| Notes |
| 2001-01-08 00:00:00 | 1) FIRE ALARM SYSTEM TO BE AUDIBLE | | | THROUGHOUT THE BUILDING WHEN ACTIVATED. | | | 2) SMOKE DETECTORS TO BE A MINIMUM OF | | | THREE FEET FROM AC DIFFUSERS. | | | 3) FIRE ALARM SYSTEM TO BE CLASS A OR | | | ADDRESSABLE. | | | 4) FIRE ALARM SYSTEM TO BE MONITORED BY | | | A LICENSED UL LISTED CENTRAL STATION. | | | 5) SYSTEM SUBJECT TO COMPLETE INSPECTION | | | AFTER INSTALLATION. |
|
|
|