Plan Review Details - Permit 00051838
Plan Review Stops For Permit 00051838
Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2000-06-02 Cont ID  
Sent By cthirben Date 2000-06-02 Time 12:46 Rev Time 0.50
Received By cthirben Date 2000-06-02 Time 12:44 Sent To  
Notes
2001-01-08 00:00:00*****************PROVISO****************
 MECHANICAL PERMIT FOR A/C DROP IN BATH-
 ROOM AND EXHAUST FAN REQUIRED IN BATH-
 ROOM PER SMC 503.3.

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-06-02 Cont ID  
Sent By tlarge Date 2000-06-02 Time 11:58 Rev Time 0.50
Received By tlarge Date 2000-06-02 Time 11:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-01 Cont ID  
Sent By tlarge Date 2000-06-01 Time 20:18 Rev Time 0.50
Received By tlarge Date 2000-06-01 Time 20:18 Sent To  
Notes
2001-01-08 00:00:00BATHROOM SHALL BE HANDICAP ACCESSIBLE
 PER FACBC SEC.4.1.3.(11),4.1.6.(1)(B).
  
 SUBMIT DETAILS/MOUNTING HEIGHT OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/FACBC OCT.1997 EDITION.
  
 DOOR TO TOILET ROOM SHALL COMPLY W/SEC.
 4.13 OF FACBC.
  
 SHOW TURNING SPACE FOR WHEELCHAIR PER
 FACBC SEC.4.2.3.
  
 SUBMIT WATER RISER FOR REVIEW PER COUNTY
 WIDE AMENDMENTS TO SPC SEC.104.2.1.
  
 SHOW FIXTURE CLEARANCE OF WATER CLOSET
 FROM WALL TO CENTER OF W.C.COMPLY W/
 FACBC FIG.28.
  
 FLOOR AND WALLS SHALL BE NONABSORBENT TO
 A HEIGHT OF 4'PER SBC SEC.1204.2.
  
 A FLOOR DRAIN W/TRAP PRIMER IS REQD.IN
 THE TOILET ROOM PER SPC SEC.409.4.1.1.