| 2001-01-08 00:00:00 | CHECKLIST: |
| | 1-DRAWINGS ARE VERY INCOMPLETE. WALL |
| | SECTION LACKS A LOT OF INFORMATION. |
| | ROOF FRAMING PLAN LACKS CONNECTION |
| | DETAILS. IT'S NOT CLEAR WHAT'S EXIST'G |
| | OR NEW. |
| | 2-EXIT FROM BEDROOM CAN NOT BE THRU THE |
| | BATHROOM. SECTION 1001.1.3 SBC 1997. |
| | 3-PERMIT APPLICATION CALLS FOR CHANGE |
| | OF ROOFING FINISH FOR CEMENT TILE. |
| | CLARIFY WHAT'S EXISTING FINISH. IF IT |
| | IS SHINGLES, THEN PROVIDE A LETTER |
| | FROM ENGINEER CERTIFYING THAT THE |
| | EXISTING ROOF FRAMING SYSTEM WILL |
| | SAFELY SUPPORT THE ADDITIONAL LOAD. |
| | 4-SPECIFY SIZE AND TYPE OF WINDOW AT THE |
| | BEDROOM TO VERIFY THAT IT MEETS THE |
| | EGRESS REQUIREMENTS OF SECTION 1005.4 |
| | OF SBC 1997. |
| | 5-FOR BATHROOM VENTILATION PROVIDE A |
| | WINDOW THAT PROVIDES NOT LESS THAN 8% |
| | GLAZED AREA OF THE ROOM AREA AND WHEN |
| | WINDOW IS OPEN THE TOTAL OPEN SPACE |
| | SHALL BE NOT LESS THAN HALF THE REQ'D |
| | WINDOW AREA. OR PROVIDE MECHANICAL |
| | VENTILATION. SECTION 1203.4.2 SBC 1997 |
| | 6-SEE COMMENTS ON PLANS AND REVISE ALL |
| | ORIGINAL DRAWINGS AS REQUIRED. |
| | INCLUDING COMMENTS BY THE OTHER TRADES |
| | 7-PROVIDE CURRENT PRODUCT APPROVALS FOR: |
| | EXTERIOR DOORS AND WINDOWS, ROOF TILE |
| | 8-PROVIDE COMPLETE CONSTRUCTION DETAIL/ |
| | SECTION AT SCREEN ENCLOSURE. SECTION |
| | 104.2.2 CITY AMENDMENTS TO SBC 1997. |
| | 9-SPECIFY LUMBER GRADE TO BE USED AT NEW |
| | PORCH AND VERIFY MAX SPAN AND SPACING |
| | ACCORDINGLY. SEC 104.2 CITY AMENDMENTS |
| | 10-ENGINEER NEEDS TO DATE HIS DRAWINGS |
| | AT TIME OF IMPRESSING HIS SEAL. |
| | CHAPTER 471 FLORIDA STATUTES. |
| | 11-CHECK/VERIFY TYPE OF ROOFING FINISH |
| | SPECIFIED AT NEW PORCH. ACCORDING TO |
| | THE DRAWINGS IT LOOKS LIKE THERE IS |
| | A "FLAT" ROOF (NOTE: 1/4" PER FOOT MIN |
| | SLOPE FOR FLAT ROOFS AS PER SECTION |
| | 1503.1.2.3 OF SBC 1997. |
| | FLAT ROOF REQUIRES A FLAT ROOF FINISH |
| | SYSTEM. SPECIFY SYSTEM AND PROVIDE |
| | CURRENT PRODUCT APPROVAL AS WELL. |
| | 12-OWES $82.90 FOR LOW VALUATION AND |
| | RADON FEES. PLEASE PAY ATTACHED |
| | RECEIPT. |
| | |
| | |
| | |
| | |
| | |
| | NOTE: |
| | PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE IN ORIGINALS IN |
| | ORDER TO EXPEDITE THE REVIEW PROCESS. |