
2000-06-06 |
Time |
17:47 |
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | SHT.A0.1-CLARIFY OCCUPANCY GROUP.PLANS | | | NOTE A-3.THERE IS NO SUCH CLASSIFICATION | | | IN THE STANDARD BUILDING CODE. | | | | | | PLANS SHALL BE ROUTED TO DEPT.OF | | | BUSINESS REGULATION FOR REVIEW.COUNTY- | | | WIDE AMENDMENTS TO SPC SEC.101.4.7. | | | | | | URINAL SHALL BE INSTALLED AT HANDICAP | | | HEIGHT PER FACBC SEC.4.18.2. | | | | | | SHT.A7.1-INDICATE ROOM FINISHES.TOILET | | | ROOMS AND RESTROOMS SHALL COMPLY W/SBC | | | SEC.1204.2. | | | | | | ALL FLOOR SINKS,HAND SINKS,FLOOR DRAINS, | | | ETC.IN THE FOOD PREP/KITCHEN AREA SHALL | | | DISCHARGE THROUGH THE GREASE INTERCEPTOR | | | PER SPC SEC.1004.4. | | | | | | PUMPED DISCHARGE SYSTEM(EJECTORS)SHALL | | | COMPLY W/SPC SEC.717.2-717.11.SUBMIT | | | INFO ON BASIN,PUMPS,ETC.COMPLY W/SPC | | | FOR CONNECTION TO SANITARY SYSTEM. | | | | | | SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. | | | ALL EQUIPMENT SHALL BE LISTED PER SGC | | | SEC.402.1 AND NFPA 54. | | | | | | SHOW ALL CUT DIMENSIONS OF GAS PIPING, | | | TYPE OF GAS,LOCATION OF GAS METER, | | | DELIVERY PRESSURE,AND SUBMIT COPY OF OR | | | REFERENCE APPLICABLE SIZING TABLE USED | | | IN SYSTEM DESIGN.SGC SEC 305.4. | | | | | | SUBMIT DETAIL OF GAS MANIFOLD.COMPLIANCE | | | W/NFPA 54 SHALL BE REQUIRED FOR DISTANCE | | | TO SOURCE OF IGNITION IF APPLICABLE. | | | | | | THE LAYOUT OF THE 2ND FLR.TOILET ROOMS | | | IS NOT CONSTANT THROUGHOUT THE DRAWINGS. | | | CLARIFY CORRECT LAYOUT.COUNTYWIDE AMEND- | | | MENTS TO SPC SEC.104.2.1. | | | | | | THE SCHEMATIC FOR THE GREASY WASTE DOES | | | NOT CORRELATE W/THE PLAN DRAWING.PLEASE | | | REVISE.SEE SHT.P5. | | | | | | FLOOR SINKS AND FLOOR DRAINS ARE NOT | | | PROPERLY VENTED.SPC SEC.901.2. | | | | | | VENT CONNECTIONS TO EXIST.ARE SHOWN AS | | | 3"ON P2 AND AS 2"0N P-5.CLARIFY. | | | | | | SCHEMATIC "A" DOESN'T CORRELATE W/FLOOR | | | PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC. | | | 104.2.1. | | | | | | WASTE AND VENT RISER "A"-WATER CLOSETS | | | AND FIXTURE BRANCHES NOT PERMITTED ON | | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | | SPC SEC.911.1.1.CIRCUIT AND LOOP SYSTEM | | | SHALL COMPLY W/SPC SEC.914.1 IF THAT IS | | | THE INTENT. | | | | | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | | SEC.610.4.1,610.4.2. | | | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | | PER SPC SEC.507.1.SUPPLY FIXED LADDER OR | | | RELOCATE TO FLOOR.HEATERS LOCATED ABOVE | | | THE 1ST FLOOR CEILING SHALL COMPLY W/ | | | COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.1 | | | | | | WATER FILTRATION SYSTEM SHALL BE NSF | | | APPROVED PER SPC SEC.615.1.SUBMIT INFO. | | | | | | FLOOR DRAINS ARE REQUIRED IN THE FIRST | | | FLOOR TOILET ROOMS PER SPC SEC.409.4.1.1 | | | AND SHALL BE EQUIPPED W/TRAP PRIMERS. | | | | | | THE SIZE OF THE HANDICAP TOILET STALLS | | | SHALL COMPLY W/FACBC 4.17.3 AND FIG.30. | | | | | | A UNION OR FLANGED CONNECTION IS REQD. | | | DOWNSTREAM OF F.A.VALVE PER NFPA 54 SEC. | | | 5.5.3. | | | | | | APPROVAL FOR GREASE TRAP CAPACITY IS | | | REQD.FROM CITY OF WPB UTILITIES.CONTACT | | | R.COMPO AT 561-835-7423. | | | | | | IF THERE ARE ANY QUESTIONS YOU MAY | | | CONTACT ME AT (561)659-8096,EXT.8377. |
|
|