Plan Review Details - Permit 00051663
Plan Review Stops For Permit 00051663
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-27 Cont ID  
Sent By dpalmer Date 2000-06-27 Time 18:19 Rev Time 0.00
Received By dpalmer Date 2000-06-27 Time 18:19 Sent To  
Notes
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE:SMOKE DETECTORS REQ`D INSIDE AND
 OUTSIDE BEDROOM. NFPA-72 2-2.1.1.1
  
 2)NOTE: MISSING OUTLET SPACING TO MEET
 CODE IN BEDROOM. 210-52
  
 3)NOTE: MISSING EGRESS LIGHTING PER
 CODE 210-70
  
 4)NOTE: PLEASE LABEL ALL OULTETS FOR
 PORCH AS GFI/GFI PROTECTED. 210-8
  
 5)NOTE: PLEASE PROVIDE REVISED PANEL
 SCHEDULE SHOWING THE REQ`D DEDICATED
 CIRCUIT FOR BATH(S). MUST BE #12 AND 20A
 AS PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2000-07-03 Cont ID  
Sent By cthirben Date 2000-07-03 Time 09:03 Rev Time 0.00
Received By cthirben Date   Time 09:02 Sent To  
Notes
2001-01-08 00:00:00NOTES: SPOKE TO NELDA ORTIZ ON 07.03.00
 AT 9:03AM, AND WAS INFORMED THAT THE
 BEDROOM ADDITION HAS A/C.
 PROVISO:PROVIDE DUCT SIZE AND LOCATION.
 PROVIDE CFM VALUE OF THE BATHROOM.
 BATHROOM REQUIRES AN EXHAUST FAN OR THE
 WINDOW TO BE 3 SQ. FT. PER 1997 SMC
 503.3.1

Review Stop P PLUMBING
Rev No 1 Status P Date 2000-07-02 Cont ID  
Sent By tlarge Date 2000-07-02 Time 07:19 Rev Time 0.33
Received By tlarge Date 2000-07-02 Time 07:19 Sent To  
Notes
2001-01-08 00:00:00PROVISO:SHOWER SHALL BE A MIN.OF 30"WIDE
 AND A MIN.OF 1024 SQ.IN.PER COUNTYWIDE
 AMENDMENTS 409.8.
  
 SUBMIT SANITARY RISER DIAGRAM FOR REVIEW
 PRIOR TO PLUMBING INSPECTION.RISER SHALL
 BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL OF RECORD.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2000-07-12 Cont ID  
Sent By jgomez Date 2000-07-12 Time 19:52 Rev Time 2.00
Received By jgomez Date 2000-07-12 Time 19:52 Sent To  
Notes
2001-01-08 00:00:00CHECKLIST:
 1-DRAWINGS ARE VERY INCOMPLETE. WALL
 SECTION LACKS A LOT OF INFORMATION.
 ROOF FRAMING PLAN LACKS CONNECTION
 DETAILS. IT'S NOT CLEAR WHAT'S EXIST'G
 OR NEW.
 2-EXIT FROM BEDROOM CAN NOT BE THRU THE
 BATHROOM. SECTION 1001.1.3 SBC 1997.
 3-PERMIT APPLICATION CALLS FOR CHANGE
 OF ROOFING FINISH FOR CEMENT TILE.
 CLARIFY WHAT'S EXISTING FINISH. IF IT
 IS SHINGLES, THEN PROVIDE A LETTER
 FROM ENGINEER CERTIFYING THAT THE
 EXISTING ROOF FRAMING SYSTEM WILL
 SAFELY SUPPORT THE ADDITIONAL LOAD.
 4-SPECIFY SIZE AND TYPE OF WINDOW AT THE
 BEDROOM TO VERIFY THAT IT MEETS THE
 EGRESS REQUIREMENTS OF SECTION 1005.4
 OF SBC 1997.
 5-FOR BATHROOM VENTILATION PROVIDE A
 WINDOW THAT PROVIDES NOT LESS THAN 8%
 GLAZED AREA OF THE ROOM AREA AND WHEN
 WINDOW IS OPEN THE TOTAL OPEN SPACE
 SHALL BE NOT LESS THAN HALF THE REQ'D
 WINDOW AREA. OR PROVIDE MECHANICAL
 VENTILATION. SECTION 1203.4.2 SBC 1997
 6-SEE COMMENTS ON PLANS AND REVISE ALL
 ORIGINAL DRAWINGS AS REQUIRED.
 INCLUDING COMMENTS BY THE OTHER TRADES
 7-PROVIDE CURRENT PRODUCT APPROVALS FOR:
 EXTERIOR DOORS AND WINDOWS, ROOF TILE
 8-PROVIDE COMPLETE CONSTRUCTION DETAIL/
 SECTION AT SCREEN ENCLOSURE. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 9-SPECIFY LUMBER GRADE TO BE USED AT NEW
 PORCH AND VERIFY MAX SPAN AND SPACING
 ACCORDINGLY. SEC 104.2 CITY AMENDMENTS
 10-ENGINEER NEEDS TO DATE HIS DRAWINGS
 AT TIME OF IMPRESSING HIS SEAL.
 CHAPTER 471 FLORIDA STATUTES.
 11-CHECK/VERIFY TYPE OF ROOFING FINISH
 SPECIFIED AT NEW PORCH. ACCORDING TO
 THE DRAWINGS IT LOOKS LIKE THERE IS
 A "FLAT" ROOF (NOTE: 1/4" PER FOOT MIN
 SLOPE FOR FLAT ROOFS AS PER SECTION
 1503.1.2.3 OF SBC 1997.
 FLAT ROOF REQUIRES A FLAT ROOF FINISH
 SYSTEM. SPECIFY SYSTEM AND PROVIDE
 CURRENT PRODUCT APPROVAL AS WELL.
 12-OWES $82.90 FOR LOW VALUATION AND
 RADON FEES. PLEASE PAY ATTACHED
 RECEIPT.
  
  
  
  
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE IN ORIGINALS IN
 ORDER TO EXPEDITE THE REVIEW PROCESS.

Review Stop Z ZONING
Rev No 1 Status P Date 2000-06-06 Cont ID  
Sent By gjoyce Date 2000-06-06 Time 08:19 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***