B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2000-06-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2000-06-06 |
Time |
14:16 |
Rev Time |
1.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2001-01-08 00:00:00 | DENIED | | | | | | 1)PROVIDE SPECIFIC DETAILS FOR ATTACHING | | | ANTENNA TO STRUCTURE. SPECIFY SPECIFIC | | | TYPE OF ANCHORS TO BE USED AND | | | STRUCTURAL MATERIAL OF BUILDING TO WHICH | | | UNIT WILL BE ANCHORED. | | | | | | 2)PROVIDE CALCULATIONS WHICH SHOW THAT | | | THE METHOD OF ATTACHMENT OF ANTENNA TO | | | STRUCTURE IS CAPABLE OF WITHSTANDING THE | | | CALCULATED WIND LOADS. | | | | | | 3)WIND LOAD CALCULATIONS MUST BE | | | DETERMINED BY ASCE 7-95 OR 1999 STANDARD | | | BUILDING CODE SECTION 1606.2. PLEASE | | | REFERENCE ONE OF THESE WHEN SUBMITTING | | | LOAD CALCULATIONS. |
|
|