Plan Review Details - Permit 00051840
Plan Review Stops For Permit 00051840
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2000-08-15 Cont ID  
Sent By bstaples Date 2000-08-15 Time 12:50 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PRIVSO:
 ALL EXTERIOR GLAZING WINDOWS AND DOORS
 PROVIDE PRODUCT APPROVAL FOR WIND LOADS
 1997 SBC 110 MPH CHAPTER 16 AND IMPACT
 PROTECTION AS PER SSTD 12-97 SBC OR
 METRO DADE COUNTY.
 APPLY FOR AND PAY FEES UNDER SEPERATE
 PERMIT FOR GLAZING SYSTEM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2000-08-14 Cont ID  
Sent By drunnels Date 2000-08-14 Time 13:43 Rev Time 1.00
Received By drunnels Date 2000-08-14 Time 13:43 Sent To  
Notes
2001-01-08 00:00:00 
  
 1.PROVIDE FLORIDA ENERGY SHEETS SIGNED
 BY OWNER/AGENT AND SIGNED AND SEALED BY
 ENG.
 2. PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE COUNTY PRODUCT APPROVALS FOR
 WINDOWS.
 3.PROVIDE WIND LOAD CALUCLATIONS THAT
 COMPLY WITH 1997 BSC CHAPTER 16 FOR
 STROEFRONT.
 4. FIRE RATING OF WALL ASSEMBLIES NOT
 INDICATED, PROVIDE UL LISTING, SEE TABLE
 704.1 1997 SBC ASSEMBLEY TO OTHER
 OCCUPANCIES, 1ST & 2ND FLOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2000-07-27 Cont ID  
Sent By drunnels Date 2000-07-27 Time 11:32 Rev Time 1.00
Received By drunnels Date 2000-07-27 Time 11:19 Sent To  
Notes
2001-01-08 00:00:00 
  
  
  
  
 1. SUBMIT PLANS SHOWING THAT MEZZANIE
 COMPLIES WITH 1997 SBC CHAPTER 5
 SECTION 505.2.3, & CHAPTER 10 SECTION
 1004.1.5, 1005.7, 1007.8 AND THE
 1997 FLORIDA HANDICAP CODE
 2. PROVIDE FLORIDA ENERGY CODE SHEETS
 SIGNED BY THE OWNER.
 3. PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE COUNTY PRODUCT APPROVALS
 FOR WINDOWS
 4. PROVIDE WIND LOAD CALUCLATIONS THAT
 COMPLY WITH 1997 SBC CHAPTER 16 FOR
 STOREFRONT.
 5. FIRE RATING OF WALL ASSEMBLIES NOT
 INDICATED, PROVIDE LISTING, SEE TABLE
 704.1 1997 SBC, SMALL ASSEMBLEY TO
 OTHER OCCUPANCIES.1ST & 2ND FLOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2000-07-19 Cont ID  
Sent By fknapp Date 2000-07-19 Time 14:09 Rev Time 0.00
Received By fknapp Date   Time   Sent To  
Notes
2001-01-08 00:00:00 
 **************REVIEW NOTES**************
  
  
 1)PROVIDE RAISE SEAL OF ENGINEER THAT
 PREPARED ENERGY SHEETS.
  
 2)FIRE SPRINKLER CONTRACTOR TO APPLY FOR
 PERMIT PRIOR TO ISSUANCE BUILDING PERMIT
  
  
 3)PROVIDE WINDLOAD CALCULATIONS THAT
 COMPLY WITH 1997 SBC CHAPTER 16 FOR
 STORE FRONT.
  
 4)PROVIDE CURRENT COPIES OF SBCCI OR
 METRO DADE PRODUCT APPROVALS FOR WINDOWS
  
 5)FABRIC TERRACE REQUIRES SEPARATE
 PERMIT.
  
 6)SIGNS REQUIRE SEPARATE PERMITS.
  
 7)FIRE RATINGS OF WALL ASSEMBLIES NOT
 INDICATED, PROVIDE LISTING, SEE TABLE
 704.1 1997 SBC SMALL ASSEMBLEY TO OTHER
 OCCUPANCIES. FIRST AND SECOND FLOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2000-06-29 Cont ID  
Sent By bstaples Date 2000-06-29 Time 13:31 Rev Time 2.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:001. FLORIDA ENERGY SHEETS SHOW COMPLIANCE
 WITH 1997 FLORIDA ENERGY CODE.
 2. FIRE SPRINKLER PALNS AND CONTRACTOR
 TO APPLY FOR PERMIT PRIOR TO ISSUANCE OF
 THE BUILDING PERMIT.
 3. STORE FRONT, PROVIDE STRUCTURAL
 DETAILS FOR STORE FRONT MEET 1997 SBC
 CHAPTER 16.
 4. WINDOWS SHEET A3.1 PROVIDE PRODUCT
 APPROVAL INFORMATION MEET SSTD12-97 OR
 METRO DADE COUNTY.
 5. FABRIC TERRACE REQUIRES SEPERATE
 PERMIT.
 6. SIGNS REQUIRE SEPERATE PERMITS.
 7. FIRE RATINGS OF WALL ASSEMBLIES NOT
 INDICATED PROVIDE LISTING SEE TABLE
 704.1, 1997 SBC SMALL ASSEMBLEY TO
 OTHER OCCUPANCIES. FIRST AND SECOND
 FLOOR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-08-14 Cont ID  
Sent By dpalmer Date 2000-08-14 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2000-08-14 Time 12:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-19 Cont ID  
Sent By dpalmer Date 2000-07-19 Time 12:05 Rev Time 0.00
Received By dpalmer Date 2000-07-19 Time 12:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-05 Cont ID  
Sent By dpalmer Date 2000-06-05 Time 19:09 Rev Time 0.00
Received By jleahy Date 2000-08-18 Time 07:59 Sent To  
Notes
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS OF ALL
 MAIN DISCONNECTS/PANELS. MAINS/PANELS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9/215-5
  
 2)NOTE: PLEASE NOTE YOU ARE SHOWING A
 150KVA TRANSFORMER WITH 150C TEMP RISE.
 PLEASE SEE ART;450-21-B EXCEPT. #1
 MUST HAVE TEMP RISE 155 C.
 PLEASE ADJUST OR TRANSFORMER MUST BE
 INSTALLED IN TRANSFORMER VAULT/ROOM
 UNDER NEC. REQ`MENTS.
  
 3)NOTE: YOU SHOW PANEL "HVPP" ON SHEET
 E-6. PLEASE INCLUDE THIS ON THE ONE-LINE
 RISER DIAGRAM. 215-5
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS!
 LOAD CALCULATIONS TO MEET REQ`MENTS OF
 THE NEC. ALSO PLEASE INCLUDE ALL LOADS
 THAT MAY BE CONTINUOUS. (LIGHTING ETC)
 PLEASE SUBMIT THE BREAK DOWN ON EACH
 PANEL AND TOTAL LOAD ON MAIN LVMDP.
 PLEASE SUBMIT THE LOAD CALCULATION FOR
 PANEL "HVPP". SHOW BREAK DOWN ON LOADS
 AND SHOW LOADS OF EQUIPMENT.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW.IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2000-08-15 Cont ID  
Sent By mcarsill Date 2000-08-15 Time 09:04 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) HANDRAILS AND GUARDS TO COMPLY WITH
 NFPA 101, LIFE SAFETY CODE, 1985 EDITION
 2) SUBMIT COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FORT FIRE ALARM EQUIPMENT
 SHOWN ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2000-08-09 Cont ID  
Sent By mcarsill Date 2000-08-09 Time 17:39 Rev Time 0.00
Received By mcarsill Date   Time   Sent To  
Notes
2001-01-08 00:00:001) ALL FABRIC AWNINGS ARE TO BE FLAME
 RETARDANT.
 2) HYDRAULIC CALCULATION SUMMARY IS NOT
 CORRECT. WHERE DID THESE FIGURES COME
 FROM.
 3) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 4) PROVIDE FIRE ALARM SYSTEM DRAWINGS
 FOR FIRE ALARM SYSTEM EQUIPMENT SHOWN
 ON PLANS. A SEPARATE PLAN AND PERMIT
 REQUIRED.
 5) OCCUPANT LOAD TO BE DETERMINED BY
 THIS OFFICE.
 6) PORTABLE FIRE EXTINGUISHERS REQUIRED.
 7) PROVIDE COMPLETE HOOD, DUCT, AND
 EXTINGUISHING PLANS. A SEPARATE PERMIT
 IS REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-06-29 Cont ID  
Sent By bstaples Date 2000-06-29 Time 12:46 Rev Time 1.00
Received By bstaples Date   Time   Sent To  
Notes
2001-01-08 00:00:00PROVISO ATTACHED TO PLANS M. CARSILLO

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-08-14 Cont ID  
Sent By cthirben Date 2000-08-14 Time 07:49 Rev Time 0.00
Received By cthirben Date 2000-08-14 Time 07:49 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 SEPERATE PERMIT REQUIRED FOR HOODS, WALK
 -IN COOLERS/FREEZERS AND SUPPRESSION
 SYSTEM. SUBMIT PLANS AT TIME OF PERMIT
 APPLICATION FOR THESE SYSTEM....

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-18 Cont ID  
Sent By cthirben Date 2000-07-18 Time 13:48 Rev Time 0.00
Received By cthirben Date 2000-07-18 Time 13:51 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 COMMENTS ON REVIEW DATED 06.05.00 DONE
 BY NCD HAS BEEN ADDRESSED ON THIS REVIEW
 ***SEPERATE PERMITS REQUIRED FOR HOODS,
 WALK-IN COOLERS/FREEZERS AND FIRE SUPPR-
 ESSION SYSTEMS. SUBMIT PLANS AT TIME OF
 PERMIT APPLICATION FOR THESE SYSTEMS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-05 Cont ID  
Sent By ndenmark Date 2000-06-05 Time 15:30 Rev Time 1.00
Received By bstaples Date 2000-06-05 Time 15:30 Sent To  
Notes
2001-01-08 00:00:00**************DENIED*******************
  
 1) OUTSIDE AIR REQUIRED PER ASHRAE 62-89
 2) PROVIDE AIR BALANCE SCHEDULE PER 1997
 501.2
 3) SPECIFY MATERIALS FOR AIR DUCTS
 4) DUCT SMOKE DETECTORS TO BE TIED TO
 BUILDING FIRE ALARM SYSTEM PER NFPA 90A
 5) EQUIPMENT ON ROOF TO PROVIDE MIN.
 CLEARANCE OF 18" BETWEEN SURFACE OF ROOF
 AND BOTTOM OF SUPPORT STRUCTURE OF STAND
 FOR ROOF ACCESS UNDER EQUIPMENT PER
 LOCAL ORDINANCE
 6) SEPERATE PERMITS REQUIRED FOR HOODS,
 WALKIN COOLERS/FREEZERS, AND SUPPRESSION
 SYSTEMS. SUBMIT PLANS AT TIME OF PERMIT
 APPLICATION FOR THESE SYSTEMS

Review Stop P PLUMBING
Rev No 4 Status P Date 2000-08-14 Cont ID  
Sent By pschmitz Date 2000-08-14 Time 06:12 Rev Time 3.00
Received By pschmitz Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEWPROVISO:
 REF SPC 94, SGC 97
 (1)
  
  
  
  
 (2) SHT P-5 ANSUL VALVE FA TO BE
 INSTALLED BELOW CEILING.
 (3) SHT M-3 ALL A/C CONDENSATE DRAINS,
 TO BE CONNECTED TO COMMON SYSTEM,
 PROVIDED B/O.
 END OF COMMENTS ANY QUESTIONS
 CONTACT PAUL SCHMITZ 561-659-8096 X 8233

Review Stop P PLUMBING
Rev No 3 Status F Date 2000-07-28 Cont ID  
Sent By tlarge Date 2000-07-28 Time 19:42 Rev Time 2.00
Received By tlarge Date 2000-07-28 Time 18:32 Sent To  
Notes
2001-01-08 00:00:00PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW AND
 APPROVAL.SUBMIT APPROVAL DOCUMENTATION
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.101.4.7.
  
 ALL FLOOR SINKS ,HAND SINKS,FLOOR DRAINS
 ETC.IN THE FOOD PREP/KITCHEN/BAR AREAS
 SHALL DISCHARGE THRU THE GREASY WASTE
 SYSTEM EXCEPT THE DISHWASHER AND THE
 FOOD WASTE GRINDER.SPC 1004.4.
  
 THE GAS MANIFOLD AT THE METER SHALL
 COMPLY W/NFPA 54 FOR DISTANCE FROM
 SOURCE OF IGNITION.THIS WILL BE SUBJECT
 TO FIELD INSPECTION AND IF FOUND TO BE
 IN VIOLATION SHALL BE RELOCATED.THIS
 ISSUE WAS ADDRESSED ON THE SHELL
 BUILDING AND REQUIRES COMPLIANCE.
  
 A SIGNED,SEALED AND DATED SANITARY AND
 WATER ISOMETRIC DRAWING SHALL BE
 SUBMITTED FOR REVIEW PRIOR TO PLUMBING
 INSPECTION.THE DRAWINGS SHALL CORRELATE
 WITH THE FLOOR PLANS AND COMPLY W/SPC
 FOR DESIGN IN ALL RESPECTS.THERE ARE
 TOO MANY VIOLATIONS OF THE CODE TO LIST.
 SEE PREVIOUS COMMENTS.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC 507.1.SUPPLY FIXED LADDER OR
 RELOCATE HEATER TO FLOOR.HEATERS LOCATED
 ABOVE THE FIRST FLOOR CEILING SHALL
 COMPLY W/COUNTYWIDE AMENDMENTS TO SPC
 SEC.507.8.1.LADDER IS NOT SHOWN ON ARCH.
 DRAWINGS.
  
 SUBMIT COPY OF APPROVAL FROM WPB
 UTILITIES DEPT.FOR GREASE TRAP.CONTACT
 R.COMPO AT 561-835-7423.
  
 AN ADDITIONAL WATER CLOSET IS REQD.IN
 MALE AND FEMALE RESTROOMS PER TABLE 407
 OF SPC AND SEC.407.2.2.
  
 SIZE DROPS TO GAS EQUIPMENT TO ENSURE
 COMPLIANCE W/SGC TABLE 305.4(A).THE
 TABLE REFERENCED ON THE PLANS DOES NOT
 EXIST IN THE SGC.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 T.LARGE PLUMBING PLANS EXAMINER.

Review Stop P PLUMBING
Rev No 2 Status F Date 2000-07-19 Cont ID  
Sent By pschmitz Date 2000-07-19 Time 09:01 Rev Time 0.50
Received By tlarge Date   Time   Sent To  
Notes
2001-01-08 00:00:00PLUMBING PLAN REVIEW
 (1) PREVIOUS COMMENTS DATED 06-06-00
 NOT ADDRESSED,(22) ITEMS.
 END OF COMMENTS

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-06 Cont ID  
Sent By tlarge Date 2000-06-06 Time 17:48 Rev Time 3.50
Received By tlarge Date 2000-06-06 Time 17:47 Sent To  
Notes
2001-01-08 00:00:00SHT.A0.1-CLARIFY OCCUPANCY GROUP.PLANS
 NOTE A-3.THERE IS NO SUCH CLASSIFICATION
 IN THE STANDARD BUILDING CODE.
  
 PLANS SHALL BE ROUTED TO DEPT.OF
 BUSINESS REGULATION FOR REVIEW.COUNTY-
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
  
 URINAL SHALL BE INSTALLED AT HANDICAP
 HEIGHT PER FACBC SEC.4.18.2.
  
 SHT.A7.1-INDICATE ROOM FINISHES.TOILET
 ROOMS AND RESTROOMS SHALL COMPLY W/SBC
 SEC.1204.2.
  
 ALL FLOOR SINKS,HAND SINKS,FLOOR DRAINS,
 ETC.IN THE FOOD PREP/KITCHEN AREA SHALL
 DISCHARGE THROUGH THE GREASE INTERCEPTOR
 PER SPC SEC.1004.4.
  
 PUMPED DISCHARGE SYSTEM(EJECTORS)SHALL
 COMPLY W/SPC SEC.717.2-717.11.SUBMIT
 INFO ON BASIN,PUMPS,ETC.COMPLY W/SPC
 FOR CONNECTION TO SANITARY SYSTEM.
  
 SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT.
 ALL EQUIPMENT SHALL BE LISTED PER SGC
 SEC.402.1 AND NFPA 54.
  
 SHOW ALL CUT DIMENSIONS OF GAS PIPING,
 TYPE OF GAS,LOCATION OF GAS METER,
 DELIVERY PRESSURE,AND SUBMIT COPY OF OR
 REFERENCE APPLICABLE SIZING TABLE USED
 IN SYSTEM DESIGN.SGC SEC 305.4.
  
 SUBMIT DETAIL OF GAS MANIFOLD.COMPLIANCE
 W/NFPA 54 SHALL BE REQUIRED FOR DISTANCE
 TO SOURCE OF IGNITION IF APPLICABLE.
  
 THE LAYOUT OF THE 2ND FLR.TOILET ROOMS
 IS NOT CONSTANT THROUGHOUT THE DRAWINGS.
 CLARIFY CORRECT LAYOUT.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.
  
 THE SCHEMATIC FOR THE GREASY WASTE DOES
 NOT CORRELATE W/THE PLAN DRAWING.PLEASE
 REVISE.SEE SHT.P5.
  
 FLOOR SINKS AND FLOOR DRAINS ARE NOT
 PROPERLY VENTED.SPC SEC.901.2.
  
 VENT CONNECTIONS TO EXIST.ARE SHOWN AS
 3"ON P2 AND AS 2"0N P-5.CLARIFY.
  
 SCHEMATIC "A" DOESN'T CORRELATE W/FLOOR
 PLAN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 WASTE AND VENT RISER "A"-WATER CLOSETS
 AND FIXTURE BRANCHES NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.CIRCUIT AND LOOP SYSTEM
 SHALL COMPLY W/SPC SEC.914.1 IF THAT IS
 THE INTENT.
  
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1,610.4.2.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.507.1.SUPPLY FIXED LADDER OR
 RELOCATE TO FLOOR.HEATERS LOCATED ABOVE
 THE 1ST FLOOR CEILING SHALL COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC.507.8.1
  
 WATER FILTRATION SYSTEM SHALL BE NSF
 APPROVED PER SPC SEC.615.1.SUBMIT INFO.
  
 FLOOR DRAINS ARE REQUIRED IN THE FIRST
 FLOOR TOILET ROOMS PER SPC SEC.409.4.1.1
 AND SHALL BE EQUIPPED W/TRAP PRIMERS.
  
 THE SIZE OF THE HANDICAP TOILET STALLS
 SHALL COMPLY W/FACBC 4.17.3 AND FIG.30.
  
 A UNION OR FLANGED CONNECTION IS REQD.
 DOWNSTREAM OF F.A.VALVE PER NFPA 54 SEC.
 5.5.3.
  
 APPROVAL FOR GREASE TRAP CAPACITY IS
 REQD.FROM CITY OF WPB UTILITIES.CONTACT
 R.COMPO AT 561-835-7423.
  
 IF THERE ARE ANY QUESTIONS YOU MAY
 CONTACT ME AT (561)659-8096,EXT.8377.