Plan Review Details - Permit 00051623
Plan Review Stops For Permit 00051623
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2000-07-24 Cont ID  
Sent By hpiskura Date 2000-07-24 Time 10:05 Rev Time 99.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2000-09-13 Cont ID  
Sent By dpalmer Date 2000-09-13 Time 10:06 Rev Time 0.00
Received By dpalmer Date 2000-09-13 Time 10:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2000-07-07 Cont ID  
Sent By dpalmer Date 2000-07-07 Time 12:24 Rev Time 0.00
Received By dpalmer Date 2000-07-07 Time 12:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2000-06-14 Cont ID  
Sent By dpalmer Date 2000-06-14 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2000-06-14 Time 12:09 Sent To  
Notes
2001-01-08 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT A REVISED LOAD
 CALCULATION IN CLUDING ALL CONTIUOUS
 LOADS AT 125%. (LIGHTING ETC.) PLEASE
 INCLUDE TRACK LIGHTINGFOR IT`S SEPAR-
 -ATE LOAD CALCULATION PER 220-12-B
  
 2)NOTE: PLEASE SHOW FIGURES FOR SQ.FT
 PER 220 OF THE NEC.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2000-07-13 Cont ID  
Sent By cthirben Date 2000-07-13 Time 07:37 Rev Time 1.00
Received By cthirben Date 2000-07-13 Time 07:36 Sent To  
Notes
2001-01-08 00:00:00NOTES:
 APPROVED BY RHETT TURNQUEST ON 06.07.00

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2000-09-07 Cont ID  
Sent By ndenmark Date 2000-09-07 Time 09:54 Rev Time 0.33
Received By ndenmark Date 2000-09-07 Time 09:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2000-07-13 Cont ID  
Sent By cthirben Date 2000-07-13 Time 07:23 Rev Time 1.00
Received By cthirben Date 2000-07-13 Time 07:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2000-06-13 Cont ID  
Sent By ndenmark Date 2000-06-13 Time 15:39 Rev Time 1.00
Received By ndenmark Date 2000-06-13 Time 15:39 Sent To  
Notes
2001-01-08 00:00:00**************DENIED********************
  
 1) PROVIDE AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2
 2) OUTSIDE AIR TOTALS ON (M-2) EQUIPMENT
 SCHEDULE DO NOT MATCH CALCULATIONS (AIR
 PROVIDED) FIGURES ON M-1

Review Stop P PLUMBING
Rev No 2 Status P Date 2000-07-12 Cont ID  
Sent By tlarge Date 2000-07-12 Time 10:58 Rev Time 0.65
Received By tlarge Date 2000-07-12 Time 10:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2000-06-05 Cont ID  
Sent By tlarge Date 2000-06-05 Time 08:47 Rev Time 1.75
Received By tlarge Date 2000-06-04 Time 10:05 Sent To  
Notes
2001-01-08 00:00:00SUBMIT SANITARY RISER THAT COMPLIES W/
 SPC.WATER CLOSETS AND FIXTURE BRANCHES
 ARE NOT PERMITTED ON WET VENTS PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 SIZE THE COLD WATER LINES TO THE LAVS IN
 THE WOMEN'S R.R.COMPLY W/SPC SEC.607.
  
 A MIN.OF 29" IS REQUIRED UNDER THE LAV.
 FROM FINISH FLOOR TO BOTTOM OF APRON PER
 FACBC SEC.4.19.2.
  
 TOILET PAPER DISPENSER SHALL BE LOCATED
 A MIN.OF 19"TO CENTER PER FACBC 4.16.6