Plan Review Details - Permit 00051675
Plan Review Stops For Permit 00051675
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-13 Cont ID  
Sent By dpalmer Date 2000-06-13 Time 19:13 Rev Time 0.00
Received By dpalmer Date 2000-06-13 Time 19:13 Sent To  
Notes
2001-01-08 00:00:00***************** UNSAT ***************
  
 1)NOTE: SHEET #2 SHOWS 150A METER/MAIN
 COMBO. SHEET #3 SHOWS 200 AMP ???
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 MAIN. MAINS MUST BE RATED FOR THE AVAIL-
 ABLE FAULT CURRENT. 110-9
  
 3)NOTE; PLEASE LIST ON PANEL SCHEDULE
 THE REQ` DEDICATED FOR BATH(S). 210-11-
 C-3.
  
 4)NOTE:SUBMIT CORRECTED LOAD CALCULATION
 -S TO MEET NEC. SHOW LOAD CALCS.215-5
  
 5)NOTE: PLEASE SHOW THE OOUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6
  
 6)NOTE:MISSING OUTLETFOR 210-52E AND
 GFI FOR A/C COMPRESSOR.
  
 PLEASE SHOW ANY REAR DOOR AND EGRESS
 LIGHTING 210-70 AND WHAT IS ROOM OFF THE
 KITCHEN?LOOKS LIKE 3RD BEDROOM IF SO
 A SD WILL BE REQ`D .
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372