| Notes |
| 2001-01-08 00:00:00 | ***************** UNSAT *************** | | | | | | 1)NOTE: SHEET #2 SHOWS 150A METER/MAIN | | | COMBO. SHEET #3 SHOWS 200 AMP ??? | | | PLEASE CORRELATE. | | | | | | 2)NOTE: PLEASE SUBMIT THE AIC RATING FOR | | | MAIN. MAINS MUST BE RATED FOR THE AVAIL- | | | ABLE FAULT CURRENT. 110-9 | | | | | | 3)NOTE; PLEASE LIST ON PANEL SCHEDULE | | | THE REQ` DEDICATED FOR BATH(S). 210-11- | | | C-3. | | | | | | 4)NOTE:SUBMIT CORRECTED LOAD CALCULATION | | | -S TO MEET NEC. SHOW LOAD CALCS.215-5 | | | | | | 5)NOTE: PLEASE SHOW THE OOUTLETS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED. 210-8-A-6 | | | | | | 6)NOTE:MISSING OUTLETFOR 210-52E AND | | | GFI FOR A/C COMPRESSOR. | | | | | | PLEASE SHOW ANY REAR DOOR AND EGRESS | | | LIGHTING 210-70 AND WHAT IS ROOM OFF THE | | | KITCHEN?LOOKS LIKE 3RD BEDROOM IF SO | | | A SD WILL BE REQ`D . | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL 659-8096 EXT 8372 |
|
|
|